Residual current-operated protective devices (RCDs) for household and similar use - Electromagnetic compatibility

Corrigendum to EN issued May 2004
2021: CLC legacy converted by DCLab NISOSTS

Fehlerstromschutzeinrichtungen (RCDs) für Hausinstallationen und ähnliche Verwendung - Elektromagnetische Verträglichkeit

Dispositifs différentiels résiduels (DDR) pour usages domestiques et analogues - Compatibilité électromagnétique

Residual current-operated protective devices (RCDs) for household and similar use - Electromagnetic compatibility - Amendment A11

General Information

Status
Published
Publication Date
29-Sep-2003
Withdrawal Date
28-Feb-2007
Current Stage
6060 - Document made available - Publishing
Start Date
30-Sep-2003
Completion Date
30-Sep-2003

Relations

Buy Standard

Amendment
EN 61543:1998/A11:2004
English language
7 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI SIST EN 61543:1998/A11:2004

STANDARD
januar 2004
(istoveten EN 61543:1995/A11:2003)
Residual current-operated protective devices (RCDs) for household and similar
use - Electromagnetic compatibility - Amendment A11
ICS 5HIHUHQþQDãWHYLOND
29.020; 29.120.50
! "#$%!&!%’()*#+’
EUROPEAN STANDARD EN 61543/A11
NORME EUROPÉENNE
EUROPÄISCHE NORM September 2003

ICS 29.020; 29.120.50 Incorporates Corrigendum May 2004

English version
Residual current-operated protective devices (RCDs)
for household and similar use –
Electromagnetic compatibility
Dispositifs différentiels résiduels (DDR) Fehlerstromschutzeinrichtungen (RCDs)
pour usages domestiques et analogues – für Hausinstallationen und ähnliche
Compatibilité électromagnétique Verwendung –
Elektromagnetische Verträglichkeit

This amendment A11 modifies the European Standard EN 61543:1995; it was approved by CENELEC on
2003-06-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2003 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 61543:1995/A11:2003 E

Foreword
The text of this document, prepared by the Technical Committee CENELEC TC 23E, Circuit breakers
and similar devices for household and similar applications, was submitted to the Unique Acceptance
Procedure and was approved by CENELEC as amendment A11 to EN 61543:1995 on 2003-06-01.

The following dates were fixed:

– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2004-03-01

– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2007-03-01

Annexes designated "normative" are part of the body of the standard.
In this standard, annex ZA is normative.
Annex ZA has been added by CENELEC.

The contents of the corrigendum of May 2004 have been included in this copy.

___________
- 3 - EN 61543:1995/A11:2003
1 Introduction
Add, after the last paragraph, the following new paragraph:

The EMC characteristics of a product are generally influenced by the design and not by the
manufacturing process, therefore the tests of this standard are to be made for design
verification and will be repeated only in the case of modifications influencing the EMC
behaviour.
Add the following title to Table 1:

Table 1 – Standard low-frequency environmental conditions
2)
Add table footnote to the reference T 1.2: Signalling voltages in the second column as
follows:
2) Superimposed mains signalling voltages are not allowed in common mode, except under specific
conditions as indicated in IEC 60364-4-44.

Add the following title to Table 2:

Table 2 – Standard high-frequency environmental conditions

Add the following title to Table 3:
Table 3 – Standard electrostatic environmental conditions

5.1.3 Add after the first sentence:
After each tripping the RCD shall be reclosed.

Replace the existing Table 4 by the following new table (modifications are underlined):
Table 4 – Low frequency immunity test conditions
Reference Electromagnetic Reference of Test level and test Subclauses including
(see table 1) phenomena basic standard for specification the performance criteria
test description
1)
T1.1 Harmonics, No requirements
interharmonics
T1.2 Signalling voltages No requirements
Voltage amplitude variations
2)
T1.3 Voltage fluctuations 9.9.5 and 9.17 of From 0,85 U to 9.16 and 9.17 of
n
3)
IEC 61008-1; 1,1 U IEC 61008-1 and
n
IEC 61009-1
9.9.1.5 and 9.17 of
IEC 61009-1
2)
Voltage dips 9.17 of IEC 61008-1 and IEC 61009-1
2)
Voltage interruptions 9.17 of IEC 61008-1 and IEC 61009-1
T1.4 Voltage unbalance Refer to T1.3
4)
T1.5 Power frequency
variations
T1.8 Magnetic field 9.11 and 9.18 of IEC 61008-1 (RCCBs)
9.12 and 9.18 of IEC 61009-1 (RCBOs)
1)
A study is undertaken for possible inclusion of requirements in a future revision.
2)
Tests specified in pr
...