EN 998-2:2003
(Main)Specification for mortar for masonry - Part 2: Masonry mortar
Specification for mortar for masonry - Part 2: Masonry mortar
This part of EN 998 specifies requirements for masonry mortars (bedding, jointing and pointing) for use in masonry (e.g. facing and rendered masonry, loadbearing or non-loadbearing masonry structures, including internal linings and partitions, for building and civil engineering).
Festlegungen für Mörtel im Mauerwerksbau - Teil 2: Mauermörtel
Diese Europäische Norm legt die Anforderungen für im Werk hergestellten Mauermörtel (für Lager-, Stoß- und Längsfugen, Fugenglattstrich, nachträgliches Verfugen) zur Verwendung in Wänden, Pfeilern und Trennwänden aus Mauerwerk (z. B. Verblendmauerwerk und verputztes Mauerwerk, tragende und nichttragende Mauerwerkskonstruktionen für Hoch- und Tiefbauten) fest.
Diese Europäische Norm beschreibt für Frischmörtel die Leistungsanforderungen in Bezug auf Chloridgehalt, Luftgehalt, Rohdichte, Verarbeitbarkeitszeit und Korrigierbarkeitszeit (nur für Dünnbettmörtel). Für Festmörtel werden die Leistungsanforderungen z.B. in Bezug auf Druckfestigkeit, Verbundfestigkeit und Rohdichte definiert. Alle Eigenschaften werden nach den entsprechend festgelegten Prüfver-fahren, die in gesonderten Europäischen Normen enthalten sind, ermittelt.
Diese Europäische Norm stellt ein Verfahren zum Nachweis der Übereinstimmung der Produkte mit dieser Europäischen Norm zur Verfügung.
Anforderungen an die Kennzeichnung der von dieser Europäischen Norm abgedeckten Produkte sind enthalten.
Diese Norm gilt für Mauermörtel nach Abschnitt 3 mit Ausnahme von Baustellenmörtel. Diese Norm oder Teile davon können jedoch in Zusammenhang mit Anwendungsvorschriften und nationalen Festlegungen auch für Baustellenmörtel angewendet werden.
Définitions et spécifications des mortiers pour maçonnerie - Partie 2: Mortiers de montage des éléments de maçonnerie
La présente Norme européenne spécifie les exigences applicables aux mortiers industriels (de montage, jointoiement et rebouchage) utilisés dans les murs, poteaux et cloisons en maçonnerie (par exemple, maçonnerie apparente ou à enduire, structures de maçonnerie porteuse ou non, destinés au bâtiment et au génie civil).
Pour les mortiers frais, la présente norme définit les performances des propriétés relatives à la durée pratique d'utilisation, la teneur en chlorure, l'air occlus, la masse volumique et le temps ouvert (pour les mortiers de joints minces) et, pour les mortiers durcis, les performances des caractéristiques liées à la résistance à la compression, l'adhérence et la masse volumique. Toutes les performances sont mesurées selon les méthodes d'essai correspondantes définies dans des Normes européennes distinctes.
La présente Norme européenne traite également de l'évaluation de la conformité des produits à la présente norme ainsi que de leur marquage.
La présente Norme européenne s'applique aux mortiers de montage définis à l'article 3, à l'exception des mortiers préparés sur chantier. Toutefois, tout ou partie de cette norme peut être utilisée en association avec des codes de mise en �uvre et des spécifications nationales relatives aux mortiers préparés sur chantier.
Specifikacija malt za zidanje – 2. del: Malta za zidanje
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 998-2:2004
01-januar-2004
Specifikacija malt za zidanje – 2. del: Malta za zidanje
Specification for mortar for masonry - Part 2: Masonry mortar
Festlegungen für Mörtel im Mauerwerksbau - Teil 2: Mauermörtel
Définitions et spécifications des mortiers pour maçonnerie - Partie 2: Mortiers de
montage des éléments de maçonnerie
Ta slovenski standard je istoveten z: EN 998-2:2003
ICS:
91.100.10 Cement. Mavec. Apno. Malta Cement. Gypsum. Lime.
Mortar
SIST EN 998-2:2004 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
EUROPEAN STANDARD
EN 998-2
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2003
ICS 91.100.10 Supersedes EN 998-2:2001
English version
Specification for mortar for masonry - Part 2: Masonry mortar
Spécifications des mortiers pour maçonnerie - Partie 2: Festlegungen für Mörtel im Mauerwerksbau - Teil 2:
Mortiers de montage Mauermörtel
This European Standard was approved by CEN on 2 October 2002.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2003 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 998-2:2003 E
worldwide for CEN national Members.
---------------------- Page: 2 ----------------------
EN 998-2:2003 (E)
Contents
page
Foreword . 3
Introduction . 4
1 Scope. 5
2 Normative references. 5
3 Terms and definitions. 6
4 Materials. 8
5 Requirements . 8
5.1 General . 8
5.2 Properties of fresh mortar. 8
5.3 Proportion of constituents . 8
5.4 Properties of hardened mortar .9
5.5 Additional requirements for thin layer mortars . 10
5.6 Reaction to fire . 10
5.7 Mixing of mortar on site . 11
6 Designation of masonry mortar. 11
7 Marking and labelling. 12
8 Evaluation of conformity . 12
8.1 General . 12
8.2 Initial type tests . 12
8.3 Factory production control . 13
(normative)
Annex A Sampling for initial type testing and independent testing of consignments15
Annex B (informative) Use of masonry units and masonry mortar. 16
Annex C (normative) Characteristic initial shear strength of designed masonry mortars. 18
Annex ZA (informative) Clauses of this European Standard addressing the provisions of EU
Construction Products Directive. 19
2
---------------------- Page: 3 ----------------------
EN 998-2:2003 (E)
Foreword
This document (EN 998-2:2003) has been prepared by Technical Committee CEN/TC125 "Masonry",
the Secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by October 2003, and conflicting national standards
shall be withdrawn at the latest by January 2005.
This document supersedes EN 998-2:2001.
This European Standard has been prepared under a mandate given to CEN by the European
Commission and the European Free Trade Association and supports the essential requirements of
the EU Construction Products Directive (89/106/EEC).
It also takes into account the general rules for reinforced and unreinforced masonry in Eurocode 6.
For relationship with EU Directives, see informative Annex ZA which is an integral part of this
standard.
In this European Standard the Annexes A and C are normative and the Annex B is informative.
EN 998 Specification for mortar for masonry consists of:
Part 1: Rendering and plastering mortar.
Part 2: Masonry mortar.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Czech
Republic, Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg,
Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and the United
Kingdom.
3
---------------------- Page: 4 ----------------------
EN 998-2:2003 (E)
Introduction
The properties required of a mortar are related to its use.
They are considered in two groups viz.: those relating to the fresh, unhardened mortar and those to
the hardened mortar.
To support the aim of achieving a performance-related standard, as far as practicable, the standard
refers only to the properties of the product and not to its method of manufacture, except where this is
unavoidable in the description of the characteristics of the product.
4
---------------------- Page: 5 ----------------------
EN 998-2:2003 (E)
1 Scope
This European Standard specifies requirements for factory made masonry mortars (bedding, jointing
and pointing) for use in masonry walls, columns and partitions (e.g. facing and rendered masonry,
load bearing or non-load bearing masonry structures for building and civil engineering).
This European Standard defines for fresh mortars the performance related to workable life, chloride
content, air content, density and correction time (for thin-layer mortars only). For hardened mortars it
defines e.g. performances related to compressive strength, bond strength, density measured
according to the corresponding test methods contained in separate European Standards.
This European Standard provides for the evaluation of conformity of the product to this European
Standard.
The marking requirement for products covered by this European Standard is included.
This European Standard covers masonry mortars defined in clause 3 with the exception of site made
mortars. However, this standard or part of this standard may be used in conjunction with codes of
applications and National specifications covering site made mortars.
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies (including
amendments).
EN 771, Specification for masonry units.
EN 1015-1, Methods of test for mortar for masonry — Part 1: Determination of particle size distribution
(by sieve analysis).
EN 1015-2, Methods of test for mortar for masonry — Part 2: Bulk sampling of mortars and
preparation of test mortars.
EN 1015-7, Methods of test for mortar for masonry — Part 7: Determination of air content of fresh
mortar.
EN 1015-9, Methods of test for mortar for masonry — Part 9: Determination of workable life and
correction time of fresh mortar.
EN 1015-10, Methods of test for mortar for masonry — Part 10: Determination of dry bulk density of
hardened mortar.
EN 1015-11, Methods of test for mortar for masonry — Part 11: Determination of flexural and
compressive strength of hardened mortar.
EN 1015-17, Methods of test for mortar for masonry — Part 17: Determination of water soluble
chloride content of fresh mortar.
EN 1015-18, Methods of test for mortar for masonry — Part 18: Determination of water absorption
coefficient due to capillary action of hardened mortar.
EN 1745:2002, Masonry and masonry products — Methods for determining design thermal values.
5
---------------------- Page: 6 ----------------------
EN 998-2:2003 (E)
EN 13501-1, Fire classification of construction products and building elements — Part 1: Classification
using test data from reaction to fire tests.
3 Terms and definitions
For the purposes of this European Standard, the following terms and definitions apply.
3.1
masonry mortar
mix of one or more inorganic binders, aggregates, water, and sometimes additions and/or admixtures
for bedding, jointing and pointing of masonry
3.1.1
fresh masonry mortar
mortar completely mixed and ready for use
3.2 Type of masonry mortar, defined according to concept
3.2.1
designed masonry mortar
mortar whose composition and manufacturing method is chosen by the producer in order to achieve
specified properties (performance concept)
3.2.2
prescribed masonry mortar
mortar made in predetermined proportions, the properties of which are assumed from the stated
proportion of the constituents (recipe concept)
3.3 Type of masonry mortar, defined according to properties and/or use
3.3.1
general purpose masonry mortar (G)
masonry mortar without special characteristics
3.3.2
thin layer masonry mortar (T)
designed masonry mortar with a maximum aggregate size less than or equal to a prescribed figure
(see 5.5.2)
3.3.3
lightweight masonry mortar (L)
designed masonry mortar with a dry hardened density below a prescribed figure (see 5.4.5)
3.4 Type of masonry mortar, defined according to the mode of manufacture
3.4.1
factory made masonry mortar
mortar batched and mixed in a factory. It may be "dry mortar" which is ready-mixed, only requiring the
addition of water or "wet mortar" which is supplied ready for use
3.4.2
semi-finished factory made masonry mortar
mortar described in either 3.4.2.1 or 3.4.2.2
6
---------------------- Page: 7 ----------------------
EN 998-2:2003 (E)
3.4.2.1
prebatched masonry mortar
mortar whose constituents are wholly batched in a factory, supplied to the building site and mixed
there according to the manufacturer's specification and conditions
3.4.2.2
premixed lime-sand- masonry mortar
mortar whose constituents are wholly batched and mixed in a factory, supplied to the building site
where further constituents specified or provided by the factory are added (e.g. cement)
3.4.3
site-made masonry mortar
mortar composed of individual constituents batched and mixed on the building site
3.5
binder
material used to hold solid particles together in a coherent mass, e.g. cement, building lime
3.6
aggregate
granular material that does not contribute to the hardening reaction of the mortar
3.7
admixture
material added in small quantities to produce specified modifications to the properties
3.8
addition
finely divided inorganic material (which is not an aggregate or binder) that may be added to mortar in
order to improve or achieve special properties
3.9
bond strength
adhesion perpendicular to the bed between the masonry mortar and the masonry unit
3.10
declared value
value that a manufacturer is confident in achieving, bearing in mind the precision of test and variability
of process
3.11
masonry subjected to severe exposure
masonry or elements of masonry which are subjected to saturation with water (driving rain, ground
water) combined with frequent freeze/thaw-cycling due to climatic conditions, and absence of
protective features
3.12
masonry subjected to moderate exposure
masonry or elements of masonry which are exposed to moisture and freeze/thaw-cycling, excluding
constructions subjected to severe exposure
3.13
masonry subjected to passive exposure
masonry or elements of masonry which are not intended to be exposed to moisture and freezing
conditions
7
---------------------- Page: 8 ----------------------
EN 998-2:2003 (E)
4 Materials
Raw materials shall have characteristics permitting the finished product to conform to the
requirements of this standard. The manufacturer shall keep records of how suitability of materials is
established.
5 Requirements
5.1 General
The requirements and properties specified in this standard shall be defined in terms of the test
methods and other procedures referred to in this standard. The conformity criteria given in the
following sub-clauses relate to initial type tests (see 8.2) and consignments testing (in accordance
with Annex A). For production evaluation the manufacturer shall define the conformity criteria in the
factory production control documentation (see 8.3).
5.2 Properties of fresh mortar
5.2.1 Workable life
The workable life shall be declared by the manufacturer. When the masonry mortar is sampled from a
consignment in accordance with EN 1015-2 and tested in accordance with EN 1015-9 the workable
life shall not be less than the declared value.
5.2.2 Chloride content
When relevant, the chloride content of the mortar as delivered shall be declared by the manufacturer.
When sampled from a consignment in accordance with EN 1015-2 and either tested in accordance
with EN 1015-17 using the procedure for determining water soluble chloride content or using a
calculation based on measured chloride ion content of the constituents of the mortar, the chloride
content shall not be higher than the declared value.
NOTE The chloride content should not exceed 0,1 % Cl of the mortar by dry mass.
5.2.3 Air content
When relevant for the use for which the masonry mortar is placed on the market the range in which
the air content will fall shall be declared by the manufacturer. When sampled from a consignment in
accordance with EN 1015-2 and tested in accordance with EN 1015-7 the air content shall fall within
the declared range.
For masonry mortar where porous aggregates are used the air content may alternatively be
determined by testing the fresh mortar density according to EN 1015-6.
5.3 Proportion of constituents
For prescribed mortars the mix proportions by volume or by weight of all the constituents shall be
declared by the manufacturer. In addition, the compressive strength shall be declared using publicly
available references establishing relationship between mix proportions and compressive strength.
8
---------------------- Page: 9 ----------------------
EN 998-2:2003 (E)
5.4 Properties of hardened mortar
5.4.1 Compressive strength
For designed mortars the compressive strength of masonry mortar shall be declared by the
manufacturer. The manufacturer may declare the compressive strength class in accordance with
Table 1, where the compressive strength is designated by an 'M' followed by the compressive
strength class in N/mm², which it exceeds.
Table 1 — Mortar classes
Class M 1 M 2,5 M 5 M 10 M 15 M 20 M d
Compressive strength
12,5 5 10 15 20 d
2
N/mm
2
d is a compressive strength greater than 25 N/mm declared by the manufacturer.
When the masonry mortar is sampled from a consignment in accordance with EN 1015-2 and tested
in accordance with EN 1015-11 the compressive strength shall not be less than the declared
compressive strength or the declared compressive strength class. It shall be declared if the air-lime
content calculated as calcium hydroxide Ca(OH) is equal to or higher than 50 % of the total amount
2
of binder mass.
5.4.2 Bond strength
For designed masonry mortars intended to be used in elements subjected to structural requirements
the bond strength of the mortar in combination with a masonry unit shall be declared in terms of the
characteristic initial shear strength. The declaration may be made either on the basis of tests as a)
below or tabulated values as b) below. The manufacturer shall declare the basis for his declaration.
a) Declaration based on tests
The characteristic initial shear strength of the mortar in combination with a specific type of unit in
accordance with EN 771 may be based on tests on mortar sampled from a consignment in
accordance with EN 1015-2 and tested with the relevant unit in accordance with EN 1052-3. The
characteristic initial shear strength shall not be less than the declared value;
b) Declaration based on tabulated values
When no declaration is made under a) the characteristic initial shear strength of the mortar in
combination with a range of unit types shall be declared by reference to Annex C.
NOTE 1 Bond strength depends on the mortar, the masonry unit, its moisture content and the
workmanship.
NOTE 2 Until a direct method of test for bond strength is available the test for initial shear strength is to be
used.
5.4.3 Water absorption
For masonry mortars intended to be used in external elements and exposed directly to the weather,
the water absorption shall be declared by the manufacturer. When sampled from a consignment in
accordance with EN 1015-2 and tested in accordance with EN 1015-18, the water absorption shall not
be higher than the declared value.
9
---------------------- Page: 10 ----------------------
EN 998-2:2003 (E)
5.4.4 Water vapour permeability
For masonry mortars intended to be used in external elements, the water vapour permeability shall be
declared by the manufacturer by reference to EN 1745:2002, Table A.12 giving tabulated values for
water vapour diffusion coefficient for mortar.
5.4.5 Density (dry hardened mortar)
When relevant for the use for which the masonry mortar is placed on the market the range in which
the density of dry hardened mortar will fall shall be declared by the manufacturer. When the masonry
mortar is sampled from a consignment in accordance with EN 1015-2 and tested in accordance with
EN 1015-10 the density shall fall within the declared range.
For lightweight masonry mortars the density shall be equal to or less than 1 300 kg/m³.
5.4.6 Thermal conductivity
For masonry mortars intended to be used in elements subject to thermal requirements the
manufacturer shall give design values for the thermal conductivity of the masonry mortar by reference
to EN 1745:2002, Table A.12. Especially for lightweight masonry mortars, measured values according
to EN 1745:2002, 4.2.2 may alternatively be declared. The manufacturer shall declare the basis for
his declaration. When the masonry mortar is sampled from a consignment in accordance with EN
1015-2 and tested in accordance with EN 1745 the thermal conductivity shall be less than the
declared value.
5.4.7 Durability
Until a European Standard method of test is available, the freeze/thaw resistance shall be evaluated
and declared to the provisions valid in the intended place of use of the mortar.
5.5 Additional requirements for thin layer mortars
5.5.1 General
Thin layer mortars shall comply with the requirements described in 5.2 and 5.4 and with the following
additional requirements.
5.5.2 Aggregates
The aggregate size shall be not greater than 2 mm when the masonry mortar is sampled from a
consignment in accordance with EN 1015-2 and tested in accordance with EN 1015-1. The
manufacturer shall declare the maximum grain size.
5.5.3 Correction time
The correction time shall be declared. When the masonry mortar is sampled from a consignment in
accordance with EN 1015-2 and tested according to EN 1015-9, the correction time shall be greater
than the declared value.
5.6 Reaction to fire
The manufacturer shall declare the reaction to fire classification of the masonry mortar.
Masonry mortars containing a mass or volume fraction of 1,0 % (whichever is the most onerous) of
homogeneously distributed organic materials are classified as reaction to fire Class A1 without the
need to test.
10
---------------------- Page: 11 ----------------------
EN 998-2:2003 (E)
Masonry mortars containing a mass or volume fraction of > 1,0 % (whichever is the most onerous) of
homogeneously distributed organic materials shall be classified in accordance with EN 13501-1 and
the appropriate reaction to fire class declared.
NOTE Attention is drawn to the Commission Decision 96/603/EC, as amended, in which non-combustible
masonry units containing not more than a mass or volume fraction of 1,0 % (whichever is the more onerous)
of homogeneously distributed organic materials are classified as reaction to fire Class A 1 without testing.
5.7 Mixing of mortar on site
If certain types of mortar need specific site mixing equipment procedures or times, these shall be
specified by the manufacturer. Mixing time is measured from the time when all constituents have been
added.
6 Designation of masonry mortar
The designation shall include the following, as relevant:
number and date of issue of this European Standard;
name of manufacturer;
a code for or the date of production;
type of mortar ( 3.2, 3.3 and 3.4);
workable life (5.2.1);
chloride content (5.2.2);
air content (5.2.3);
proportion of constituents (for prescribed mortars) and relationship to compressive strength or
compressive strength class (5.3);
compressive strength, or compressive strength class (for designed mortars) (5.4.1);
bond strength ( 5.4.2);
water absorption (5.4.3);
water vapour permeability (5.4.4);
density (5.4.5);
thermal conductivity (5.4.6);
durability (5.4.7);
maximum aggregate grain size (5.5.2);
correction time (5.5.3);
reaction to fire (5.6).
11
---------------------- Page: 12 ----------------------
EN 998-2:2003 (E)
NOTE In the designation for a product, information about special qualities may be included when the mortar
is intended for use in special construction.
7 Marking and labelling
The designation (see clause 6) or code identifying the designation shall be marked on the packaging,
the delivery ticket or the manufacturers data sheet or other information accompanying the product.
NOTE For CE marking and labelling ZA.3 applies. When annex ZA.3 requires the CE marking to be
accompanied by the same information as required by this clause the requirements of this clause can be
considered to have been met.
8 Evaluation of conformity
8.1 General
The manufacturer (or his agent) shall demonstrate compliance for his product with the requirements of
this European Standard and with declared values by carrying out both initial type testing (see 8.2) and
factory production control (see 8.3).
Alternative methods of test to the reference methods specified in this European Standard may be
adopted except for the initial type tests and in case of dispute, provided that these alternative
methods satisfy the following:
a) a relationship can be shown to exist between the results from the reference test and those from
the alternative test; and
b) the information on which the relationship is based is available.
8.2 Initial type tests
8.2.1 General
After completion of the development of a new product type and before commencement of
manufacture and offering for sale appropriate initial type tests shall be carried out to confirm that the
properties predicted from the development meet the requirements of this standard and the values to
be declared for the product.
Sampling shall be carried out in accordance with annex A.
Initial type tests shall also be carried out on existing products when a change in the basic materials or
manufacturing procedures lead to what the manufacturer consider will change the product designation
or the use of the product. In these cases the appropriate initial type tests are those for the properties
which are affected or need confirming and new properties introduced by a change of use.
The results of initial type tests shall be recorded. No tests need to be carried out where a declaration
of tabulated values is allowed.
The tests to be conducted shall be reference tests as described in this standard for the properties
selected from the following list in accordance with 8.2.2 and 8.2.3, consistent with the product type's
intended use.
12
---------------------- Page: 13 ----------------------
EN 998-2:2003 (E)
NOTE For the performance characteristics to be determined in order to address the CE marking
provisions, see Table ZA.1.
8.2.2 Fresh mortar properties
workable life;
chloride content;
air content;
correction time (for thin layer mortars);
aggregate size (for thin layer mortars).
8.2.3 Hardened mortar properties
compressive strength;
bond strength;
water absorption;
water vapour permeability;
density;
thermal conductivity;
reaction to fire (for mortars containing > 1 % of organic materials).
durability
8.3 Factory production control
8.3.1 General
A factory production control scheme shall be established and documented in a manual. The factory
production control system shall consist of procedures for internal control of the production to ensure
that such products placed on the market conform to this standard and the declared values. The
internal control will consist of one or both of the following:
a) Regular inspections, checks and tests and the utilization of the results to control equipment, raw
or incoming materials and the production process;
b) Regular inspections, checks and tests on the finished product.
Records shall be maintained of the dates of tests and inspections, identification of the products
tested, and the results of the tests or inspections as indicated in the quality manual.
8.3.2 Process control
The items to be addressed in the quality documents relating to the system of control chosen from
8.3.1 are given below:
1) Incoming materials
13
---------------------- Page: 14 ----------------------
EN 998-2:2003 (E)
As appropriate the manufacturer shall define the acceptance criteria of incoming materials and the
procedures that he operates to ensure that these are met;
2) Production process
As appropriate the relevant features of the plant and production process shall be defined giving the
frequency of the inspections, checks and tests, together with the values or criteria required, both on
equipment and on work in progress. The action to be taken when control values or criteria are not
achieved shall be given. Weighing and measuring equipment shall be calibrated. The frequency of
calibration shall be indicated.
8.3.3 Finished product test
1) Tests on the finished product
As appropriate the factory production control system incorporates a sampling plan and the frequency
of testing the finished product. The results of sampling and testing shall be recorded. The frequency
of sampling and testing shall be determined from statistical principles, ensuring that the corresponding
production conforms to the compliance criteria in this standard and the declared values for the mortar.
2) Test equipment
Test equipment having a bearing on test results shall be calibrated. The calibration criteria and
inspection procedures shall be given in the quality manual.
8.3.4 Traceability
As appropriate systems of traceability and control of incoming materials and the use of materials shall
be given in the quality documents. The stock control system of manufactured products shall be given
in the quality documents. This should include the method of treating non-conforming products.
14
---------------------- Page: 15 ----------------------
EN 998-2:2003 (E)
Annex A
(normative)
Sampling for initial type testing and independent testing of
consignments
A.1 General
This sampling procedure shall apply for initial type testing and in the event that there is a requirement
for an assessment of product compliance. For independent testing where only those properties
declared by the manufacturer shall be assessed, representati
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.