Safety of power transformers, power supply units and similar - Part 2-15: Particular requirements for isolating transformers for the supply of medical locations

This part 2-15 of IEC 61558 applies to stationary, single-phase or polyphase, air-cooled (natural or forced) isolating transformers for the supply of group II medical locations, designed to be permanently connected to the fixed wiring of IT supply system. This standard also applies to transformers incorporating electronic circuits. This standard does not apply to external circuits and their components intended to be connected to the input and output terminals or socket-outlets of the transformer. It has the status of a group safety publication in accordance with IEC Guide 104. This part 2 is intended to be used in conjunction with IEC 61558-1.

Sicherheit von Transformatoren, Netzgeräten und dergleichen - Teil 2-15: Besondere Anforderungen an Trenntransformatoren zur Versorgung medizinischer Räume

Sécurité des transformateurs, blocs d'alimentation et analogues - Partie 2-15: Règles particulières pour les transformateurs de séparation de circuits pour locaux à usages médicaux

La présente partie 2-15 de la CEI 61558 est applicable aux transformateurs de séparation de circuits fixes, monophasés ou polyphasés, à refroidissement par air (naturel ou forcé), destinés à alimenter des locaux à usages médicaux du groupe II et conçus pour être reliés en permanence au câblage fixe du système d'alimentation IT. Les transformateurs incorporant des circuits électroniques sont également couverts par cette norme. Cette norme ne s'applique pas aux circuits externes et à leurs composants connectés aux bornes ou aux socles de prise de courant du transformateur. Elle a le statut de publication groupée de sécurité conformément au Guide CEI 104. La présente partie 2 est destinée à être utilisée avec la CEI 61558-1.

Safety of power transformers, power supply units and similar - Part 2-15: Particular requirements for isolating transformers for the supply of medical locations

General Information

Status
Withdrawn
Publication Date
12-Jun-2001
Withdrawal Date
31-Jul-2003
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
27-Dec-2014
Completion Date
27-Dec-2014

Relations

Buy Standard

Standard
EN 61558-2-15:2002
English language
22 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI SIST EN 61558-2-15:2002
prva izdaja
STANDARD
september 2002
Safety of power transformers, power supply units and similar - Part 2-15: Particular
requirements for isolating transformers for the supply of medical locations
ICS 29.180 Referenčna številka
SIST EN 61558-2-15:2002(en)
©  Standard je založil in izdal Slovenski inštitut za standardizacijo. Razmnoževanje ali kopiranje celote ali delov tega dokumenta ni dovoljeno

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD EN 61558-2-15
NORME EUROPÉENNE
EUROPÄISCHE NORM June 2001
ICS 29.180
English version
Safety of power transformers, power supply units and similar
Part 2-15: Particular requirements for isolating transformers for the
supply of medical locations
(IEC 61558-2-15:1999, modified)
Sécurité des transformateurs, blocs Sicherheit von Transformatoren,
d'alimentation et analogues Netzgeräten und dergleichen
Partie 2-15: Règles particulières pour les Teil 2-15: Besondere Anforderungen an
transformateurs de séparation de circuits Trenntransformatoren zur Versorgung
pour locaux à usages médicaux medizinischer Räume
(CEI 61558-2-15:1999, modifiée) (IEC 61558-2-15:1999, modifiziert)
This European Standard was approved by CENELEC on 2000-08-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway,
Portugal, Spain, Sweden, Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2001 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61558-2-15:2001 E

---------------------- Page: 2 ----------------------

EN 61558-2-15:2001 - 2 -
Foreword
The text of document 96/119/FDIS, future edition 1 of IEC 61558-2-15, prepared by IEC TC 96, Small
power transformers, reactors and power supply units: Safety requirements, was submitted to the
IEC/CENELEC parallel vote.
The CENELEC Technical Board asked BTTF 64-1 to assess the comments received and to prepare
common modifications, as appropriate. The text of the draft was submitted to the formal vote and was
approved by CENELEC as EN 61558-2-15 on 2000-08-01.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2001-12-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2003-08-01
Annexes designated "normative" are part of the body of the standard.
In this standard, annex ZA is normative.
Annex ZA has been added by CENELEC.
This Part 2-15 of EN 61558 is to be used in conjunction with EN 61558-1:1997.
This Part 2-15 supplements or modifies the corresponding clauses of EN 61558-1, so as to convert it into
the European Standard “Particular requirements for isolating transformers for the supply of medical
locations”.
When a particular clause or subclause of Part 1 is not mentioned in this Part 2-15, that clause or
subclause applies as far as is reasonable. Where this Part 2-15 states “addition”, “modification” or
“replacement”, the relevant text of Part 1 is to be adapted accordingly.
Subclauses, tables and figures which are in addition to those of Part 1 are numbered starting with 101.
The reference of subclauses, notes, figures and annexes which have been added by CENELEC is
prefixed with the letter Z.
There are no special national conditions (snc) causing a deviation from this European Standard other
than those listed in annex ZA of EN 61558-1.
__________

---------------------- Page: 3 ----------------------

- 3 - EN 61558-2-15:2001
Endorsement notice
The text of the International Standard IEC 61558-2-15:1999 was approved by CENELEC as a European
Standard with agreed common modifications as given below.
COMMON MODIFICATIONS
1 Scope
Replace the second paragraph by:
This part 2-15 of EN 61558 applies to stationary, single-phase or polyphase, air-cooled (natural or forced)
isolating transformers for the supply of group II medical locations, designed to be perman
...