IEC 60309-2:1999+AMD1:2005 CSV
(Main)Plugs, socket-outlets and couplers for industrial purposes - Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories
Plugs, socket-outlets and couplers for industrial purposes - Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories
This standard applies to plugs and socket-outlets, cable couplers and appliance couplers with a rated operating voltage not exceeding 690 V, 500 Hz and a rated current not exceeding 125 A, primarily intended for industrial use, either indoors or outdoors. This consolidated version consists of the fourth edition (1999) and its amendment 1 (2005). Therefore, no need to order amendment in addition to this publication.
Prises de courant pour usages industriels - Partie 2: Règles d'interchangeabilité dimensionnelle pour les appareils à broches et alvéoles
La présente norme s'applique aux prises de courant, aux prolongateurs et aux connecteurs ayant une tension nominale d'emploi ne dépassant pas 690 V, 500 Hz et un courant nominal ne dépassant pas 125 A, destinés essentiellement aux usages industriels, à l'intérieur ou à l'extérieur des bâtiments. Cette version consolidée comprend la quatrième édition (1999) et son amendement 1 (2005). Il n'est donc pas nécessaire de commander l'amendement avec cette publication.
General Information
Standards Content (Sample)
IEC 60309-2
Edition 4.1 2005-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Plugs, socket-outlets and couplers for industrial purposes –
Part 2: Dimensional interchangeability requirements for pin and contact-tube
accessories
Prises de courant pour usages industriels –
Partie 2: Règles d'interchangeabilité dimensionnelle pour les appareils
à broches et alvéoles
IEC 60309-2:1999+A1:2005
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.
IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
ƒ Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
ƒ IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
ƒ Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
ƒ Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
ƒ Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
ƒ Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
ƒ Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
ƒ Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 60309-2
Edition 4.1 2005-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Plugs, socket-outlets and couplers for industrial purposes –
Part 2: Dimensional interchangeability requirements for pin and contact-tube
accessories
Prises de courant pour usages industriels –
Partie 2: Règles d'interchangeabilité dimensionnelle pour les appareils
à broches et alvéoles
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CQ
CODE PRIX
ICS 29.120.30 ISBN 2-8318-8368-7
– 2 – 60309-2 CEI:1999+A1:2005
SOMMAIRE
FOREWORD.4
INTRODUCTION.8
1 Domaine d'application .10
2 Définitions .10
3 Références normatives.12
4 Généralités.12
5 Caractéristiques normalisées.12
6 Classification.14
7 Marques et indications.14
8 Dimensions .20
9 Protection contre les chocs électriques.30
10 Dispositions en vue de la mise à la terre .30
11 Bornes et raccordements.30
12 Dispositifs de verrouillage et dispositifs de retenue .36
13 Résistance au vieillissement du caoutchouc et des matières thermoplastiques.36
14 Construction générale .38
15 Construction des socles de prises de courant.40
16 Construction des fiches et des prises mobiles .42
17 Construction des socles de connecteurs.44
18 Degrés de protection .46
19 Résistance d'isolement et rigidité diélectrique .46
20 Pouvoir de coupure .46
21 Fonctionnement normal .46
22 Echauffements .48
23 Câbles souples et leur raccordement.48
24 Résistance mécanique .48
25 Vis, parties transportant le courant et connexions.48
26 Lignes de fuite, distances dans l'air et distances à travers la matière
de remplissage .48
27 Résistance à la chaleur, au feu et aux courants de cheminement .48
28 Corrosion et résistance à la rouille .48
29 Essai de tenue au courant de court-circuit potentiel.50
30 Compatibilité électromagnétique.50
Feuilles de normes .52
Figures .86
Annexe AA (informative) Liste des articles qui requièrent de procéder
à de nouveaux essais .100
60309-2 IEC:1999+A1:2005 – 3 –
CONTENTS
FOREWORD.5
INTRODUCTION.9
1 Scope.11
2 Definitions .11
3 Normative references .13
4 General .13
5 Standard ratings .13
6 Classification.15
7 Marking .15
8 Dimensions .21
9 Protection against electric shock .31
10 Provision for earthing .31
11 Terminals and terminations .31
12 Interlocks and retaining devices .37
13 Resistance to ageing of rubber and thermoplastic material .37
14 General construction .39
15 Construction of socket-outlets .41
16 Construction of plugs and connectors .43
17 Construction of appliance inlets.45
18 Degrees of protection .47
19 Insulation resistance and dielectric strength .47
20 Breaking capacity .47
21 Normal operation.47
22 Temperature rise .49
23 Flexible cables and their connection.49
24 Mechanical strength .49
25 Screws, current-carrying parts and connections.49
26 Creepage distances, clearances and distances through sealing compound .49
27 Resistance to heat, fire and tracking.49
28 Corrosion and resistance to rusting .49
29 Conditional short-circuit current withstand test .51
30 Electromagnetic compatibility .51
Standards sheets.53
Figures .87
Annex AA (informative) List of the clause numbers that require re-testing.101
– 4 – 60309-2 © CEI:1999+A1:2005
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
PRISES DE COURANT POUR USAGES INDUSTRIELS –
Partie 2: Règles d'interchangeabilité dimensionnelle pour
les appareils à broches et alvéoles
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation composée de
l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de favoriser
la coopération internationale pour toutes les questions de normalisation dans les domaines de l'électricité et de
l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes internationales, des Spécifications
techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des Guides (ci-après
dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des comités d'études, aux travaux desquels
tout Comité national intéressé par le sujet traité peut participer. Les organisations internationales, gouvernementales
et non gouvernementales, en liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement
avec l'Organisation Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux
organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure du
possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI intéressés
sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées comme
telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI s'assure de
l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable de l'éventuelle
mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications nationales et
régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications nationales ou régionales
correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa responsabilité
pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou mandataires, y
compris ses experts particuliers et les membres de ses comités d'études et des Comités nationaux de la CEI, pour
tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre dommage de quelque nature que
ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais de justice) et les dépenses découlant de
la publication ou de l'utilisation de cette Publication de la CEI ou de toute autre Publication de la CEI, ou au crédit qui
lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire l’objet
de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour responsable de ne pas
avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60309-2 a été établie par le sous-comité 23H: Prises de courant
à usage industriel, du comité d'études 23 de la CEI: Petit appareillage.
La présente partie 2 doit être lue conjointement avec la partie 1.
La présente version consolidée de la CEI 60309-2 comprend la quatrième édition (1999)
[documents 23H/89/FDIS et 23H/92/RVD] et son amendement 1 (2005) [documents
23H/175/FDIS et 23H/183/RVD].
Le contenu technique de cette version consolidée est donc identique à celui de l'édition de
base et à son amendement; cette version a été préparée par commodité pour l'utilisateur.
Elle porte le numéro d'édition 4.1.
Une ligne verticale dans la marge indique où la publication de base a été modifiée par
l'amendement 1.
60309-2 © IEC:1999+A1:2005 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
PLUGS, SOCKET-OUTLETS AND COUPLERS
FOR INDUSTRIAL PURPOSES –
Part 2: Dimensional interchangeability requirements
for pin and contact-tube accessories
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60309-2 has been prepared by subcommittee 23H: Industrial plugs
and socket-outlets, of IEC technical committee 23: Electrical accessories.
This part 2 shall be used in conjunction with part 1.
This consolidated version of IEC 60309-2 consists of the fourth (1999) [documents
23H/89/FDIS and 23H/92/RVD] and its amendment 1 (2005) [documents 23H/175/FDIS and
23H/183/RVD].
The technical content is therefore identical to the base edition and its amendment and has
been prepared for user convenience.
It bears the edition number 4.1.
A vertical line in the margin shows where the base publication has been modified by
amendment 1.
– 6 – 60309-2 CEI:1999+A1:2005
Le comité a décidé que le contenu de la publication de base et de ses amendements ne sera
pas modifié avant la date de maintenance indiquée sur le site web de la CEI sous
"http://webstore.iec.ch" dans les données relatives à la publication recherchée. A cette date,
la publication sera
• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.
60309-2 IEC:1999+A1:2005 – 7 –
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until the maintenance result date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date,
the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 8 – 60309-2 CEI:1999+A1:2005
INTRODUCTION
La présente norme comporte plusieurs parties:
Partie 1: Règles générales, qui comprend les articles de caractère général.
Parties suivantes: Règles particulières, traitant de types particuliers. Les articles de ces
règles particulières représentent des compléments ou modifications aux articles
correspondants de la première partie. Si le texte des parties suivantes indique une «addition»
ou un «remplacement» des règles, essais ou commentaires pertinents de la première partie,
ces changements sont introduits dans les passages pertinents de la première partie, et ils
deviennent alors des parties de la norme. Lorsque aucune modification n'est nécessaire, les
mots «L'article de la première partie est applicable» sont utilisés.
60309-2 IEC:1999+A1:2005 – 9 –
INTRODUCTION
This standard is divided into several parts:
Part 1: General requirements, comprising clauses of a general character.
Subsequent parts: Particular requirements dealing with particular types. The clauses of these
particular requirements supplement or modify the corresponding clauses in Part 1. Where the
text of subsequent parts indicates an "addition" to or a "replacement" of the relevant
requirement, test specification or explanation of Part 1, these changes are made to the
relevant text of Part 1, which then becomes part of the standard. Where no change is
necessary, the words "This clause of Part 1 is applicable" are used.
– 10 – 60309-2 CEI:1999+A1:2005
PRISES DE COURANT POUR USAGES INDUSTRIELS –
Partie 2: Règles d'interchangeabilité dimensionnelle pour
les appareils à broches et alvéoles
1 Domaine d'application
Remplacement:
La présente norme s'applique aux prises de courant, aux prolongateurs et aux connecteurs
ayant une tension nominale d'emploi ne dépassant pas 690 V, 500 Hz et un courant nominal
ne dépassant pas 125 A, destinés essentiellement aux usages industriels, à l'intérieur ou à
l'extérieur des bâtiments.
NOTE Toutes références aux appareils ayant un courant nominal dépassant 125 A dans la partie 1 ne sont plus
valables dans cette deuxième partie.
La présente norme s'applique aux prises de courant, aux prolongateurs et aux connecteurs
comportant des broches et des alvéoles de contact, ayant des configurations normalisées.
La présente norme s'applique aux prises de courant, aux prolongateurs et aux connecteurs,
désignés dans la suite du texte sous le nom d'appareils, pour usage dans une température
ambiante comprise normalement dans une plage de –25 °C à 40 °C.
L'usage de ces appareils dans des chantiers de construction et pour des applications
agricoles, commerciales et domestiques n'est pas exclu.
La présente norme s'applique aux appareils équipés de bornes sans vis ou de bornes à
perçage d’isolant, de courant nominal ne dépassant pas 16 A pour la série I et 20 A pour la
série II.
NOTE Dans les pays suivants, la présente norme s'applique aux appareils équipés de bornes sans vis ou
de bornes à perçage d’isolant, de courant nominal ne dépassant pas 32 A pour la série I et 30 A pour la série II:
DE, IT.
Les socles de prises de courant et les socles de connecteurs incorporés ou fixés au matériel
électrique sont compris dans le domaine d'application de la présente norme. La présente
norme s'applique aussi aux appareils destinés à être utilisés dans les installations à très
basse tension.
NOTE La présente norme ne s'applique pas aux appareils destinés essentiellement aux usages domestiques et
aux usages généraux analogues.
Pour l'emploi dans des locaux présentant des conditions particulières, par exemple à bord des navires et dans les
locaux présentant des risques d'explosion, des prescriptions complémentaires peuvent être nécessaires.
2 Définitions
L'article de la partie 1 est applicable avec l'exception suivante:
Paragraphe complémentaire:
2.101
inverseur de phases
une fiche ou un socle de connecteur avec un dispositif permettant d'interchanger la position
de deux broches de phases sans les déconnecter des conducteurs
60309-2 IEC:1999+A1:2005 – 11 –
PLUGS, SOCKET-OUTLETS AND COUPLERS
FOR INDUSTRIAL PURPOSES –
Part 2: Dimensional interchangeability requirements for
pin and contact-tube accessories
1 Scope
Replacement:
This standard applies to plugs and socket-outlets, cable couplers and appliance couplers with
a rated operating voltage not exceeding 690 V, 500 Hz and a rated current not exceeding 125
A, primarily intended for industrial use, either indoors or outdoors.
NOTE All references for accessories with a rated current of more than 125 A in part 1 are not applicable to this
part 2.
This standard applies to plugs and socket-outlets, cable couplers and appliance couplers with
pins and contact tubes of standardized configurations.
This standard applies to plugs and socket-outlets, cable couplers and appliance couplers,
hereinafter referred to as accessories, for use when the ambient temperature is normally
within the range –25 °C to 40 °C.
The use of these accessories on building sites and for agricultural, commercial and domestic
applications is not precluded.
This standard applies to accessories with screwless type terminals or insulation piercing
terminals, with a rated current up to and including 16 A for Series I and 20 A for Series II .
NOTE In the following countries, this standard applies to accessories with screwless type terminals or insulation
piercing terminals, with a rated current up to and including 32 A for Series I and 30 A for Series II : DE, IT.
Socket-outlets or appliance inlets incorporated in or fixed to electrical equipment are within
the scope of this standard. This standard also applies to accessories intended to be used in
extra-low voltage installations.
NOTE This standard does not apply to accessories primarily intended for domestic and similar general purposes.
In locations where special conditions prevail, for example on board ship or where explosions are liable to occur,
additional requirements may be necessary.
2 Definitions
This clause of part 1 is applicable except as follows:
Additional subclause:
2.101
phase inverter
a plug or an appliance inlet with operating means to interchange the position of two phase
pins without disconnecting them from the conductors
– 12 – 60309-2 CEI:1999+A1:2005
3 Références normatives
L'article de la partie 1 est applicable avec l'exception suivante:
Addition:
CEI 60617-2: 1996, Symboles graphiques pour schémas – Partie 2: Eléments de symboles,
symboles distinctifs et autres symboles d'application générale
4 Généralités
L'article de la partie 1 est applicable avec l'exception suivante:
4.1 Le dernier alinéa de ce paragraphe de la Partie 1 n’est pas applicable.
Voir Amendement 1 de la CEI 60309-1.
Paragraphe complémentaire:
4.101 Si des calibres sont utilisés, ils doivent être faits en acier trempé. Tous les coins
doivent être légèrement arrondis avec un rayon maximal de 0,1 mm et l'état de surface pour
N8
toutes les surfaces servant aux mesures doit être min., sauf spécification contraire.
Dans cette norme:
2P + inclut 2P + et 1P + N + et
3P + inclut 3P + et 2P + N +
à moins que le contraire ne soit explicitement spécifié (voir Tableau 104).
5 Caractéristiques normalisées
L'article de la partie 1 est applicable avec l'exception suivante:
5.2 Remplacement:
Les courants nominaux normalisés sont donnés dans le Tableau 101.
Tableau 101
Série I Série II
A A
16 20
32 30
63 60
125 100
5.101 Les degrés de protection IP normalisés selon la CEI 60529 sont:
– IP44,
– IP67,
– IP66/IP67
60309-2 IEC:1999+A1:2005 – 13 –
3 Normative references
This clause of part 1 is applicable except as follows:
Addition:
IEC 60617-2:1996, Graphical symbols for diagrams – Part 2: Symbol elements, qualifying
symbols and other symbols having general application
4 General
This clause of part 1 is applicable except as follows:
4.1 The last paragraph of this subclause of Part 1 is not applicable.
See Amendment 1 of IEC 60309-1.
Additional subclause:
4.101 If gauges are used, they shall be of hardened steel, all corners shall be slightly
rounded-off with a maximum radius of 0,1 mm, and the surface finish for all measurement
N8
surfaces shall be min., if not otherwise specified.
In this standard:
2P + covers both 2P + and 1P + N + and
3P + covers both 3P + and 2P + N +
unless specifically excluded (see Table 104).
5 Standard ratings
This clause of part 1 is applicable except as follows:
5.2 Replacement:
Standard rated currents are given in Table 101.
Table 101
Series I Series II
A A
16 20
32 30
63 60
125 100
5.101 The standard IP ratings according to IEC 60529 are:
– IP44,
– IP67,
– IP66/IP67.
– 14 – 60309-2 CEI:1999+A1:2005
6 Classification
L'article de la partie 1 est applicable avec l'exception suivante:
6.1.2 L'article de la Partie 1 est applicable.
7 Marques et indications
L'article de la partie 1 est applicable avec l'exception suivante:
7.1 Modification:
Supprimer la note
Addition:
Le symbole indiquant la position du contact de terre ou de l'ergot ou de la rainure auxiliaire
doit être placé avant ou au-dessus du nombre indiquant la tension nominale d'emploi, et
séparé de celui-ci par une ligne.
Ces indications doivent être placées après celle du courant nominal, un trait les séparant si le
symbole indiquant la position du contact de terre ou de l'ergot ou de la rainure auxiliaire et le
nombre indiquant la tension nominale d'emploi sont séparés par une ligne oblique.
Si l'on utilise un symbole pour la nature du courant, il doit être placé aussitôt après ou
au-dessous de l'indication de la tension nominale d'emploi.
Pour les appareils triphasés il n'est pas nécessaire de marquer la tension phase neutre, si
elle existe.
L'indication du ou des courants nominaux, de la position du contact de terre ou de l'ergot ou
de la rainure auxiliaire, de la ou des tensions nominales d'emploi et de la nature du courant
peut, par exemple, avoir les formes suivantes:
Pour la série I:
9 h
16 A - 9 h/400 V~, ou 16 - 9 h/400~, ou 16 - , ou
400 ~
9 h
16 A - 9 h/380-415 V~, ou 16 - 9 h/380-415~, ou 16 -
380 - 415 ~
6 h
32 A - 6 h/230/400 V~, ou 32 - 6 h/230/400~, ou 32 - , ou
230 / 400 ~
6 h
6 h / 220 / 380 V ~ 6 h / 220 / 380 ~
32 A - , ou 32 - , ou 32 -
220 / 380 ~
240 / 415 V ~ 240 / 415 V ~
240 / 415 ~
60309-2 IEC:1999+A1:2005 – 15 –
6 Classification
This clause of part 1 is applicable except as follows:
6.1.2 This clause of Part 1 is applicable.
7 Marking
This clause of part 1 is applicable except as follows:
7.1 Modification:
Delete the note
Addition:
The symbol indicating the position of the earthing contact or of the minor key or keyway shall
be placed before or above the figure for the rated operating voltage, and separated from it by
a line.
These markings shall be placed after that for rated current, separated from it by a dash if an
oblique line separates the symbol indicating the position of the earthing contact or of the
minor key or keyway from the figure for the rated operating voltage.
If a symbol for nature of supply is used, it shall be placed next to or below the marking for
rated operating voltage.
For three-phase accessories it is not necessary to mark the voltage phase to neutral, if any.
The marking for rated current(s), position of the earthing contact or the minor key, keyway,
rated operating voltage(s) and nature of supply accordingly may be as follows:
For series I:
9 h
16 A - 9 h/400 V~, or 16 - 9 h/400~, or 16 - , or
400 ~
9 h
16 A - 9 h/380-415 V~, or 16 - 9 h/380-415~, or 16 -
380 - 415 ~
6 h
32 A - 6 h/230/400 V~, or 32 - 6 h/230/400~, or 32 - , or
230 / 400 ~
6 h
6 h / 220 / 380 V ~ 6 h / 220 / 380 ~
32 A - , or 32 - , or 32 -
220 / 380 ~
240 / 415 V ~ 240 / 415 V ~
240 / 415 ~
– 16 – 60309-2 CEI:1999+A1:2005
Pour la série II
7 h
20 A - 7 h/480 V a.c. ou 20 A - 7 h/480~, ou 20 A -
480 ~
7 h
30 A - 7 h/480 V, 3 Phase, ou 30 A - 7 h/480, 3Φ, ou 30 A -
480 V, 3Φ
7 h
60 A - 7 h/277/480 V, 3 Phase Y, ou 60 A - 7 h/277/480, 3ΦY, ou 60 A -
277 / 480 V, 3Φ Y
Il est permis de mettre les symboles (~) pour courant alternatif et ( ou ) pour courant
continu après les valeurs (CEI 60617-2).
Les dessins figurant sur les feuilles de normes 2-I, 2-II, 2-III et 2-lV représentent des
appareils ayant le symbole 6 h, et ceux figurant sur les feuilles de normes 2-VIII et 2-lX
représentent des appareils ayant le symbole 12 h.
Pour les appareils de tension nominale d'emploi dépassant 50 V, le symbole indiquant la
position du contact de terre doit être une valeur suivie de la lettre h.
La valeur est déduite de la position de l'alvéole de terre, par comparaison à un cadran
d'horloge, le socle de prise de courant ou la prise mobile étant vu de devant et la rainure
étant sur la sixième heure.
Pour les appareils de tension nominale d'emploi ne dépassant pas 50 V, le symbole indiquant
la position de l'ergot doit être une valeur suivie de la lettre h.
La valeur est déduite de la position de l'ergot auxiliaire, par comparaison à un cadran
d'horloge, le socle de prise de courant ou la prise mobile étant vu de devant et l'ergot
principal étant sur la sixième heure.
Pour les fiches et les socles de connecteurs, le symbole indiquant la position du contact de
terre ou de la rainure auxiliaire doit être identique à celui du socle de prise de courant ou de
la prise mobile correspondante.
Les alvéoles des socles de prises de courant et des prises mobiles doivent se trouver dans le sens
de rotation des aiguilles d'une montre, si l'on regarde les alvéoles de l'avant conformément aux
feuilles de normes (voir aussi 7.5)
Les broches des fiches et des socles des connecteurs doivent se trouver dans l'ordre opposé,
si l'on regarde les broches de l'avant.
7.2 L'article de la Partie 1 est applicable.
7.4 Remplacement
Pour les fiches et les prises mobiles, le marquage spécifié en 7.1 doit être distingué lorsque
l'appareil est équipé de ses conducteurs et prêt à l'emploi.
L'indication de la tension d'isolement doit être portée sur la partie principale; elle ne doit pas être
visible lorsque l'appareil est installé et équipé de ses conducteurs comme en usage normal.
NOTE 1 L'expression «prêt à l'emploi» n'implique pas qu'une fiche ou une prise mobile soit engagée dans
l'appareil complémentaire.
NOTE 2 L'expression «partie principale» d'une fiche ou d'une prise mobile désigne la partie qui porte les
contacts.
La conformité est vérifiée par examen.
60309-2 IEC:1999+A1:2005 – 17 –
For series II
7 h
20 A - 7 h/480 V a.c. or 20 A - 7 h/480~, or 20 A -
480 ~
7 h
30 A - 7 h/480 V, 3 Phase, or 30 A - 7 h/480, 3Φ, or 30 A -
480 V, 3Φ
7 h
60 A - 7 h/277/480 V, 3 Phase Y, or 60 A - 7 h/277/480, 3ΦY, or 60 A -
277 / 480 V, 3Φ Y
It is allowed to put the symbols for a.c. (~) and d.c. ( or ) after the values (IEC 60617-2).
The drawings of standard sheets 2-I, 2-II, 2-III and 2-lV show accessories with the symbol 6 h
and those of standard sheets 2-VIII and 2-lX accessories with the symbol 12 h.
For accessories having rated operating voltages exceeding 50 V, the symbol indicating the
position of the earthing contact shall be a numeral followed by the letter h.
The numeral is derived from the position of the earth contact tube, when compared with the
face of a clock, the socket-outlet or connector being viewed from the front with the keyway at
the sixth hour.
For accessories having rated operating voltages not exceeding 50 V, the symbol indicating
the position of the minor key shall be a numeral followed by the letter h.
The numeral is derived from the position of the minor key, when compared with the face of a
clock, the socket-outlet or connector being viewed from the front with the major key at the
sixth hour.
For plugs and appliance inlets, the symbol indicating the position of the earthing contact or
the minor keyway shall be the same as that for the corresponding socket-outlet or connector.
Contact tubes of socket-outlets and connectors shall be positioned in the clockwise order
when viewed from the front as shown in the standard sheets (see also 7.5).
Pins of plugs and appliance inlets shall be positioned in the opposite order viewed from the
front.
7.2 This clause of Part 1 is applicable.
7.4 Replacement
For plugs and connectors, the marking specified in 7.1 shall be easily discernible when the
accessory is wired ready for use.
The marking for insulation voltage shall be on the main part; it shall not be visible when the
accessory is mounted and wired as in normal use.
NOTE 1 The term "ready for use" does not imply that the plug or connector is engaged with its complementary
accessory.
NOTE 2 The term "main part" of a plug or a connector means the part carrying the contacts.
Compliance is checked by inspection.
– 18 – 60309-2 CEI:1999+A1:2005
7.5 Remplacement
Pour les appareils démontables les contacts doivent être repérés par les symboles suivants.
– pour les appareils avec trois contacts (phase + neutre + terre, ou, phase + phase + terre)
L / +, non marqué, ou
sauf pour la série II position 4 h et 5 h qui sont marqués comme suit:
N, non marqué, ou
– pour les appareils avec quatre contacts (trois phases + terre):
L1, L2, L3, ou ou en variante 1, 2, 3 ou
sauf pour la série II position 12 h (monophasé + trou central + monophasé + terre) qui est
marqué:
L1, N, L2, ou
– pour les appareils avec cinq contacts (trois phases + neutre + terre):
L1, L2, L3, N, ou ou en variante 1, 2, 3, N, ou
– pendant un temps, les indications R1, S2, T3 peuvent être utilisées à la place de L1, L2, L3.
– pour les appareils de tension nominale d'emploi inférieure ou égale à 50 V, en position 8 h
pour couveuses électriques portables: +12, +24.
Ces symboles doivent être placés près des bornes correspondantes; ils ne doivent pas être
placés sur des vis, des rondelles amovibles ou d'autres parties amovibles.
Pour les inverseurs de phases ces symboles doivent être conformes avec les prescriptions
de 7.1 dans une seule position. Dans l'autre position du dispositif d'inversion, le marquage
des phases n'a pas besoin d'être conforme.
NOTE Aucun repérage n'est requis pour les bornes des conducteurs pilotes.
Les chiffres utilisés avec des lettres peuvent être écrits en indice. Il est recommandé d'utiliser, si possible, le
symbole
La conformité est vérifiée par inspection.
7.7 Modification:
Le paragraphe de la partie 1 est applicable avec l'adjonction suivante:
Ajouter:
Les appareils 2P + N + terre, 12 h, de la série II, doivent utiliser des indications de couleur orange.
60309-2 IEC:1999+A1:2005 – 19 –
7.5 Replacement
For rewirable accessories, the contacts shall be indicated by the following symbols.
– for accessories with three contacts (phase + neutral + earth, or, phase + phase + earth):
L / +, unmarked, or
except for Series II clock position 4 h and 5 h which are marked:
N, unmarked, or
– for accessories with four contacts (three phase + earth):
L1, L2, L3, or or alternatively 1, 2, 3, or
except for Series II clock position 12 h (phase + centre tap + phase + earth) which is
marked:
L1, N, L2, or
– for accessories with five contacts (three phase + neutral + earth):
L1, L2, L3, N, or or alternatively 1, 2, 3, N or
– for a period of time the marking R1, S2, T3 may be used instead of L1, L2, L3.
– for accessories having a rated operating voltage not exceeding 50 V, 8 h clock position for
portable electric incubator : +12, +24.
These symbols shall be placed close to the relevant term
...