IEC 61000-3-2:2000/AMD1:2001
(Amendment)Amendment 1 - Electromagnetic compatibility (EMC) - Part 3-2: Limits - Limits for harmonic current emissions (equipment input current <= 16 A per phase)
Amendment 1 - Electromagnetic compatibility (EMC) - Part 3-2: Limits - Limits for harmonic current emissions (equipment input current <= 16 A per phase)
Amendement 1 - Compatibilité électromagnétique (CEM) - Partie 3-2: Limites - Limites pour les émissions de courant harmonique (courant appelé par les appareils <= 16 A par phase)
General Information
Relations
Buy Standard
Standards Content (Sample)
NORME CEI
INTERNATIONALE IEC
61000-3-2
INTERNATIONAL
STANDARD
AMENDEMENT 1
AMENDMENT 1
2001-08
Amendement 1
Compatibilité électromagnétique (CEM) –
Partie 3-2:
Limites – Limites pour les émissions
de courant harmonique (courant appelé
par les appareils ≤≤≤≤16 A par phase)
Amendment 1
Electromagnetic compatibility (EMC) –
Part 3-2:
Limits – Limits for harmonic current emissions
(equipment input current ≤≤16 A per phase)
≤≤
IEC 2001 Droits de reproduction réservés Copyright - all rights reserved
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
N
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61000-3-2 amend. 1 © CEI:2001
AVANT-PROPOS
Cet amendement a été préparé par le sous-comité 77A: Phénomènes basse fréquence, du
Comité d’études n° 77 de la CEI: Compatibilité électromagnétique.
Le texte de cet amendement est basé sur les documents suivants:
FDIS Rapport de vote
77A/337/FDIS 77A/357/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l’approbation de cet amendement.
Le comité a décidé que le contenu de la publication de base et de ses amendements ne sera
pas modifié avant 2004. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
__________
Page 2
SOMMAIRE
Sous l’annexe B, supprimer les titres B.1 à B.5.
Sous l’annexe C, modifier le titre de l’article C.1 comme suit:
C.1 Généralités
Modifier le titre de l’article C.8 comme suit:
C.8 Conditions d’essai des lave-linge
Après C.15, ajouter à la liste des annexes: «Bibliographie»
Dans la liste des figures, supprimer les titres des figures 1 et 2 existantes et les remplacer
par le titre de la nouvelle figure 1:
Figure 1 – Organigramme pour déterminer la conformité
Ajouter à la liste des tableaux, après le tableau 3, le nouveau titre suivant:
Tableau 4 – Période d’observation pour les essais
61000-3-2 Amend. © IEC:2001 – 3 –
FOREWORD
This amendment has been prepared by subcommittee 77A: Low frequency phenomena, of
IEC technical committee 77: Electromagnetic compatibility.
The text of this amendment is based on the following documents:
FDIS Report on voting
77A/337/FDIS 77A/357/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until 2004. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
_____________
Page 3
CONTENTS
Under annex B, delete headings B.1 to B.5.
Under annex C, modify the heading of clause C.1 as follows:
C.1 General
The amendment of the title of C.8 applies to the French version only.
After C.15, add “Bibliography” to the list.
In the list of figures, delete the titles of the existing figures 1 and 2, and replace them by the
title of the new figure 1:
Figure 1 – Flowchart for determining conformity
Add to the list of tables, after table 3, the following new title:
Table 4 – Test observation period
– 4 – 61000-3-2 amend. 1 © CEI:2001
Page 12
1 Domaine d'application
Supprimer le dernier alinéa commençant par «Un appareil spécifique …» et finissant par
«…CEI 61000-3-4.».
2 Références normatives
Remplacer la totalité de cet article par ce qui suit:
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références
non datées, la dernière édition du document de référence s'applique (y compris les éventuels
amendements).
CEI 60050(131), Vocabulaire Electrotechnique International (VEI) – Chapitre 131: Circuits
électriques et magnétiques
CEI 60050(161), Vocabulaire Electrotechnique International (VEI) – Chapitre 161:
Compatibilité électromagnétique
CEI 60065, Appareils audio, vidéo et appareils électroniques analogues – Exigences de
sécurité
CEI 60107-1, Méthodes de mesures applicables aux récepteurs de télévision – Partie 1:
Considérations générales – Mesures aux domaines radiofréquences et vidéofréquences
CEI 60155, Interrupteurs d'amorçage à lueur pour lampes à fluorescence (starters)
CEI 60268-3, Equipements pour systèmes électroacoustiques – Partie 3: Amplificateurs
CEI 60335-2-2, Sécurité des appareils électrodomestiques et analogues – Partie 2-2: Règles
particulières pour les aspirateurs et les appareils de nettoyage à aspiration d'eau
CEI 60335-2-7, Sécurité des appareils électrodomestiques et analogues – Partie 2-7: Règles
particulières pour les machines à laver le linge
CEI 60335-2-14, Sécurité des appareils électrodomestiques et analogues – Partie 2-14:
Règles particulières pour les machines de cuisine
CEI 60974-1, Matériel de soudage électrique – Partie 1: Sources de courant pour soudage
CEI 61000-2-2, Compatibilité électromagnétique (CEM) – Partie 2: Environnement –
Section 2: Niveaux de compatibilité pour les perturbations conduites basse fréquence et la
transmission de signaux sur les réseaux publics d'alimentation à basse tension
CEI/TS 61000-3-4, Compatibilité électromagnétique (CEM) – Partie 3-4: Limites – Limitation
des émissions de courants harmoniques dans les réseaux basse tension pour les matériels
ayant un courant assigné supérieur à 16 A
CEI 61000-4-7, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d'essai et de
mesure – Section 7: Guide général relatif aux mesures d'harmoniques et d'interharmoniques
ainsi qu'à l'appareillage de mesure applicable aux réseaux d'alimentation et aux appareils qui
y sont raccordés
61000-3-2 Amend. © IEC:2001 – 5 –
Page 13
1 Scope
Delete the last paragraph beginning with "Special equipment…" and ending with
"…IEC 61000-3-4."
2 Normative references
Replace the entire existing text of clause 2 by the following:
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050(131), International Electrotechnical Vocabulary (IEV) – Chapter 131: Electric and
magnetic circuits
IEC 60050(161), International Electrotechnical Vocabulary (IEV) – Chapter 161: Electro-
magnetic compatibility
IEC 60065, Audio, video and similar electronic apparatus – Safety requirements
IEC 60107-1, Methods of measurement on receivers for television broadcast transmissions –
Part 1: General considerations – Measurements at radio and video frequencies
IEC 60155, Glow-starters for fluorescent lamps
IEC 60268-3, Sound system equipment – Part 3: Amplifiers
IEC 60335-2-2, Safety of household and similar electrical appliances – Part 2-2: Particular
requirements for vacuum cleaners and water suction cleaning appliances
IEC 60335-2-7, Safety of household and similar electrical appliances – Part 2-7: Particular
requirements for washing machines
IEC 60335-2-14, Safety of household and similar electrical appliances – Part 2-14: Particular
requirements for kitchen machines
IEC 60974-1, Arc welding equipment – Part 1: Welding power sources
IEC 61000-2-2, Electromagnetic compatibility (EMC) – Part 2: Environment – Section 2:
Compatibility levels for low-frequency conducted disturbances and signalling in public low-
voltage power supply systems
IEC/TS 61000-3-4, Electromagnetic compatibility (EMC) – Part 3-4: Limits – Limitation of
emission of harmonic currents in low-voltage power supply systems for equipment with rated
current greater than 16 A
IEC 61000-4-7, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 7: General guide on harmonics and interharmonics measurements and
instrumentation, for power supply systems and equipment connected thereto
– 6 – 61000-3-2 amend. 1 © CEI:2001
Page 14
3 Définitions
Ajouter, après la définition 3.13, la note suivante:
NOTE La puissance active d'entrée est la puissance active qui est mesurée aux bornes d'entrée d'alimentation du
matériel soumis aux essais.
Ajouter, après la définition 3.15, les nouvelles définitions suivantes:
3.16
courant harmonique total
valeur efficace totale des composantes harmoniques du courant dont les rangs vont de 2 à 40
courant harmonique total = ∑I
n
n=2
3.17
variateur de lumière incorporé
variateur de lumière, y compris le dispositif de commande pour l'utilisateur, qui est
entièrement contenu à l'intérieur de l'enveloppe d'un luminaire
3.18
courant harmonique impair partiel
valeur efficace totale des composantes harmoniques impaires du courant dont les rangs vont
de 21 à 39
courant harmonique impair partiel = ∑I
n
n=21,23
3.19
appareils d'éclairage
appareils dont une fonction principale est de produire et/ou de réguler et/ou de distribuer du
rayonnement optique au moyen de lampes à incandescence, de lampes à décharge ou de
LED
Sont inclus dans les appareils d'éclairage:
– les lampes et les luminaires;
– la partie destinée à l'éclairage des appareils à fonctions multiples, lorsqu'une des
principales fonctions de ces appareils est l'éclairement lumineux;
– les ballasts indépendants pour lampes à décharge et les transformateurs indépendants
pour lampes à incandescence;
– les appareils à rayonnement ultraviolet (UV) et infrarouge (IR);
– les enseignes publicitaires lumineuses;
– les variateurs de lumière pour les lampes qui ne sont pas à incandescence.
Sont exclus des appareils d'éclairage:
– les dispositifs d'éclairage incorporés dans des équipements ayant une fonction principale
différente tels que les photocopieurs, les rétroprojecteurs et les projecteurs de diapo-
sitives, ou employés à des fins d'indicateur ou d'éclairage de graduations;
– les variateurs de lumière pour lampes à incandescence.
61000-3-2 Amend. © IEC:2001 – 7 –
Page 15
3 Definitions
Add, after definition 3.13, the following note:
NOTE The active input power is the active power measured at the input supply terminals of the equipment under
test.
Add, after definition 3.15, the following new definitions:
3.16
total harmonic current
total r.m.s. value of the harmonic current components of orders 2 to 40
total harmonic current = ∑I
n
n=2
3.17
built-in dimmer
dimmer, including the user control, which is entirely contained within the enclosure of a
luminaire
3.18
partial odd harmonic current
total r.m.s. value of the odd harmonic current components of orders 21 to 39
partial odd harmonic current = ∑I
n
n=21,23
3.19
lighting equipment
equipment with a primary function of generating and/or regulating and/or distributing optical
radiation by means of incandescent lamps, discharge lamps or LED's
Included are:
– lamps and luminaires;
– the lighting part of multi-function equipment where one of the primary functions of this is
illumination;
– independent ballasts for discharge lamps and independent incandescent lamp
transformers;
– ultraviolet (UV) and infrared (IR) radiation equipment;
– illuminated advertising signs;
– dimmers for lamps other than incandescent.
Excluded are:
– lighting devices built in equipment with another primary purpose such as photocopiers,
overhead projectors and slide projectors or employed for scale illuminating or indication
purposes;
– dimmers for incandescent lamps.
– 8 – 61000-3-2 amend. 1 © CEI:2001
3.20
mode veille
mode (habituellement indiqué d'une façon ou d'une autre sur l'équipement) où l'appareil n'est
pas en fonctionnement et où sa consommation de puissance est faible, et qui peut se
prolonger pendant une durée indéterminée
Page 18
4 Généralités
Ajouter, à la fin de l'article 4, le nouvel alinéa suivant:
Les appareils professionnels qui ne respectent pas les exigences de la présente norme
peuvent être autorisés à être raccordés à certains types d'alimentations basse tension, si le
manuel d'instructions précise qu'il faut demander au distributeur la permission de se raccor-
der. Des recommandations concernant cet aspect se trouvent dans la CEI/TS 61000-3-4 .
5 Classification des appareils
Remplacer la totalité de l’article 5, y compris les figures 1 et 2, par le nouveau texte suivant:
Pour ce qui concerne la limitation du courant harmonique, les appareils sont classés de la
manière suivante:
Classe A:
– appareils triphasés équilibrés;
– appareils électrodomestiques à l'exclusion des appareils identifiés comme appartenant à
la classe D;
– outils à l'exclusion des outils portatifs;
– variateurs de lumière pour lampes à incandescence;
– matériels audios.
Les matériels non spécifiés dans l'une des trois autres classes doivent être considérés
comme des matériels de classe A.
NOTE 1 Les appareils dont on peut montrer qu'ils ont un effet significatif sur le réseau d'alimentation pourront
être changés de classe dans une future édition de la norme. Les facteurs à prendre en compte comprennent:
– le nombre d’appareils utilisés;
– la durée d'utilisation;
– la simultanéité d'emploi;
– la consommation de puissance;
– le spectre harmonique, y compris les phases.
Classe B:
– outils portatifs;
– appareils de soudage à l'arc hors matériel professionnel.
Classe C:
– appareils d'éclairage.
———————
Quand la CEI 61000-3-12, actuellement en préparation, sera publiée, elle remplacera la CEI/TS 61000-3-4.
61000-3-2 Amend. © IEC:2001 – 9 –
3.20
stand-by mode
sleep-mode
non-operational, low power consumption mode (usually indicated in some way on the
equipment) that can persist for an indefinite time
Page 19
4 General
Add at the end of clause 4, the following new paragraph:
Professional equipment that does not comply with the requirements of this standard may be
permitted to be connected to certain types of low voltage supplies, if the instruction manual
contains a requirement to ask the supply utility for permission to connect. Recommendations
1.
concerning this aspect are contained in IEC/TS 61000-3-4
5 Classification of equipment
Replace the entire clause 5, including figures 1 and 2,
...
Questions, Comments and Discussion