EN IEC 61439-3:2024
(Main)Low-voltage switchgear and controlgear assemblies - Part 3: Distribution boards intended to be operated by ordinary persons (DBO)
Low-voltage switchgear and controlgear assemblies - Part 3: Distribution boards intended to be operated by ordinary persons (DBO)
IEC 61439-3:2024 defines the specific requirements for distribution boards intended to be operated by ordinary persons (abbreviated DBO throughout this document, see 3.1.101) as follows: - assemblies intended to be operated by ordinary persons (e.g. switching operations and replacing fuse-links), e.g. in domestic (household) applications; - assemblies containing outgoing circuits with protective devices intended to be operated by ordinary persons, complying e.g. with IEC 60898-1, the IEC 61008 series, the IEC 61009 series, IEC 62606, IEC 62423 and IEC 60269-3; - assemblies for applications where the nominal voltage to earth does not exceed 300 V AC (see Table G.1 of IEC 61439-1:2020); NOTE The voltage limits for DC applications are under consideration. - assemblies with a rated current (Inc) of the outgoing circuits not exceeding 125 A and a rated current (InA) not exceeding 250 A; - assemblies intended for use in connection with the generation, transmission, distribution and conversion of electrical energy, and for the control of equipment consuming electrical energy and for associated data processing; - enclosed, stationary assemblies; - assemblies for indoor or outdoor use. This second edition cancels and replaces the first edition published in 2012. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) alignment with the structure of IEC 61439-1:2020; b) inclusion in the scope of more examples of the type of protection and control devices; c) deletion of type A and Type B DBOs; d) addition of a new Annex BB related to DBOs used in a prosumer’s electrical installation (PEI); e) addition of a new Annex CC related to rated current of a DBO with additional source of supply in parallel/simultaneously with another source that is connected to the DBO e.g. PV.
Niederspannungs-Schaltgerätekombinationen - Teil 3: Installationsverteiler für die Bedienung durch Laien (DBO)
Ensembles d'appareillage à basse tension - Partie 3: Tableaux de répartition destinés à être utilisés par des personnes ordinaires (DBO)
L'IEC 61439-3:2024 définit les exigences spécifiques pour les tableaux de répartition destinés à être utilisés par des personnes ordinaires (abrégés DBO dans l'ensemble du présent document, voir 3.1.101) ci-après: - ensembles destinés à être utilisés par des personnes ordinaires (par exemple, pour manœuvrer des appareils de commande et remplacer des éléments de fusible), par exemple dans des applications domestiques; - ensembles qui contiennent des circuits de départ avec des dispositifs de protection, destinés à être utilisés par des personnes ordinaires, qui satisfont par exemple à l'IEC 60898-1, à la série IEC 61008, à la série IEC 61009, à l'IEC 62606, à l'IEC 62423 et à l'IEC 60269-3; - ensembles destinés à des applications pour lesquelles la tension nominale à la terre ne dépasse pas 300 V en courant alternatif (voir Tableau G.1 de l'IEC 61439-1:2020); NOTE Les limites de tension pour les applications en courant continu sont à l'étude. - ensembles dans lesquels le courant assigné (Inc) des circuits de départ est inférieur ou égal à 125 A et dont le courant assigné (InA) est inférieur ou égal à 250 A; - ensembles destinés à être utilisés avec des équipements conçus pour la production, le transport, la distribution et la conversion de l'énergie électrique, la commande des matériels qui consomment de l'énergie électrique et le traitement des données associées; - ensembles fixes sous enveloppe; - ensembles pour utilisation en intérieure ou en extérieur. Cette seconde édition annule et remplace la première édition parue en 2012. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente: a) alignement sur la structure de l'IEC 61439-1:2020; b) inclusion dans le domaine d'application de plus d'exemples de types de dispositifs de protection et de commande; c) suppression des DBO de type A et de type B; d) ajout d'une nouvelle Annexe BB relative aux DBO utilisés dans une installation électrique de prosommateur (PEI); e) ajout d'une nouvelle Annexe CC relative au courant assigné d'un DBO avec une source d'alimentation supplémentaire parallèlement/simultanément avec une autre source reliée au DBO, par exemple un panneau photovoltaïque (PV).
Sestavi nizkonapetostnih stikalnih in krmilnih naprav - 3. del: Električni razdelilniki, s katerimi lahko ravnajo nestrokovnjaki (DBO) (IEC 61439-3:2024)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN IEC 61439-3:2022
01-oktober-2022
Sestavi nizkonapetostnih stikalnih in krmilnih naprav - 3. del: Električni
razdelilniki, s katerimi lahko ravnajo nestrokovnjaki (DBO)
Low-voltage switchgear and controlgear assemblies - Part 3: Distribution boards
intended to be operated by ordinary persons (DBO)
Niederspannungs-Schaltgerätekombinationen - Teil 3: Installationsverteiler für die
Bedienung durch Laien (DBO)
Ensembles d'appareillage à basse tension - Partie 3: Tableaux de répartition destinés à
être utilisés par des personnes ordinaires (DBO)
Ta slovenski standard je istoveten z: prEN IEC 61439-3:2022
ICS:
29.130.20 Nizkonapetostne stikalne in Low voltage switchgear and
krmilne naprave controlgear
oSIST prEN IEC 61439-3:2022 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
oSIST prEN IEC 61439-3:2022
oSIST prEN IEC 61439-3:2022
121B/159/CDV
COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 61439-3 ED2
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2022-07-15 2022-10-07
SUPERSEDES DOCUMENTS:
121B/139/CD, 121B/158/CC
IEC SC 121B : LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ASSEMBLIES
SECRETARIAT: SECRETARY:
Germany Mr Jörg Hußmann
OF INTEREST TO THE FOLLOWING COMMITTEES: PROPOSED HORIZONTAL STANDARD:
TC 18,TC 44,TC 64,SC 121A
Other TC/SCs are requested to indicate their interest, if
any, in this CDV to the secretary.
FUNCTIONS CONCERNED:
EMC ENVIRONMENT QUALITY ASSURANCE SAFETY
SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.
This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.
TITLE:
Low-voltage switchgear and controlgear assemblies - Part 3: Distribution boards intended to
be operated by ordinary persons (DBO)
PROPOSED STABILITY DATE: 2026
NOTE FROM TC/SC OFFICERS:
download this electronic file, to make a copy and to print out the content for the sole purpose of preparing National
Committee positions. You may not copy or "mirror" the file or printed version of the document, or any part of it, for
any other purpose without permission in writing from IEC.
oSIST prEN IEC 61439-3:2022
IEC CDV 61439-3 © IEC 2022 2 121B/159/CDV
1 CONTENTS
2 FOREWORD . 4
3 1 Scope . 6
4 2 Normative references . 6
5 3 Terms and definitions . 7
6 3.1 General terms . 7
7 4 Symbols and abbreviations . 8
8 5 Interface characteristics . 8
9 5.1 General . 8
10 5.2.4 Rated impulse withstand voltage (U ) (of the assembly ). 8
imp
11 5.4 Rated diversity factor (RDF) . 8
12 6 Information . 8
13 6.1 Assembly designation marking . 8
14 6.2.2 Instructions for handling, installation, operation and maintenance . 9
15 6.3 Device and/or component identification . 9
16 7 Service conditions . 9
17 7.1.2 Pollution degree . 9
18 8 Constructional requirements . 9
19 8.1.3.2.2 Resistance of insulating materials to normal heat . 9
20 8.2.1 Protection against mechanical impact (IK code) . 9
21 8.2.2 Protection against contact with live parts, ingress of solid foreign bodies and
22 water (IP code) . 9
23 IP 2XC shall be maintained when operating devices e.g. switching and operating
24 test buttons in normal use. The degree of protection can be temporarily
25 reduced when permitted in a product standard for use by ordinary / unskilled
26 persons e.g. IEC 60269-3 for replacing a fuse-link, the degree of protection
27 may temporarily be reduced to IP1X. . 9
28 8.4.2.3 Barriers or enclosures . 9
29 8.5.3 Selection of switching devices and components . 10
30 8.6.1 Main circuits . 10
31 8.8 Terminals for external cables . 10
32 9 Performance requirements . 10
33 9.1.1 General . 10
34 10 Design verification . 10
35 10.2.2.2Severity test A . 10
36 10.2.2.4Results to be obtained . 11
37 10.2.3.2.1 Verification by test . 11
38 10.2.6 Verification of protection against mechanical impact (IK code) . 11
39 10.2.7.1 Verification by test . 12
40 10.10.2.2.3 Functional units . 12
41 10.10.2.3.1General . 13
42 10.10.2.3.6 Verification considering individual functional units
43 separately and the complete assembly . 13
44 10.10.2.3.7 Verification considering individual functional units and the
45 main and distribution busbars separately as well as the complete assembly . 13
46 10.10.3.2Assemblies . 14
47 10.10.4.2.3Results to be obtained . 14
48 10.10.4.3.2Results to be obtained . 14
49 10.11.5.3.3Incoming circuit and main busbars . 14
50 11 Routine verification . 15
oSIST prEN IEC 61439-3:2022
IEC CDV 61439-3 © IEC 2022 3 121B/159/CDV
51 Annexes. 18
52 Annex AA (informative) Items subject to agreement between the DBO manufacturer
53 and the user . 19
54 Annex BB (informative) Effects upon a DBO design and related ratings, instructions
55 etc when used in a prosumer’s electrical installation (PEI) . 25
56 Annex CC (informative) . 26
57 Annex DD (informative) List of notes concerning certain countries . 27
58 Bibliography . 40
60 UK Figure 101 – Example of temperature rise verification by test of a complete
61 split-load DBO as in 10.10.2.3.6 . 31
63 Table 101 – Values of assumed loading . 16
64 Table 102 – Tightening torque values for the verification of mechanical strength . 17
65 Table AA.1 – Items subject to agreement between the DBO manufacturer and the user . 19
oSIST prEN IEC 61439-3:2022
IEC CDV 61439-3 © IEC 2022 4 121B/159/CDV
68 INTERNATIONAL ELECTROTECHNICAL COMMISSION
69 ____________
71 LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ASSEMBLIES –
73 Part 3: Distribution boards intended to be operated
74 by ordinary persons (DBO)
76 FOREWORD
77 1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
78 all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
79 co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
80 in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
81 Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
82 preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
83 may participate in this preparatory work. International, governmental and non-governmental organizations liaising
84 with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
85 Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
86 2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
87 consensus of opinion on the relevant subjects since each technical committee has representation from all
88 interested IEC National Committees.
89 3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
90 Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
91 Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
92 misinterpretation by any end user.
93 4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
94 transparently to the maximum extent possible in their national and regional publications. Any divergence between
95 any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
96 5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
97 assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
98 services carried out by independent certification bodies.
99 6) All users should ensure that they have the latest edition of this publication.
100 7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
101 members of its technical committees and IEC National Committees for any personal injury, property damage or
102 other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
103 expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
104 Publications.
105 8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
106 indispensable for the correct application of this publication.
107 9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
108 rights. IEC shall not be held responsible for identifying any or all such patent rights.
109 International Standard IEC 61439-3 has been prepared by subcommittee 121B: Low-voltage
110 switchgear and controlgear assemblies, of IEC technical committee 121: Switchgear and
111 controlgear and their assemblies for low voltage.
112 This second edition cancels and replaces the first edition published in 2012, corrigendum 1
113 (2013) and corrigendum 2 (2019). It constitutes a technical revision.
114 This edition includes the following significant technical changes with respect to the previous
115 edition:
116 a) XX
117 b) XX
118 c) alignment with the structure of IEC 61439-1, 2020;
119 d) general editorial review.
120 The text of this standard is based on the following documents:
FDIS Report on voting
121B/XXX/FDIS 121B/XXX/RVD
...