EN 1366-1:2014+A1:2020
(Main)Fire resistance tests for service installations - Part 1: Ventilation ducts
Fire resistance tests for service installations - Part 1: Ventilation ducts
This Part of EN 1366 specifies a method for determining the fire resistance of vertical and horizontal ventilation ducts including those access panels, which are integral part of the tested ducts. The test examines the behaviour of ducts exposed to fire from the outside (duct A) and fire inside the duct (duct B). This Standard is used in conjunction with EN1363-1.
Annex A provides general guidance and gives background information.
This European Standard is not applicable to:
a) ducts whose fire resistance depends on the fire resistance performance of a ceiling or wall(where ducts are located in cavities enclosed by fire-resistant shafts or ceilings);
b) ducts containing fire dampers at points where they pass through fire separations;
c) one, two or three sided ducts;
d) fixing of suspension devices (e.g. anchors) to floors or walls.
Feuerwiderstandsprüfungen für Installationen - Teil 1: Lüftungsleitungen
Diese Europäische Norm legt ein Verfahren zur Bestimmung des Feuerwiderstands von vertikalen und hori¬zontalen Lüftungsleitungen, einschließlich Zugangsklappen, fest, die fester Bestandteil der zu prüfenden Leitungen sind. Die Prüfung untersucht das Verhalten von Leitungen, die Brandeinwirkung von außen (Leitung A) sowie Brandeinwirkung innerhalb der Leitung (Leitung B) ausgesetzt sind. Diese Europäische Norm wird in Zusammenhang mit EN 1363 1 angewendet.
Anhang A enthält eine allgemeine Anleitung und Hintergrundinformationen.
Diese Europäische Norm gilt nicht für:
a) Leitungen, deren Feuerwiderstand von der Feuerwiderstandsklasse einer Decke oder Wand abhängig ist (wobei Leitungen in Hohlräumen in feuerwiderstandsfähigen Schächten oder Decken eingeschlossen sind);
b) Leitungen mit Brandschutzklappen an den Durchführungsstellen von raumabschließenden Bauteilen;
c) ein-, zwei- oder dreiseitige Leitungen;
d) Befestigungsmittel von Abhängevorrichtungen (z. B. Anker) an Decken oder Wänden.
Essais de résistance au feu des installations techniques - Partie 1: Conduits de ventilation
La présente Norme européenne spécifie une méthode de détermination de la résistance au feu des conduits de ventilation horizontaux ou verticaux, y compris les trappes d’accès qui font partie intégrante des conduits soumis à l’essai. L’essai examine le comportement des conduits exposés au feu de l’extérieur (conduit A) et de l’intérieur (conduit B). La présente Norme européenne est utilisée conjointement avec l’EN 1363-1.
L’Annexe A donne des lignes directrices générales et des informations de base.
La présente Norme européenne n’est pas applicable :
a) aux conduits dont la résistance au feu dépend de la performance de résistance au feu d’un plafond ou d’un mur (lorsque les conduits se trouvent à l’intérieur de cavités situées dans des gaines ou des plafonds résistant au feu) ;
b) aux conduits comportant des clapets résistant au feu au niveau des cloisonnements coupe-feu ;
c) aux conduits à un, deux ou trois côtés ;
d) à la fixation des dispositifs de suspension (par exemple ancrages) aux planchers ou aux murs.
Preskusi požarne odpornosti servisnih inštalacij - 1. del: Ventilacijski kanali
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-oktober-2020
Nadomešča:
SIST EN 1366-1:2014
Preskusi požarne odpornosti servisnih inštalacij - 1. del: Ventilacijski kanali
Fire resistance tests for service installations - Part 1: Ventilation ducts
Feuerwiderstandsprüfungen für Installationen - Teil 1: Lüftungsleitungen
Essais de résistance au feu des installations techniques - Partie 1: Conduits de
ventilation
Ta slovenski standard je istoveten z: EN 1366-1:2014+A1:2020
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 1366-1:2014+A1
EUROPEAN STANDARD
NORME EUROPÉENNE
August 2020
EUROPÄISCHE NORM
ICS 13.220.50; 91.140.30 Supersedes EN 1366-1:2014
English Version
Fire resistance tests for service installations - Part 1:
Ventilation ducts
Essais de résistance au feu des installations techniques Feuerwiderstandsprüfungen für Installationen - Teil 1:
- Partie 1: Conduits de ventilation Lüftungsleitungen
This European Standard was approved by CEN on 13 June 2014 and includes Amendment approved by CEN on 1 June 2020.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1366-1:2014+A1:2020 E
worldwide for CEN national Members.
Contents Page
European foreword . 3
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 Test equipment . 7
5 Test conditions . 9
6 Test specimen . 9
7 Installation of test specimen . 12
8 Conditioning . 14
9 Application of instrumentation . 14
10 Test procedure . 16
11 Performance criteria . 18
12 Test report . 18
13 Field of direct application of test results . 19
Bibliography . 50
European foreword
This document (EN 1366-1:2014+A1:2020) has been prepared by Technical Committee CEN/TC 127
“Fire safety in buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by February 2021 and conflicting national standards shall
be withdrawn at the latest by February 2021.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document includes Amendment 1 approved by CEN on 1 June 2020.
This document supersedes !EN 1366-1:2014".
The start and finish of text introduced or altered by amendment is indicated in the text by tags !".
!This European Standard has been prepared under a mandate given to CEN by the European
Commission and the European Free Trade Association."
EN 1366 “Fire resistance tests for service installations” consists of the following:
— Part 1: Ventilation ducts;
— Part 2: Fire dampers;
— Part 3: Penetration seals;
— Part 4: Linear joint seals;
— Part 5: Service ducts and shafts;
— Part 6: Raised floors;
— !Part 7: Conveyor systems and their closures;"
— Part 8: Smoke extraction ducts;
— Part 9: Single compartment smoke extraction ducts;
— Part 10: Smoke control dampers (in course of preparation);
— Part 11: Protective Systems for Essential Services (in course of preparation);
— Part 12: Non-mechanical fire barrier for ventilation ductwork;
— !Part 13: Chimneys."
!deleted text"
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
Introduction
The purpose of this test is to measure the ability of a representative ventilation duct assembly / system
that is part of an air distribution system to resist the spread of fire from one fire compartment to
another with fire attack from inside or outside the duct. It is applicable to vertical and horizontal ducts,
with or without branches, taking into account joints and openings, as well as suspension devices and
penetration points.
The test measures the length of time for which ducts, of specified dimensions, suspended as they would
be in practice, satisfy defined criteria when exposed to fire from (separately) both inside and outside
the duct.
The closed end of each horizontal duct at the back of the furnace is fully restraint. Outside the furnace,
ducts exposed to fire from the outside are tested unrestrained, while ducts exposed to fire from the
inside (horizontal only) are tested restrained.
The force measurement at horizontal duct B is not mandatory but can be done on the request of the
sponsor.
The test takes into account the effect of fire exposure from the outside where a pressure differential is
maintained in the duct as well as the effect of fire entering the ducts in conditions where forced air
movement may or may not be present.
Caution
The attention of all persons concerned with managing and carrying out this fire resistance test is drawn
to the fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful
smoke and gases may be evolved during the test. Mechanical and operational hazards may also arise
during the construction of the test elements or structures, their testing and disposal of test residues.
An assessment of all potential hazards and risks to health should be made and safety precautions
should be identified and provided. Written safety instructions should be issued. Appropriate training
should be given to relevant personnel. Laboratory personnel should ensure that they follow written
safety instructions at all times.
1 Scope
This European Standard specifies a method for determining the fire resistance of vertical and horizontal
ventilation ducts including those access panels, which are integral part of the tested ducts. The test
examines the behaviour of ducts exposed to fire from the outside (duct A) and fire inside the duct (duct
B). This European Standard is used in conjunction with EN 1363-1.
Annex A provides general guidance and gives background information.
This European Standard is not applicable to:
a) ducts whose fire resistance depends on the fire resistance performance of a ceiling or wall (where
ducts are located in cavities enclosed by fire-resistant shafts or ceilings);
b) ducts containing fire dampers at points where they pass through fire separations;
c) one, two or three sided ducts;
d) fixing of suspension devices (e.g. anchors) to floors or walls.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 1363-1, Fire resistance tests - Part 1: General Requirements
EN 1364-1:1999, Fire resistance tests for non-loadbearing elements - Part 1: Walls
EN 1366-8, Fire resistance tests for service installations - Part 8: Smoke extraction ducts
EN 1507, Ventilation for buildings - Sheet metal air ducts with rectangular section - Requirements for
strength and leakage
EN 12237, Ventilation for buildings - Ductwork - Strength and leakage of circular sheet metal ducts
EN 15882-1, Extended application of results from fire resistance tests for service installations - Part 1:
Ducts
EN 60584-1, Thermocouples - Part 1: EMF specifications and tolerances (IEC 60584-1)
EN ISO 898-1, Mechanical properties of fasteners made of carbon steel and alloy steel - Part 1: Bolts,
screws and studs with specified property classes - Coarse thread and fine pitch thread (ISO 898-1)
EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular
cross-section conduits running full - Part 1: General principles and requirements (ISO 5167-1)
EN ISO 5167-2, Measurement of fluid flow by means of pressure differential devices inserted in circular
cross-section conduits running full - Part 2: Orifice plates (ISO 5167-2)
EN ISO 5167-3, Measurement of fluid flow by means of pressure differential devices inserted in circular
cross-section conduits running full - Part 3: Nozzles and Venturi nozzles (ISO 5167-3)
EN ISO 13943, Fire safety - Vocabulary (ISO 13943)
3 Terms and definitions
For the purposes of document, the terms and definitions given in EN 1363-1 and EN ISO 13943,
together with the following, apply.
3.1
fire-resistant ventilation duct
duct used for the distribution or extraction of air and designed to provide a degree of fire resistance
3.2
combustible lining
lining / coating on the inner surface of the duct; reaction to fire classification of the lining material
(tested in end use condition, treated as an external, non-substantial component) worse than class A2-
s1,d0 according to EN 13501-1
3.3
self-supporting duct
duct constructed e.g. from fire-protective boards without encasing a steel duct
3.4
suspension devices
components used for suspending and fixing a duct from a floor or supporting a duct from a wall
3.5
supporting construction
wall, partition or floor which the duct passes through in the test
3.6
compensator
device used to prevent damage from the forces generated by expansion
3.7
access panel
cover for an inspection opening within the duct
3.8
fire protected steel duct
steel duct with an external insulation to provide fire resistance
!3.9
kitchen extract duct
ductwork where combustible deposits, such as grease are likely to accumulate on its internal
surfaces"
4 Test equipment
4.1 General
In addition to the test equipment specified in EN 1363-1 the following is required:
4.2 Furnace
This shall be capable of subjecting ventilation ducts to the standard heating and pressure conditions
specified in EN 1363-1 and be suitable for testing ducts in the vertical (see Figure 1) or horizontal (see
Figure 2) orientation.
4.3 Fan for duct A
This shall be able to produc
...
Questions, Comments and Discussion