Multi-element metallic cables used in analogue and digital communication and control - Part 11-2: Sectional specification for un-screened cables, characterized from 1 MHz up to 500 MHz for work area, patch cord and data centre applications

EN 50288-11-2 is a sectional specification for un-screened cables, characterised from 1 MHz up to 500 MHz, to be used in work area cables to connect a telecommunications outlet to the terminal equipment and for patch cord cables to establish connections on a patch panel as defined in EN 50173. Work area and data centres cables may also be used as patch cord cables in any distributor of a generic building wiring system to interconnect with equipment or to cross-connect between cabling systems. This sectional specification contains the electrical, mechanical, transmission and environmental performance characteristics and requirements of the cables when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential provisions for its application. The cables covered in this sectional specification are intended to operate with voltages and currents normally encountered in communications systems. These cables are not intended to be used in conjunction with low impedance sources, for example the electrical power supplies of public utility mains.

Mehradrige metallische Daten- und Kontrollkabel für analoge und digitale Kommunikation - Teil 11-2: Rahmenspezifikation für ungeschirmte Kabel von 1 MHz bis 500 MHz für Geräteanschlusskabel, Schaltkabel und Anwendungen für Rechenzentren

EN 50288-11-2 ist eine Rahmenspezifikation für ungeschirmte Kabel von 1 MHz bis 500 MHz zur Verwendung als Geräteanschlusskabel für den Anschluss von Endgeräten an informationstechnische Anschlüsse und als Schaltkabel zur Herstellung von Verbindungen an Rangierfeldern nach EN 50173. Geräteanschlusskabel und Kabel für Rechenzentren dürfen auch als Schaltkabel in jedem Verteiler einer anwendungsneutralen Kommuni-kationskabelanlage zur Verbindung mit Geräten oder zur Verbindung zwischen Kommunikationskabelanlagen verwendet werden. Diese Rahmenspezifikation beschreibt die elektrischen, mechanischen, übertragungstechnischen und umge-bungsrelevanten Eigenschaften und Anforderungen für Kabel, die nach den angegebenen Referenzprüf-verfahren geprüft werden. Diese Rahmenspezifikation ist zusammen mit EN 50288-1 anzuwenden, die die grundlegenden Anwendungs-bestimmungen enthält. Die in dieser Rahmenspezifikation beschriebenen Kabel sind für den Betrieb mit Spannungen und Strömen vorgesehen, die üblicherweise in Kommunikationssystemen vorkommen. Diese Kabel sind nicht für die Verwendung in Verbindung mit niederohmigen Quellen vorgesehen, wie zum Beispiel Verteilungsnetzen zur elektrischen Energieversorgung.

Câbles métalliques à éléments multiples utilisés pour les transmissions et les commandes analogiques et numériques - Partie 11-2: Spécification intermédiaire pour les câbles non écrantés, caractérisés de 1 MHz à 500 MHz - Câbles horizontaux et câbles verticaux de bâtiment

La présente spécification intermédiaire s'applique aux câbles non écrantés caractérisés de 1 MHz à 500 MHz, destinés à être utilisés pour la construction de cordons dans les câblages spécifiés dans la série de normes EN 50173. Les normes de câblage spécifiques aux locaux de la série EN 50173 font référence aux exigences D1 de la présente spécification pour les câbles utilisés dans les cordons relevant des "mises en œuvre de référence" de ces normes. Les exigences alternatives D2 de la présente spécification peuvent être utilisées pour la production de cordons pour d’autres mises en œuvre et applications, y compris le raccordement direct de matériels dans les centres de traitement de données. La présente spécification intermédiaire contient les caractéristiques et les exigences applicables pour les performances électriques, mécaniques, de transmission et d’environnement relatives aux câbles soumis aux essais selon les méthodes d’essai référencées. La présente spécification intermédiaire doit être utilisée conjointement avec l’EN 50288-1, qui contient les dispositions essentielles pour son application. Les câbles couverts par la présente spécification intermédiaire sont destinés à fonctionner avec des tensions et des courants rencontrés normalement dans les systèmes de communication. Ces câbles ne sont pas destinés à être utilisés conjointement avec des sources de faible impédance, par exemple, les alimentations électriques du réseau public.

Večelementni kovinski kabli za analogne in digitalne komunikacije in krmiljenje - 11-2. del: Področna specifikacija za nezaslonjene kable z lastnostmi od 1 MHz do 500 MHz - Vodoravni (etažni) in stavbni hrbtenični (medetažni) kabli

Standard EN 50288-11-2 je področna specifikacija za nezaslonjene kable, ki se lahko uporabljajo za pasovne širine 1 MHz do 500 MHz kot kabli na delovnem območju za povezavo telekomunikacijske vtičnice s terminalsko opremo, ter za povezovalne vrvice za vzpostavljanje povezav na povezovalni plošči, kot je določeno v standardu EN 50173. Kabli delovnega območja in podatkovnih centrov se lahko uporabljajo tudi kot povezovalne vrvice v katerem koli razdelilniku generičnega stavbnega sistema ožičenja za povezavo z opremo ali navzkrižno povezavo med kabelskimi sistemi.
Ta področna specifikacija vsebuje električne, mehanske, prenosne in okoljske karakteristike delovanja ter zahteve za kable pri preskušanju v skladu z navedenimi preskusnimi metodami.
Ta področna specifikacija se uporablja skupaj s standardom EN 50288-1, ki vsebuje bistvene določbe za njeno uporabo.
Kabli, zajeti v tej področni specifikaciji, so namenjeni za delovanje pri napetostih in tokovih, ki so običajni v komunikacijskih sistemih. Ti kabli niso namenjeni za uporabo z viri z nizko impedanco, na primer z električnim napajanjem javnih omrežij.

General Information

Status
Published
Publication Date
03-Sep-2015
Withdrawal Date
02-Aug-2018
Current Stage
6060 - Document made available - Publishing
Start Date
04-Sep-2015
Due Date
20-Aug-2015
Completion Date
04-Sep-2015

Overview

EN 50288-11-2:2015 (CLC) is a sectional specification for un‑screened multi‑element metallic cables characterized from 1 MHz to 500 MHz. It defines construction, electrical, mechanical, transmission and environmental performance for cables used as work‑area cords, patch cords and data‑centre interconnects. This Part 11‑2 is intended to be read together with EN 50288‑1 (generic provisions) and references EN 50173 (premises cabling) for application context.

Key topics and technical requirements

  • Scope and construction
    • Applies to unscreened pair/quad cables for horizontal and building backbone (work area, patch panel, data centre).
    • Conductors: solid (nominal diameter 0.40–0.80 mm) or stranded (7 wires, each 0.10–0.21 mm). Insulation and sheath follow EN 50290‑2 series.
  • Low‑frequency / DC electrical tests
    • Conductor loop resistance: D1 ≤ 28.0 Ω/100 m; D2 ≤ 34.0 Ω/100 m.
    • Insulation resistance: ≥ 5 000 MΩ·km.
    • Dielectric strength and resistance unbalance requirements are specified.
  • High‑frequency transmission tests (1–500 MHz)
    • Attenuation, NEXT, ACR‑F, PSNEXT, PSACR‑F specified as frequency‑dependent limits (e.g., NEXT and PSNEXT minimums follow formulae such as ≥ 75.3 − 15 log f dB).
    • Characteristic impedance: mean 100 ± 5 Ω at 100 MHz.
    • Return loss, skew (propagation delay difference) and velocity of propagation are defined (skew ≤ 45 ns/100 m at 100 MHz; phase delay limit ≤ 534 + 36/√f ns/100 m).
  • Mechanical, environmental and fire tests
    • Includes tensile, crush, impact, bending, temperature cycling and other routine test methods referenced to EN 50289 series.
  • Application notes
    • Annex A gives recommended maximum voltage/current and conductor temperature for Power over Ethernet (PoE) applications.

Applications and users

Who uses EN 50288‑11‑2:2015:

  • Cable manufacturers and product engineers designing unscreened cords and patch leads.
  • Data‑centre designers and network integrators specifying patching and work‑area cabling.
  • Installers, test laboratories and QA teams verifying compliance (electrical and transmission performance).
  • Procurement and compliance officers referencing standards for contract specifications.

Practical use:

  • Specifying patch cords and work‑area cables that meet performance limits for Ethernet and other balanced communications up to 500 MHz.
  • Ensuring interoperability in patch panels, outlet‑to‑equipment cords, and short data‑centre interconnects.

Related standards

  • EN 50288‑1 (Generic specification) - mandatory companion document
  • EN 50173 (Premises cabling series)
  • EN 50290‑2 series (design rules)
  • EN 50289 test methods series, IEC 60189‑2, EN 60708

Keywords: EN 50288‑11‑2:2015, un‑screened cables, 1 MHz–500 MHz, work area cables, patch cord, data centre cabling, NEXT, attenuation, ACR‑F, PSNEXT, characteristic impedance.

Standard
EN 50288-11-2:2016
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-februar-2016
9HþHOHPHQWQLNRYLQVNLNDEOL]DDQDORJQHLQGLJLWDOQHNRPXQLNDFLMHLQNUPLOMHQMH
GHO3RGURþQDVSHFLILNDFLMD]DQH]DVORQMHQHNDEOH]ODVWQRVWPLRG0+]GR
0+]9RGRUDYQL HWDåQL LQVWDYEQLKUEWHQLþQL PHGHWDåQL NDEOL
Multi-element metallic cables used in analogue and digital communication and control --
Part 11-2: Sectional specification for un-screened cables, characterized from 1 MHz up
to 500 MHz - Horizontal and building backbone cables
Mehradrige metallische Daten- und Kontrollkabel für analoge und digitale Übertragung --
Teil 11-2: Rahmenspezifikation für ungeschirmte Kabel von 1 MHz bis 500 MHz - Kabel
für den Horizontal- und Steigbereich
Câbles métalliques à éléments multiples utilisés pour les transmissions et les
commandes analogiques et numériques -- Partie 11-2: Spécification intermédiaire pour
les câbles non écrantés, caractérisés de 1 MHz à 500 MHz - Câbles horizontaux et
câbles verticaux de bâtiment
Ta slovenski standard je istoveten z: EN 50288-11-2:2015
ICS:
33.120.20 äLFHLQVLPHWULþQLNDEOL Wires and symmetrical
cables
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN 50288-11-2

NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2015
ICS 33.120.10
English Version
Multi-element metallic cables used in analogue and digital
communication and control - Part 11-2: Sectional specification
for un-screened cables, characterized from 1 MHz up to 500
MHz for work area, patch cord and data centre applications
Câbles métalliques à éléments multiples utilisés pour les Mehradrige metallische Daten- und Kontrollkabel für
transmissions et les commandes analogiques et
analoge und digitale Kommunikation - Teil 11-2:
numériques - Partie 11-2: Spécification intermédiaire pour Rahmenspezifikation für ungeschirmte Kabel von 1 MHz bis
les câbles non écrantés, caractérisés de 1 MHz à 500 MHz 500 MHz für Geräteanschlusskabel, Schaltkabel und
- Câbles horizontaux et câbles verticaux de bâtiment Anwendungen für Rechenzentren
This European Standard was approved by CENELEC on 2015-08-03. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 50288-11-2:2015 E
Contents Page
European foreword . 3
1 Scope . 4
2 Normative references . 4
3 Terms, definitions, symbols and abbreviations . 5
3.1 Terms and definitions . 5
3.2 Symbols and abbreviations . 5
4 Cable construction . 5
4.1 Conductor . 5
4.2 Insulation . 5
4.3 Cabling elements . 5
4.4 Identification of cabling elements . 5
4.5 Screening of cabling elements . 5
4.6 Cable make-up . 5
4.7 Filling compound . 6
4.8 Interstitial fillers . 6
4.9 Screening of the cable core . 6
4.10 Moisture barriers . 6
4.11 Wrapping layers . 6
4.12 Sheath . 6
5 Test methods and requirements for completed cables . 6
5.1 Electrical tests . 6
5.2 Mechanical tests . 10
5.3 Environmental tests . 11
5.4 Fire performance tests . 11
Annex A (informative) Maximum voltage, current and temperature rating for cables used for
POE applications . 12
Annex B (informative) Blank Detail Specification . 13
B.1 General . 13
B.2 Document Details . 13
B.3 Generic specification EN 50288-1 . 14

Tables
Table 1 – Low-frequency and d.c. electrical measurements .6
Table 2 – High-frequency electrical and transmission measurements .7
Table 3 – Mechanical test requirements .10
Table 4 – Environmental test requirements .11
Table A.1 – Maximum recommended voltage, current, current density and conductor temperature for
cables when used for POE applications .12
Table B.1 – Blank detail specification for symmetrical pair/quad cables for digital communications .14

European foreword
This document (EN 50288-11-2:2015) has been prepared by CLC/SC 46XC "Multicore, multipair and quad
data communication cables," of CLC/TC 46X, "Communication cables".

The following dates are fixed:

(dop) 2015-08-03
• latest date by which this document has to be
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) 2018-08-03
conflicting with this document have to
be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights.
This Part 11-2 is to be read in conjunction to EN 50288-1.
This document has been prepared under a mandate given to CENELEC by the European Commission and
the European Free Trade Association.
This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment Designed for
Use within Certain Voltage Limits (LVD - 2006/95/EC).
1 Scope
This sectional specification covers un-screened cables, characterised from 1 MHz up to 500 MHz, to be used
to construct cords for use in cabling specified in the EN 50173 series of standards.
The premises-specific cabling standards of the EN 50173 series reference the D1 requirements of this
specification for the cable used within cords of the “reference implementations” of those standards. The
alternative D2 requirements of this specification may be used to produce cords for other implementations and
applications including the direct connection of equipment in data centres.
This sectional specification contains the electrical, mechanical, transmission and environmental performance
characteristics and requirements of the cables when tested in accordance with the referenced test methods.
This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential
provisions for its application.
The cables covered in this sectional specification are intended to operate with voltages and currents normally
encountered in communications systems. These cables are not intended to be used in conjunction with low
impedance sources, for example the electrical power supplies of public utility mains.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 50288-1:2013, Multi-element metallic cables used in analogue and digital communication and control –
Part 1: Generic specification
EN 50289-3-2, Communication cables – Specifications for test methods – Part 3-2: Mechanical test
methods – Tensile strength and elongation for conductor
EN 50289-3-4, Communication cables – Specifications for test methods – Part 3-4: Mechanical test
methods – Tensile strength, elongation and shrinkage of insulation and sheath
EN 50289-3-5, Communication cables – Specifications for test methods – Part 3-5: Mechanical test
methods – Crush resistance of the cable
EN 50289-3-6, Communication cables – Specifications for test methods – Part 3-6: Mechanical test
methods – Impact resistance of the cable
EN 50289-3-8, Communication cables – Specifications for test methods – Part 3-8: Mechanical test
methods – Abrasion resistance of cable sheath markings
EN 50289-3-9:2001, Communication cables – Specifications for test methods – Part 3-9: Mechanical test
methods – Bending tests
EN 50289-3-16, Communication cables – Specifications for test methods – Part 3-16: Mechanical test
methods – Cable tensile performance
EN 50289-4-6, Communication cables – Specifications for test methods – Part 4-6: Environmental test
methods – Temperature cycling
EN 50290-2 series, Communication cables – Part 2: Common design rules and construction
EN 60708, Low-frequency cables with polyolefin insulation and moisture barrier polyolefin sheath (IEC 60708)
IEC 60189-2, Low-frequency cables and wires with PVC insulation and PVC sheath – Part 2: Cables in pairs,
triples, quads and quintuples for inside installations
3 Terms, definitions, symbols and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions of EN 50288-1 apply.
3.2 Symbols and abbreviations
For the purposes of this document, the following abbreviations apply.
EX Exogenous (derived or originating externally)
POE Power Over Ethernet
4 Cable construction
4.1 Conductor
The conductor shall be solid or stranded annealed copper and meet the requirements of EN 50288-1:2013,
4.1
The solid conductor nominal diameter shall be ≥ 0,40 mm and ≤ 0,80 mm.
The stranded conductor shall consist of seven wires each with a nominal diameter of ≥ 0,10 mm to
≤ 0,21 mm.
NOTE Constructions with ‘copper clad’ conductors do not meet the requirements.
4.2 Insulation
The insulation shall be of a suitable material in accordance with the appropriate part of the EN 50290-2
series.
4.3 Cabling elements
The cable element shall be a pair or quad.
4.4 Identification of cabling elements
Unless otherwise specified, the colour coding for identification shall be as specified in IEC 60189-2 or
EN 60708, as appropriate. The colours shall comply with the requirements of EN 50288-1:2013, 4.4.
4.5 Screening of cabling elements
Not applicable.
4.6 Cable make-up
The cable elements shall be laid up in concentric layer(s) or units to form the cable core.
4.7 Filling compound
Not applicable.
4.8 Interstitial fillers
Where fillers are used they shall comply with the requirements of EN 50288-1:2013, 4.8.
4.9 Screening of the cable core
Not applicable.
4.10 Moisture barriers
Not applicable.
4.11 Wrapping layers
Where wrapping layers are used they shall comply with the requirements of EN 50288-1:2013, 4.11
4.12 Sheath
The sheath shall be of a suitable material and comply with the appropriate part of the EN 50290-2 series.
5 Test methods and requirements for completed cables
5.1 General
The following tables specify the tests that shall be applied to the completed cable, together with the
requirements to demonstrate compliance with this sectional specification.
5.2 Electrical tests
5.2.1 Low-frequency and DC electrical measurements
Table 1 – Low-frequency and DC electrical measurements
EN 50288- Parameter Requiremen
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

Frequently Asked Questions

EN 50288-11-2:2015 is a standard published by CLC. Its full title is "Multi-element metallic cables used in analogue and digital communication and control - Part 11-2: Sectional specification for un-screened cables, characterized from 1 MHz up to 500 MHz for work area, patch cord and data centre applications". This standard covers: EN 50288-11-2 is a sectional specification for un-screened cables, characterised from 1 MHz up to 500 MHz, to be used in work area cables to connect a telecommunications outlet to the terminal equipment and for patch cord cables to establish connections on a patch panel as defined in EN 50173. Work area and data centres cables may also be used as patch cord cables in any distributor of a generic building wiring system to interconnect with equipment or to cross-connect between cabling systems. This sectional specification contains the electrical, mechanical, transmission and environmental performance characteristics and requirements of the cables when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential provisions for its application. The cables covered in this sectional specification are intended to operate with voltages and currents normally encountered in communications systems. These cables are not intended to be used in conjunction with low impedance sources, for example the electrical power supplies of public utility mains.

EN 50288-11-2 is a sectional specification for un-screened cables, characterised from 1 MHz up to 500 MHz, to be used in work area cables to connect a telecommunications outlet to the terminal equipment and for patch cord cables to establish connections on a patch panel as defined in EN 50173. Work area and data centres cables may also be used as patch cord cables in any distributor of a generic building wiring system to interconnect with equipment or to cross-connect between cabling systems. This sectional specification contains the electrical, mechanical, transmission and environmental performance characteristics and requirements of the cables when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential provisions for its application. The cables covered in this sectional specification are intended to operate with voltages and currents normally encountered in communications systems. These cables are not intended to be used in conjunction with low impedance sources, for example the electrical power supplies of public utility mains.

EN 50288-11-2:2015 is classified under the following ICS (International Classification for Standards) categories: 33.120.10 - Coaxial cables. Waveguides. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 50288-11-2:2015 is associated with the following European legislation: EU Directives/Regulations: 2006/95/EC, 2014/35/EU, 2014/53/EU; Standardization Mandates: M/212. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase EN 50288-11-2:2015 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CLC standards.