Alarm systems - Alarm transmission systems and equipment - Part 4: Annunciation equipment used in alarm receiving centres

This Technical Specification specifies the requirements and test procedures for annunciation equipment located in an alarm receiving centre. The annunciation equipment may be made up of one or more items of apparatus connected together (e.g. computers, electronic cards in separate housings, displays, keypads, printers, etc). The combination of the different apparatus is considered as one item of annunciation equipment which shall conform to the requirements of this specification. NOTE These requirements do not apply to annunciation equipment, made up of more than one piece of apparatus, when one or more parts of the annunciation equipment are outside the alarm receiving centre at which message acceptance will be performed.

Alarmanlagen - Alarmübertragungsanlagen und -einrichtungen - Teil 4: Anzeige- und Bedieneinrichtung

Systèmes d'alarme - Systèmes et équipements de transmission d'alarme - Partie 4: Equipements d'annonce

Alarmni sistemi - Sistemi in oprema za prenos alarma - 4. del: Oprema za javljanje za uporabo v sprejemnih centrih

General Information

Status
Published
Publication Date
07-Jan-2004
Technical Committee
Drafting Committee
Parallel Committee
Current Stage
6060 - Document made available - Publishing
Start Date
08-Jan-2004
Completion Date
08-Jan-2004

Buy Standard

Technical specification
TS CLC/TS 50136-4:2004
English language
24 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-junij-2004
Alarmni sistemi - Sistemi in oprema za prenos alarma - 4. del: Oprema za javljanje
za uporabo v sprejemnih centrih
Alarm systems - Alarm transmission systems and equipment - Part 4: Annunciation
equipment used in alarm receiving centres
Alarmanlagen - Alarmübertragungsanlagen und -einrichtungen - Teil 4: Anzeige- und
Bedieneinrichtung
Systèmes d'alarme - Systèmes et équipements de transmission d'alarme - Partie 4:
Equipements d'annonce
Ta slovenski standard je istoveten z: CLC/TS 50136-4:2004
ICS:
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

TECHNICAL SPECIFICATION CLC/TS 50136-4
SPECIFICATION TECHNIQUE
TECHNISCHE SPEZIFIKATION January 2004

ICS 13.320
English version
Alarm systems –
Alarm transmission systems and equipment
Part 4: Annunciation equipment
used in alarm receiving centres

Systèmes d'alarme – Alarmanlagen –
Systèmes et équipements Alarmübertragungsanlagen
de transmission d'alarme und -einrichtungen
Partie 4: Equipements d'annonce Teil 4: Anzeige- und Bedieneinrichtung

This Technical Specification was approved by CENELEC on 2003-05-31.

CENELEC members are required to announce the existence of this TS in the same way as for an EN and to
make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting
national standards in force.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland
and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. CLC/TS 50136-4:2004 E

Foreword
This Technical Specification was prepared by the Technical Committee CENELEC TC 79,
Alarm systems.
The text of the draft was submitted to the formal vote and was approved by CENELEC as
CLC/TS 50136-4 on 2003-05-31.
The following date was fixed:
- latest date by which the existence of the CLC/TS
has to be announced at national level (doa) 2004-04-08
EN 50136 will consist of the following parts, under the general title “Alarm systems - Alarm
transmission systems and equipment”:
- Part 1-1 General requirements for alarm transmission systems
- Part 1-2 Requirements for systems using dedicated alarm paths
- Part 1-3 Requirements for systems with digital communicators using the public
switched telephone network
- Part 1-4 Requirements for systems with voice communicators using the public
switched telephone network
- Part 2-1 General requirements for alarm transmission equipment
- Part 2-2 Requirements for equipment used in systems using dedicated alarm paths
- Part 2-3 Requirements for equipment used in systems with digital communicators
using the public switched telephone network
- Part 2-4 Requirements for equipment used in systems with voice communicators
using the public switched telephone network
- Part 3 (Free)
1)
- Part 4 Annunciation equipment used in alarm receiving centres
- Part 5 (Free)
- Part 6 (Free)
1)
- Part 7 Application guidelines

1)
This part is published as a Technical Specification.

- 3 - CLC/TS 50136-4:2004
Contents
Introduction.4
1 Scope.4
2 Normative references.4
3 Definitions.5
4 Requirements.6
4.1 Fault information.6
4.2 Other functions.7
4.2.1 General case.7
4.2.2 Social alarms case.7
4.3 Messages.7
4.4 Message queue.8
4.5 Input priorities.8
4.6 Alert indication.8
4.7 Message acceptance.9
4.8 Information to be presented .9
4.9 Coding of the presentation of information .9
4.10 Failure of the means of presentation of information .10
4.11 Logging.10
4.12 Access levels .10
4.13 Access to annunciation equipment .11
4.14 Access to annunciation equipment configuration data .11
4.15 Access to log data.11
4.16 Monitoring of interconnection with the receiving centre transceiver .11
4.17 Power supply.12
4.18 Power supply total failure .12
4.19 Software security.12
4.20 Monitoring of software controlled annunciation equipment.12
5 Environmental requirements .12
6 Testing.13
6.1 Conditions.13
6.2 Functional tests.13
6.3 Environmental tests.21
7 Documentation.21

Annex A (informative) Message acknowledgement and securing message.23
Annex B (informative) Presentation of messages and message acceptance.24

Introduction
This Technical Specification describes the requirements for annunciation equipment used in
alarm receiving centres.
It does not cover the operation (e.g. organisation, manning, construction of the building) of an
alarm receiving centre.
The Technical Specification defines how messages, presented to the annunciation equipment
by the receiving centre transceiver, should be secured.
The requirements of this specification apply to all messages received from an alarm
transmission system used for fire alarm systems and any alarm system within the scope of
CENELEC TC 79 (e.g. intruder systems and social alarm systems and access control systems
and CCTV systems communicating with alarm receiving centres).
1 Scope
This Technical Specification specifies the requirements and test procedures for annunciation
equipment located in an alarm receiving centre.
The annunciation equipment may be made up of one or more items of apparatus connected
together (e.g. computers, electronic cards in separate housings, displays, keypads, printers,
etc). The combination of the different apparatus is considered as one item of annunciation
equipment which shall conform to the requirements of this specification.
NOTE These requirements do not apply to annunciation equipment, made up of more than one piece of
apparatus, when one or more parts of the annunciation equipment are outside the alarm receiving centre at which
message acceptance will be performed.
2 Normative references
This Technical Specification incorporates by dated or undated references, provisions from
other publications. These normative references are cited at the appropriate place in the text
and the publications are listed hereafter. For dated references, subsequent amendments to or
revisions of any of these publications apply to this Technical Specification only when
incorporated in it by an amendment or revision. For undated references, the latest edition of
the publication referred to applies.
EN 50130-4 Alarm systems – Part 4: Electromagnetic compatibility – Product
family standard: Immunity requirements for components of fire,
intruder and social alarm systems
EN 50130-5 Part 5: Environmental test methods
EN 50134-1 Alarm systems – Social alarm systems – Part 1: System requirements
EN 50136-1-1 Alarm systems – Alarm transmission systems and equipment –
Part 1-1: General requirements for alarm transmission systems
EN 60065 Audio, video and similar apparatus – Safety requirements
(IEC 60065, mod)
EN 60073  Basic and safety principles for man-machine interface, marking and
identification – Coding principles for indicators and actuators
(IEC 60073)
EN 60950 Information technology equipment – Safety (IEC 60950, mod)
EN 61000-6-1 Electromagnetic compatibility (EMC) – Part 6-1: Generic standards -
Immunity for residential, commercial and light-industrial environments
(IEC 61000-6-1:1997, mod)
EN 61000-6-3 Electromagnetic compatibility (EMC) – Part 6-3: Generic standards -
Emission standard for residential, commercial and light-industrial
environments (IEC 61000-6-3:1996, mod)

- 5 - CLC/TS 50136-4:2004
3 Definitions
For the purpose of this Technical Specification, the following definitions apply.

3.1
annunciation equipment
equipment which presents, directly or after processing, information contained in messages

3.2
messages
a series of signals which are presented to the annunciation equipment interface by the
receiving centre transceiver
The messages are divided into four types:

3.2.1
alarm messages
messages which contain a warning that a hazard (or a potential hazard) to life or property
exists at one or more of the connected alarm systems

3.2.2
fault messages
messages which contain information that a fault has been detected in the connected alarm
systems
3.2.3
expected messages
messages from an alarm system which confirm the occurrence of a scheduled event

3.2.4
other messages
messages that are not alarm messages, fault messages or expected messages

3.3
operator
person responsible for the handling of messages presented at the annunciation equipment

3.4
queue
list of messages
3.5
message queue
queue awaiting message acceptance

3.6
log queue
list of messages waiting to be recorded in the log

3.7
log
permanent record
3.8
message acceptance
action, by an operator at the annunciation equipment, to indicate that a message has been
accepted
3.9
message acknowledgement
automatic information sent back to the receiving centre transceiver interface, confirming that
the message was passed correctly to the annunciation equipment

3.10
secured message
message which can not be lost (e.g. a message which can be retrieved in the event of power
failure)
3.11
alternative recording means
temporary record capable of storing messages and local information waiting to be logged

3.12
local information
information generated within the annunciation equipment (e.g. message acceptance, operator
actions, restart, fault conditions)

3.13
fault condition
event which prevents the annunciation equipment from functioning normally

3.14
fault information
information generated within the annunciation equipment resulting from a fault condition

3.15
presentation of information
information presented in an understandable format (e.g. names, addresses) for message
acceptance
3.16
annunciation equipment configuration data
data which influences the processing, indication, presentation, logging of messages. (e.g.
names and addresses, .)
3.17
alert indication
means to draw attention to the operator (e.g. audible and/or visual)
4 Requirements
4.1 Fault information
4.1.1 Generation of fault condition
A fault condition shall be generated within the annunciation equipment following the
corresponding fault.
4.1.2 Presentation of fault information
Fault information shall be presented within 10 s of the occurrence of the fault, unless
otherwise specified.
A fault condition resulting from the monitoring requirements specified in 4.20 shall generate
an alert indication
NOTE When the annunciation equipment is in the fault condition logging and/or presentation may be impossible.

- 7 - CLC/TS 50136-4:2004
4.2 Other functions
4.2.1 General case
When the annunciat
...