District cooling pipes - Bonded single pipe systems for directly buried cold water networks - Part 3: Factory made steel valve assembly for steel or plastic service pipe, polyurethane thermal insulation and a casing of polyethylene

This document specifies requirements, design and test methods for factory made thermally insulated bonded valve assemblies for directly buried district cooling distribution systems, comprising a steel valve from DN 15 to DN 1200, rigid polyurethane foam insulation and a casing of polyethylene.
The valve assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document applies only to insulated valve assemblies, for continuous operation with water at various temperatures (1 to 30) °C and a maximum operation pressure of 25 bar.
The design is based on an expected service life with continuous operation of a minimum 50 years.
NOTE   An expected service life of 50 years presupposes that treated water is used.

Fernkälterohre - Einrohr-Verbundsysteme für direkt erdverlegte Fernkältenetze - Teil 3: Werkmäßig gefertigte Stahlarmaturenbaueinheiten für Stahl- oder Kunststoff-Mediumrohre, einer Wärmedämmung aus Polyurethan und einer Ummantelung aus Polyethylen

Dieses Dokument legt die Anforderungen, Auslegung und Prüfverfahren für werkmäßig gefertigte, wärmegedämmte Verbundmantel-Stahlarmaturenbaueinheiten für direkt erdverlegte Fernkälte-netzwerke fest, die aus einer Stahlarmatur von DN 15 bis DN 1 200, einer Polyurethan-Hartschaumstoff¬dämmung und einem Polyethylenmantel bestehen.
Die Absperrarmatur kann darüber hinaus die folgenden zusätzlichen Bauteile umfassen: Messdrähte, Abstandhalter und Diffusionsbarrieren.
Dieses Dokument ist nur anzuwenden für gedämmte Absperrarmaturen, für den Dauerbetrieb mit Wasser bei verschiedenen Temperaturen (1 °C bis 30 °C) und einem Betriebsdruck von höchstens 25 bar.
Die Auslegung basiert auf einer erwarteten Lebensdauer von mindestens 50 Jahren bei Dauerbetrieb.
ANMERKUNG Bei der erwarteten Lebensdauer von 50 Jahren wird die Verwendung von aufbereitetem Wasser vorausgesetzt.

Réseaux d’eau glacée - Systèmes bloqués de tuyaux pour les réseaux d'eau glacée enterrés directement — Partie 3 : Assemblages d'appareils de robinetterie manufacturés pour tubes de service en acier ou en plastique, isolation thermique en polyuréthane et tube de protection en polyéthylène

Le présent document spécifie les exigences, la conception et les méthodes d’essai pour des assemblages manufacturés d’appareils de robinetterie bloqués préisolés thermiquement pour les réseaux de distribution d’eau glacée urbains enterrés directement, constitués d’un appareil de robinetterie en acier de DN 15 à DN 1200, d’une isolation en mousse de polyuréthane rigide et d’un tube de protection en polyéthylène.
L’assemblage d’appareils de robinetterie peut également comprendre les éléments supplémentaires suivants : les câbles de mesure, les entretoises et les barrières anti diffusion.
Ce document ne concerne que les assemblages d’appareils de robinetterie, destinés à un usage continu avec de l’eau à diverses températures (de 1 à 30) °C et à une pression de service maximale de 25 bar.
La conception est fondée sur une durée utile prévue en fonctionnement continu d’au moins 50 ans.
NOTE   Une durée utile prévue de 50 ans présuppose l'utilisation d'eau traitée.

Cevi za daljinsko hlajenje - Spojeni enocevni sistemi za neposredno vkopana hladnovodna omrežja - 3. del: Tovarniško izdelan sestav jeklenih ventilov iz jeklene ali plastične delovne cevi, poliuretanske toplotne izolacije in polietilenskega plašča

General Information

Status
Published
Publication Date
31-Aug-2021
Withdrawal Date
30-Mar-2022
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
01-Sep-2021
Due Date
01-Mar-2022
Completion Date
01-Sep-2021

Buy Standard

Standard
EN 17415-3:2021 - BARVE
English language
30 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2021
Cevi za daljinsko hlajenje - Spojeni enocevni sistemi za neposredno vkopana
hladnovodna omrežja - 3. del: Tovarniško izdelan sestav jeklenih ventilov iz
jeklene ali plastične delovne cevi, poliuretanske toplotne izolacije in
polietilenskega plašča
District cooling pipes - Bonded single pipe systems for directly buried cold water
networks - Part 3: Factory made steel valve assembly for steel or plastic service pipe,
polyurethane thermal insulation and a casing of polyethylene
Fernkälterohre - Einzelrohr-Verbundsysteme für direkt erdverlegte Fernkältenetze - Teil
3: Werkmäßig gefertigte Stahl-Absperrarmaturen für Stahl- oder Kunststoff-
Mediumrohre, einer Wärmedämmung aus Polyurethan und einer Ummantelung aus
Polyethylen
Réseaux d’eau glacée - Systèmes bloqués de tuyaux pour les réseaux d'eau glacée
enterrés directement — Partie 3 : Assemblages d'appareils de robinetterie manufacturés
pour tubes de service en acier ou en plastique, isolation thermique en polyuréthane et
tube de protection en polyéthylène
Ta slovenski standard je istoveten z: EN 17415-3:2021
ICS:
23.040.99 Drugi sestavni deli za Other pipeline components
cevovode
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 17415-3
EUROPEAN STANDARD
NORME EUROPÉENNE
September 2021
EUROPÄISCHE NORM
ICS 23.040.99
English Version
District cooling pipes - Bonded single pipe systems for
directly buried cold water networks - Part 3: Factory made
steel valve assembly for steel or plastic service pipe,
polyurethane thermal insulation and a casing of
polyethylene
Réseaux d'eau glacée - Systèmes bloqués de tuyaux Fernkälterohre - Einzelrohr-Verbundsysteme für
pour les réseaux d'eau glacée enterrés directement - direkt erdverlegte Fernkältenetze - Teil 3: Werkmäßig
Partie 3 : Assemblages d'appareils de robinetterie gefertigte Stahl-Absperrarmaturen für Stahl- oder
manufacturés pour tubes de service en acier ou en Kunststoff-Mediumrohre, einer Wärmedämmung aus
plastique, isolation thermique en polyuréthane et tube Polyurethan und einer Ummantelung aus Polyethylen
de protection en polyéthylène
This European Standard was approved by CEN on 18 July 2021.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 17415-3:2021 E
worldwide for CEN national Members.

Contents Page
European foreword . 3
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 6
4 Requirements . 6
4.1 Pressure ratings for valves . 6
4.2 Service temperatures for valves . 6
4.3 Steel parts . 6
4.4 Casing . 8
4.5 Polyurethane (PUR) foam thermal insulation . 8
4.6 Valve assembly . 8
4.7 Requirements for effective operation and maintenance . 10
4.8 Resistance to axial forces and bending moments. 10
5 Testing, test methods and test requirements . 10
5.1 General . 10
5.2 Test specimens . 10
5.3 Steel parts . 11
5.4 Casing . 16
5.5 Polyurethane (PUR) foam thermal insulation . 16
5.6 Valve assembly . 16
5.7 Surveillance system . 16
6 Marking . 16
6.1 General . 16
6.2 Steel valve . 17
6.3 Casing . 17
6.4 Valve assembly . 17
7 Installation and maintenance . 17
Annex A (informative) Guidelines for inspection and testing . 18
Annex B (normative) Resistance to axial force and bending moment . 20
Annex C (normative) Resistance to bending forces . 25
Annex D (informative) Waste treatment and recycling . 29

European foreword
This document (EN 17415-3:2021) has been prepared by Technical Committee CEN/TC 107
“Prefabricated district heating and district cooling pipe system”, the secretariat of which is held by DS.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by March 2022, and conflicting national standards shall
be withdrawn at the latest by March 2022.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
Introduction
Factory made bonded single pipe systems for directly buried district cooling networks are of common
technical usage. In order to ensure quality including product-related service life, to ensure safety in use,
economical energy usage and to facilitate comparability in the market, CEN/TC 107 decided to set up
standards for these products.
This document is one of a series of standards which form several parts of EN 17415, District cooling
pipes – Bonded single pipe systems for directly buried cold water networks:
— Part 1: Factory made pipe assembly of steel or plastic service pipe, polyurethane thermal insulation
and a casing of polyethylene;
— Part 2: Factory made fitting assemblies of steel or plastic service pipe, polyurethane thermal insulation
and a casing of polyethylene;
— Part 3: Factory made steel valve assembly for steel or plastic service pipe, polyurethane thermal
insulation and a casing of polyethylene (this document).
The other standards from CEN/TC 107 covering this subject are:
— EN 17414-1, District cooling pipes — Factory made flexible pipe systems — Part 1: Classification,
general requirements and test methods;
— EN 17414-2, District cooling pipes — Factory made flexible pipe systems — Part 2: Bonded system
with plastic service pipes; requirements and test methods;
— EN 17414-3, District cooling pipes — Factory made flexible pipe systems — Part 3: Non bonded system
with plastic service pipes; requirements and test methods;
— EN XXXXX-1, District cooling pipes — Design and installation of thermal insulated bonded single and
twin pipe systems for directly buried cold water networks — Part 1: Design;
— EN XXXXX-2, District cooling pipes — Design and installation of thermal insulated bonded single and
twin pipe systems for directly buried cold water networks — Part 2: Installation;
— EN 489-1, District heating pipes — Bonded single and twin pipe systems for buried hot water
networks — Part 1: Joint casing assemblies and thermal insulation for hot water networks in
accordance with EN 13941-1;
— EN 14419, District heating pipes — Bonded single and twin pipe systems for directly buried hot water
networks — Surveillance systems.
Waste management and recycling of materials is dealt with in Annex D.

1 Under development.
1 Scope
This document specifies requirements, design and test methods for factory made thermally insulated
bonded valve assemblies for directly buried district cooling distribution systems, comprising a steel
valve from DN 15 to DN 1 200, rigid polyurethane foam insulation and a casing of polyethylene.
The valve assembly can also include the following additional elements: measuring wires, spacers and
diffusion barriers.
This document applies only to insulated valve assemblies, for continuous operation with water at
various temperatures (1 to 30) °C and a maximum operation pressure of 25 bar.
The design is based on an expected service life with continuous operation of a minimum 50 years.
NOTE An expected service life of 50 years presupposes that treated water is used.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 19, Industrial valves - Marking of metallic valves
EN 736-1, Valves - Terminology - Part 1: Definition of types of valves
EN 1092-1, Flanges and their joints - Circular flanges for pipes, valves, fittings and accessories, PN
designated - Part 1: Steel flanges
EN 10088-1, Stainless steels - Part 1: List of stainless steels
EN 10204, Metallic products - Types of inspection documents
EN 12201-2:2011+A1:2013, Plastics piping systems for water supply, and for drainage and sewerage
under pressure - Polyethylene (PE) - Part 2: Pipes
EN 12266-1, Industrial valves - Testing of metallic valves - Part 1: Pressure tests, test procedures and
acceptance criteria - Mandatory requirements
EN 13941-1, District heating pipes - Design and installation of thermal insulated bonded single and twin
pipe systems for directly buried hot water networks - Part 1: Design
EN 14419, District heating pipes - Bonded single and twin pipe systems for buried hot water net
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.