IEC TS 61000-3-5:2009/COR1:2009
(Corrigendum)Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 3-5: Limits - Limitation of voltage fluctuations and flicker in low-voltage power supply systems for equipment with rated current greater than 75 A
Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 3-5: Limits - Limitation of voltage fluctuations and flicker in low-voltage power supply systems for equipment with rated current greater than 75 A
Corrigendum 1 - Compatibilité électromagnétique (CEM) - Partie 3-5: Limites - Limitation des fluctuations de tension et du flicker dans les réseaux basse tension pour les équipements ayant un courant appelé supérieur à 75 A
General Information
Relations
Buy Standard
Standards Content (Sample)
IEC/TS 61000-3-5 CEI/TS 61000-3-5
(Second edition – 2009) (Deuxième édition – 2009)
Electromagnetic compatibility (EMC) – Compatibilité électromagnétique (CEM) –
Part 3-5: Limits – Limitation of voltage Partie 3-5: Limites – Limitation des fluctuations
fluctuations and flicker in low-voltage power de tension et du flicker dans les réseaux basse
supply systems for equipment with rated current
...
This May Also Interest You
IEC 61000-2-4:2024 is related to conducted disturbances in the frequency range from 0 kHz to 150 kHz. It gives compatibility levels in differential mode (L-L and L-N) for industrial locations, with a nominal voltage up to 35 kV and a nominal frequency of 50 Hz or 60 Hz.
NOTE 1 Industrial locations are defined in 3.1.8.
Power distribution systems on ships, aircraft, offshore platforms and railways are not included.
NOTE 2 See also Annex E. The compatibility levels specified in this document apply at the in-plant point of coupling (IPC). The level of the low-frequency disturbances at the terminals of equipment receiving its supply from the IPC is generally assumed to be similar to the disturbance level at the IPC itself. However, in some situations this is not the case, particularly when a long feeder is dedicated to the supply of a particular load, or when a disturbance is generated or amplified within the installation of which the equipment forms a part.
Compatibility levels are specified for the types of low-frequency electromagnetic disturbances expected at any in-plant point of coupling (IPC) within industrial locations, for guidance in the definition of:
a) limits for disturbance emissions in industrial power distribution systems (including the planning levels defined in 3.1.5);
NOTE 3 A very wide range of conditions is possible in the electromagnetic environments of industrial networks. These are approximated in this document by the three classes described in Clause 4. However, it is the responsibility of the operator of such a network to take account of the particular electromagnetic and economic conditions, including equipment characteristics, in setting the above-mentioned limits.
b) immunity levels for the equipment within these systems.
The disturbance phenomena considered are:
- voltage deviations;
- voltage dips and short interruptions;
- voltage imbalance;
- power-frequency variations;
- harmonics up to order 40;
- interharmonics up to the 40th harmonic;
- voltage components above the 40th harmonic up to 150 kHz;
- DC component;
- transient overvoltages.
The compatibility levels are given for different classes of environment determined by the characteristics of the supply network and loads.
NOTE 4 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000‑2‑2 for low-voltage networks and IEC 61000‑2‑12 for medium-voltage networks. IEC TR 61000‑3‑6 and IEC TR 61000‑3‑7 describe the approach of power distribution system operators to the limitation of emissions from installations and large loads.
This third edition cancels and replaces the second edition published in 2002. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) introduction of new classes 2a, 2b and 2L (former class 2);
b) modification of existing compatibility levels for class 3;
c) addition of compatibility levels in the frequency range 2 kHz to 150 kHz;
d) addition of compatibility levels using a new quantity: partial weighted harmonic distortion (PWHD).
- Standard150 pagesEnglish languagesale 15% off
- Standard96 pagesEnglish and French languagesale 15% off
IEC TR 61000-1-9:2024 which is a Technical Report, provides examples for the evaluation of measurement uncertainty of harmonic emission tests performed using IEC 61000-3-2 and IEC 61000-3-12, and their application to the relevant conformity decisions. It also contains practical formulae to enable calculations in accordance with ISO/IEC Guide 98-3 (GUM).
- Technical report23 pagesEnglish languagesale 15% off
- Standard38 pagesEnglish and French languagesale 15% off
IEC 61000-3-2:2018 deals with the limitation of harmonic currents injected into the public supply system. It specifies limits of harmonic components of the input current which can be produced by equipment tested under specified conditions. It is applicable to electrical and electronic equipment having a rated input current up to and including 16 A per phase, and intended to be connected to public low-voltage distribution systems. Arc welding equipment which is not professional equipment, with a rated input current up to and including 16 A per phase, is included in this document. Arc welding equipment intended for professional use, as specified in IEC 60974-1, is excluded from this document and can be subject to installation restrictions as indicated in IEC 61000-3-12. The tests according to this document are type tests. For systems with nominal voltages less than but not equal to 220 V (line-to-neutral), the limits have not yet been considered.
This fifth edition cancels and replaces the fourth edition published in 2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) an update of the emission limits for lighting equipment with a rated power = 25 W to take into account new types of lighting equipment;
b) the addition of a threshold of 5 W under which no emission limits apply to all lighting equipment;
c) the modification of the requirements applying to the dimmers when operating non-incandescent lamps;
d) the addition of test conditions for digital load side transmission control devices;
e) the removal of the use of reference lamps and reference ballasts for the tests of lighting equipment;
f) the simplification and clarification of the terminology used for lighting equipment;
g) the classification of professional luminaires for stage lighting and studios under Class A;
h) a clarification about the classification of emergency lighting equipment;
i) a clarification for lighting equipment including one control module with an active input power = 2 W;
j) an update of the test conditions for television receivers;
k) an update of the test conditions for induction hobs, taking also into account the other types of cooking appliances;
l) for consistency with IEC 61000-3-12, a change of the scope of IEC 61000-3-2 from equipment with an input current = 16 A to equipment with a rated input current = 16 A.
- Standard114 pagesEnglish languagesale 15% off
- Standard80 pagesEnglish languagesale 15% off
- Standard73 pagesEnglish and French languagesale 15% off
- Standard168 pagesEnglish and French languagesale 15% off
- Standard210 pagesEnglish and French languagesale 15% off
IEC TR 61000-3-18:2024 which is a technical report, reports on the development of a methodology for adapting IEC equipment emission limits from IEC 61000-3-2 and IEC 61000-3-12 for use in regions not covered by these documents. It identifies gaps in the existing equipment emission limit standards concerning their international applicability and identifies public power system characteristics important for the evaluation of harmonic voltage performance. The purpose of adapting the above-mentioned IEC equipment harmonic emission standards in a particular region is to maintain similar electromagnetic compatibility (EMC) of equipment up to 75 A per phase in the public power systems in those regions.
NOTE The boundaries between the various voltage levels differ amongst different countries (see IEC 60050‑601:1985, 601-01-28). This document uses the following terms when referring to 50 Hz and 60 Hz system voltages:
- low voltage (LV) refers to Un ≤ 1 kV;
- medium voltage (MV) refers to 1 kV - high voltage (HV) refers to 35 kV EMC requirements can have economic and societal impacts; these have not been considered in the development of this document. The consideration of these factors generally occurs in the technical committees working on development and maintenance of emission limit standards.
- Technical report58 pagesEnglish languagesale 15% off
IEC TR 61000-1-4:2022 is available as IEC TR 61000-1-4:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC TR 61000-1-4:2022 which is a technical report, reviews the sources and effects of power frequency conducted harmonic current emissions in the frequency range up to 2 kHz on the public electricity supply, and gives an account of the reasoning and calculations leading to the existing emission limits for equipment in the editions of IEC 61000-3-2, up to and including the fifth edition (2018) with Amendment 1 (2020), and in the second edition of IEC 61000-3-12. The history is traced from the first supra-national standard on low-frequency conducted emissions into the public electricity supply, EN 50006:1975 and its evolution through IEC (60)555-2 to IEC 61000-3-2, IEC TR 61000-3-4 and IEC 61000-3-12. To give a full picture of the history, that of the standard for the measuring instrument IEC 61000-4-7 is mentioned as well. NOTE All IEC standards were renumbered starting from 60000 from 1998-01-01. To indicate the references of standards withdrawn before, or not reprinted after, that date, the “60x” prefix is here enclosed in parentheses. Hence “IEC (60)555-2”. Some concepts in this document apply to all low voltage AC systems, but the numerical values apply specifically to the European 230 V/400 V 50 Hz system. This second edition cancels and replaces the first edition published in 2005. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- relation between compatibility levels, emission limits and immunity requirements clarified;
- sharing of emission levels between LV, MV and HV clarified;
- new historical information added.
- Technical report38 pagesEnglish languagesale 15% off
- Technical report94 pagesEnglish languagesale 15% off
- Standard2 pagesEnglish and French languagesale 15% off
IEC 61000-3-12:2011 deals with the limitation of harmonic currents injected into the public supply system. The limits given in this International Standard are applicable to electrical and electronic equipment with a rated input current exceeding 16 A and up to and including 75 A per phase, intended to be connected to public low-voltage a.c. distribution systems of the following types:
- nominal voltage up to 240 V, single-phase, two or three wires;
- nominal voltage up to 690 V, three-phase, three or four wires;
- nominal frequency 50 Hz or 60 Hz. Other distribution systems are excluded. The limits given in this edition apply to equipment when connected to 230/400 V, 50 Hz systems. This standard applies to equipment intended to be connected to low-voltage systems interfacing with the public supply at the low-voltage level. It does not apply to equipment intended to be connected only to private low-voltage systems interfacing with the public supply only at the medium- or high-voltage level. This standard defines:
a) requirements and emission limits for equipment;
b) methods for type tests and simulations. Tests according to this International Standard are type tests of complete pieces of equipment. Conformity with this standard can also be determined by validated simulations. This second edition cancels and replaces the first edition published in 2004 and constitutes a technical revision. The significant technical changes with respect to the previous edition are:
- the replacement of the reference fundamental current I1 by the reference current Iref for the calculation of emission limits;
- a new added table of current emission limits (Table 5);
- a new added annex (Annex A) to define test conditions for some types of equipment;
- Deletion of the former Annexes B (Approximate interpolation formulas) and D (Information on the PWHD factor).
- Standard51 pagesEnglish and French languagesale 15% off
- Standard54 pagesEnglish and French languagesale 15% off
- Standard13 pagesEnglish and French languagesale 15% off