IEC 60079-1:2026
(Main)Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
- Abstract
IEC 60079-1:2026 contains specific requirements for the construction and testing of Ex Equipment and Ex Components with the Type of Protection flameproof enclosure "d", intended for use in explosive gas atmospheres.
This document supplements and modifies the general requirements of IEC 60079‑0. Where a requirement of this document conflicts with a requirement of IEC 60079‑0, the requirement of this document takes precedence.
This eighth edition constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 8.0 and the previous edition of the document.
Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the "history" tab of the page for each document.
- Status
- Published
- Publication Date
- 08-Oct-2026
- Technical Committee
- TC 31 - Equipment for explosive atmospheres
- Drafting Committee
- MT 60079-1 - Equipment protection by flameproof enclosures "d"
- Current Stage
- PPUB - Publication issued - 60 Publication
- Start Date
- 09-Oct-2026
- Due Date
- 30-Oct-2026
- Completion Date
- 30-Oct-2026
Buy Documents
IEC 60079-1:2026 - Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-1:2026 - Atmospheres explosives - Partie 1: Protection des appareils par enveloppes antidéflagrantes "d"
IEC 60079-1:2026 is an IEC International Standard for explosive atmospheres. It specifies how to construct and test Ex Equipment and Ex Components with the Type of Protection flameproof enclosure "d" for use in explosive gas atmospheres. The document supplements IEC 60079-0, and where the two conflict, IEC 60079-1:2026 takes precedence.
What does IEC 60079-1:2026 specify?
IEC 60079-1:2026 sets out the detailed requirements for flameproof enclosures "d", including enclosure construction, joint design, entry devices, testing, marking and instructions. It applies to Ex Equipment and Ex Components and is organized into clauses 1 to 22, followed by annexes A to I.
| Annex | What it covers |
|---|---|
| A | Additional requirements for crimped ribbon elements and multiple screen elements of breathing and draining devices |
| B | Additional requirements for elements with non-measurable paths in breathing and draining devices |
| C | Additional requirements for flameproof entry devices |
| D | Empty flameproof enclosures as Ex Components |
| E | Cells and batteries used in flameproof enclosures |
| F | Mechanical properties for screws and nuts |
| G | Additional requirements for flameproof enclosures with a containment system |
| H | Electric machines used with converters |
| I | Recommendation to improve the effectiveness of the determination of explosion pressure |
The main body covers the general protection levels, flameproof joints, sealed joints, operating rods, electric machines, breathing and draining devices, fasteners, materials, entries, batteries, testing, switchgear for Group I, lampholders, non-metallic enclosures, marking and instructions.
What are the key requirements of IEC 60079-1:2026?
IEC 60079-1:2026 is mainly about keeping an internal explosion inside the enclosure while preventing ignition of the surrounding atmosphere. In practice, that means the enclosure geometry, materials, fasteners, entries and test results all have to work together as part of the protection concept.
Protection levels and overall design
IEC 60079-1:2026 defines three Levels of Protection for flameproof enclosure "d": da, db and dc, corresponding to equipment protection levels (EPL) Ma or Ga, Mb or Gb, and Gc. Clause 4 says the document applies to all levels unless a later clause states a special rule. For a designer or certifier, this means the intended level must be fixed early because it drives the construction and testing route.
Level of Protection "da" is a special case for catalytic sensors in certain gas detection equipment. The sensor volume is limited, the conductors must enter through a sealed joint in the sensor wall, the breathing device must be bonded or press-fitted so that gaps are eliminated, and the sensor must be supplied by an "ia" circuit with a limited dissipated power. Clause 4 also requires a higher number of non-transmission tests. In practice, "da" is not a general-purpose flameproof solution, but a narrow one for specific gas detection applications.
Level of Protection "db" follows the general requirements of the document except where the "da" and "dc" rules add further conditions. Level of Protection "dc" has its own construction and type-test requirements in Clause 4.4. That matters because the same flameproof enclosure family can be assessed at different protection levels, but not with the same evidence package.
Flameproof joints, sealed joints and moving parts
Clause 5 is the core of the standard. It requires all flameproof joints, whether permanently closed or opened during installation or maintenance, to meet the dimensional requirements and the relevant tests. The clause covers non-threaded joints, threaded joints, gaskets, capillaries and a range of joint geometries such as spigot, cylindrical, conical, serrated and multi-step forms. For the user, this means the flamepath is a controlled design feature, not an incidental manufacturing detail.
The document uses minimum lengths, maximum gaps and thread engagement rules to define flamepath performance. When the joint dimensions are outside the standard limits, the certificate and instructions have to carry the extra conditions of use, including the "X" suffix where applicable. That is important for maintenance and repair because the enclosure may depend on exact dimensions that must be preserved over its life.
Clause 6 covers cemented, fused glass, welded, brazed and moulded sealed joints. Clause 7 covers operating rods, and Clause 8 adds extra requirements for electric machines, including shaft joints and bearings. In practice, any moving penetration through the enclosure wall has to be treated as part of the explosion-protection design.
Entries, fasteners and materials
Clause 11 controls fasteners and openings. Fasteners that pass through enclosure walls have to form a flameproof joint or be permanently fixed, and special fasteners are required when they are accessible from outside and needed for assembly. Plastic fasteners and light-alloy fasteners are not permitted. Blind holes, thread inserts and openings for optional devices all have specific conditions. This matters because a small fastening detail can affect the integrity of the whole enclosure.
Clause 12 sets material rules. Cast iron must be at least grade 150, zinc and zinc alloys with 80 % zinc or more are not allowed, and some insulating materials in Group I enclosures need a comparative tracking index (CTI) of at least 400 M when they are exposed to electrical stresses capable of arcing. Liquids are allowed only when they do not create a more hazardous atmosphere by decomposition, or when the enclosure passes the relevant tests for the mixture produced. For buyers and manufacturers, these rules affect material selection, supplier qualification and change control.
Clause 13 covers threaded and non-threaded entries, cable glands, conduit sealing devices, plugs and sockets, bushings, blanking elements, thread adapters and fluid entries. Separate entries may be treated as Ex Equipment or Ex Components depending on type and Group, while non-threaded entries for Groups IIA and IIB are only Ex Components. Annex C adds the detailed construction and test requirements. In practice, the entry device is not an accessory - it is part of the certified protection system.
Verification, type tests and routine tests
Clauses 15 to 17 define verification, type tests and routine tests. Type testing starts with determination of explosion pressure, followed by overpressure testing and the test for non-transmission of an internal ignition. Non-metallic enclosures and parts add an erosion-by-flame test. Clause 17 requires routine testing to confirm pressure resistance and freedom from holes or cracks, and it provides special treatment for welded or brazed joints and batch testing. That is the basis for both certification and production control.
The test program changes with the equipment family. Clause 16 gives separate paths for Groups I, IIA, IIB and IIC, and for flameproof enclosures with breathing and draining devices. Clause 15 also ties surface-temperature determination to defined overload or malfunction conditions for luminaires and electric machines. For the practical user, this means the test plan has to match the exact equipment type, not just the enclosure shape.
Special equipment, marking and instructions
Clause 18 deals with Group I switchgear that is opened on site and can produce arcs or sparks. Clause 19 covers lampholders and lamp caps that form a flameproof enclosure together, and Clause 20 applies special rules to non-metallic enclosures and non-metallic parts, including tracking, creepage and flame-erosion testing. These clauses matter where the enclosure is part of a larger functional assembly rather than a simple housing.
Clause 21 sets marking for da, db and dc, plus caution, warning and informative markings. Clause 22 requires instructions to include flamepath details where needed, selection guidance for entry and breathing/draining devices at higher reference pressures, information for non-threaded entries, and containment-system instructions where applicable. In practice, the label and the instructions carry part of the safety case.
What terms does IEC 60079-1:2026 define?
- flameproof enclosure "d" - an enclosure that contains parts able to ignite an explosive gas atmosphere, withstands the pressure of an internal explosion, prevents transmission of the explosion to the outside atmosphere, and avoids external surface temperatures capable of ignition.
- flameproof joint or flamepath - the place where enclosure parts meet in a way intended to stop flame transmission from inside to outside.
- sealed joint - a joint sealed by a material intended to prevent transmission of an internal explosion to the surrounding explosive gas atmosphere.
- containment system - the part of the equipment that contains a flammable or non-flammable substance that can become an internal source of release.
- internal source of release - a point or location from which a substance can be released into the enclosure so that an explosive gas atmosphere could form.
- quick-acting door or quick-acting cover - a door or cover that opens or closes by a simple operation, with a separate locking or unlocking stage.
- door fixed by threaded fasteners - a door or cover that requires screws, studs, bolts or nuts to open or close.
Who uses IEC 60079-1:2026?
IEC 60079-1:2026 is used by manufacturers of Ex Equipment and Ex Components, certification bodies, and test laboratories that assess flameproof designs. It is also used by design engineers, quality managers and buyers who need to specify or review flameproof enclosures, entry devices, cable glands, bushings, blanking elements, batteries, electric machines, switchgear and luminaires.
The standard is relevant in industries that use explosive gas atmospheres, including Group I applications and Group II gas applications. It is particularly important for gas detection equipment, electric machines, switchgear, lighting equipment and enclosure component suppliers because the details of joints, entries, markings and tests directly affect certification and maintenance.
What changed in IEC 60079-1:2026 from the previous edition?
IEC 60079-1:2026 is the eighth edition and the foreword describes it as a technical revision. The change list visible in the document includes a clarification for the application of bushing requirements to moulded joints, removal of the limitation that previously did not allow the use of a blanking element with a thread adaptor, and a significant rewrite of Annex G. The foreword also states that the full list of technical changes is given there.
Which standards are used with IEC 60079-1:2026?
IEC 60079-1:2026 refers to several standards that supply general requirements, methods or component definitions used in flameproof design and testing:
- IEC 60079-0 - the general requirements baseline for Ex Equipment and Ex Components.
- IEC 60079-7 - increased safety requirements used for clearances, creepage distances and some lampholder and insulation provisions.
- IEC 60079-11 - intrinsic safety requirements used for certain circuits and isolation arrangements.
- IEC 60061 - lamp caps, lamp holders and gauges for interchangeability and safety.
- IEC 60086-1 - primary batteries, used in Annex E for acceptable cell systems.
- IEC 60127 and ANSI/UL 248 - miniature and low-voltage fuse standards used where fuse selection matters.
- ISO 185 - cast iron classification for material selection.
- ISO 228-1, ISO 965-1 and ISO 965-3 - thread dimensions and tolerances for threaded entries and joints.
- ANSI/ASME B1.20.1 - NPT pipe thread requirements.
- ISO 2859-1 - sampling by attributes for batch testing.
- ISO 4003 and ASTM F316 - bubble-test and pore-size methods for sintered and porous elements.
- ISO 80000-1 - quantity and unit rules used when rounding dimensions.
What does the IEC 60079-1:2026 document contain?
IEC 60079-1:2026 contains many dimensioned tables, test conditions and construction examples that are central to design and certification work. The tables cover joint lengths and gaps, threaded joint engagement, batch sampling, static pressures, battery systems and tightening torques, while the figures illustrate flange, spigot, cylindrical, conical and serrated joints, gasket arrangements, blanking elements and sealing-test setups.
The annexes add detailed methods for breathing and draining devices, entry devices, empty enclosures as Ex Components, batteries, containment systems and electric machines with converters. The document also includes acceptance criteria, routine-test options and marking text that manufacturers and certifiers use to document the approved configuration.
Relations
- Effective Date
- 05-Sep-2023
- Revises
IEC 60079-1:2014 - Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d" - Effective Date
- 05-Sep-2023
- Effective Date
- 05-Sep-2023
Buy Documents
IEC 60079-1:2026 - Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-1:2026 - Atmospheres explosives - Partie 1: Protection des appareils par enveloppes antidéflagrantes "d"
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
IEC 60079-1:2026 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"". This standard covers: IEC 60079-1:2026 contains specific requirements for the construction and testing of Ex Equipment and Ex Components with the Type of Protection flameproof enclosure "d", intended for use in explosive gas atmospheres. This document supplements and modifies the general requirements of IEC 60079‑0. Where a requirement of this document conflicts with a requirement of IEC 60079‑0, the requirement of this document takes precedence. This eighth edition constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 8.0 and the previous edition of the document. Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the "history" tab of the page for each document.
IEC 60079-1:2026 contains specific requirements for the construction and testing of Ex Equipment and Ex Components with the Type of Protection flameproof enclosure "d", intended for use in explosive gas atmospheres. This document supplements and modifies the general requirements of IEC 60079‑0. Where a requirement of this document conflicts with a requirement of IEC 60079‑0, the requirement of this document takes precedence. This eighth edition constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 8.0 and the previous edition of the document. Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the "history" tab of the page for each document.
IEC 60079-1:2026 is classified under the following ICS (International Classification for Standards) categories: 29.260.20 - Electrical apparatus for explosive atmospheres. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 60079-1:2026 has the following relationships with other standards: It is inter standard links to IEC 60079-1:2014/ISH1:2020, IEC 60079-1:2014, IEC 60079-1:2014/COR1:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
IEC 60079-1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 flameproof enclosure "d"
- 3.2 enclosure volume
- 3.3 flameproof joint
- 3.4 length
- 3.5 distance
- 3.6 gap
- 3.7 maximum experimental safe gap
- 3.8 shaft
- 3.9 operating rod
- 3.10 pressure piling
- 1 Pressure Rise Time
- 2 Maximum Rate of Rise
- 3 Explosion Pressure Curve
- 1 Pressure Rise Time
- 3.11 quick-acting door
- 3.12 door fixed by threaded fasteners
- 3.13 sealed joint
- 3.14 threaded door
- 3.15 containment system
- 3.16 flammable substance
- 3.17 internal source of release
- 4 Level of Protection
- 4.1 General
- 4.2 Requirements for Level of Protection "da"
- 4.3 Requirements for Level of Protection "db"
- 4.4 Requirements for Level of Protection "dc"
- 5 Flameproof joints
- 5.1 General requirements
- 5.2 Non-threaded flameproof joints
- 1 Flameproof enclosure
- 2 Cylindrical dowel driven into hole
- 3 Cover
- 1 Flameproof joint gap (Normal Clearance)
- 2 Gap During Explosion (Clearance During Explosion)
- 5.3 Threaded flameproof joints
- 5.4 Gaskets (including O-rings)
- 2 O-ring
- 5.5 Equipment using capillaries
- 6 Sealed joints
- 6.1 Cemented joints
- 6.2 Fused glass joints
- 6.3 Welded or brazed joints
- 6.4 Moulded joints
- 7 Operating rods
- 8 Supplementary requirements for electric machines
- 8.1 Flameproof joints of shafts
- 8.2 Bearings
- 9 Light-transmitting parts
- 10 Breathing and draining devices which form part of a flameproof enclosure
- 10.1 General
- 10.2 Openings for breathing or draining
- 10.3 Composition limits
- 10.4 Dimensions
- 10.5 Elements with measurable paths
- 10.6 Elements with non-measurable paths
- 10.7 Removable devices
- 10.8 Mounting arrangements of the elements
- 10.9 Mechanical strength
- 10.10 Breathing devices and draining devices when used as Ex Components
- 11 Fasteners and openings
- 11.1 General
- 11.2 Construction
- 11.3 Type tests
- 11.4 Blind holes
- 11.5 Openings
- 11.6 Thread inserts used for threaded holes
- 12 Materials
- 12.1 General
- 12.2 Metals
- 12.3 Insulating materials
- 12.4 Liquids
- 13 Entries and entry devices for flameproof enclosures
- 13.1 Threaded entries
- 13.2 Non-threaded entries (for Groups I, IIA and IIB only)
- 2 O-ring (opt.)
- 3 M8 × 1,25 × 16 capscrew / M8 × 2 washer (opt.)
- 4 Keeper plate
1 Scope
This part of IEC 60079 contains specific requirements for the construction and testing of Ex Equipment and Ex Components with the Type of Protection flameproof enclosure "d", intended for use in explosive gas atmospheres.
This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60061 (all parts), Lamp caps and holders together with gauges for the control of interchangeability and safety IEC 60079-0, Explosive atmospheres - Part 0: Equipment - General requirements IEC 60079-7, Explosive atmospheres - Part 7: Equipment protection by increased safety "e" IEC 60079-11, Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i" IEC 60086-1, Primary batteries - Part 1: General IEC 60127 (all parts), Miniature fuses ISO 185:2020, Grey cast irons - Classification ISO 228-1, Pipe Threads Where Pressure-Tight Joints Are Not Made on the Threads - Part 1:
Dimensions, Tolerances and Designation ISO 965-1:2013, ISO general purpose metric screw threads - Tolerances - Part 1: Principles and basic data ISO 965-3:2021, ISO general purpose metric screw threads - Tolerances - Part 3: Limit deviations for screw threads ISO 2859-1:1999, Sampling procedures for inspection by attributes - Part 1: Sampling schemes indexed by acceptance quality limit (AQL) for lot-by-lot inspection ISO 4003:1977, Permeable sintered metal materials - Determination of bubble test pore size ISO 80000-1:2022, Quantities and units - Part 1: General ANSI/ASME B1.20.1, Pipe threads, general purpose (inch)ANSI/UL 248 (all parts), Low-Voltage Fuses ASTM F316, Standard Test Methods for Pore Size Characteristics of Membrane Filters by Bubble Point and Mean Flow Pore Test
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60079-0 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- IEC Electropedia: available at https://www.electropedia.org/ - ISO Online browsing platform: available at https://www.iso.org/obp NOTE Additional definitions applicable to explosive atmospheres can be found in the International Electrotechnical Vocabulary, IEC 60050-426.
3.1 flameproof enclosure "d"
enclosure in which the parts that can ignite an explosive gas atmosphere are placed and which is intended to a) withstand the pressure developed during an internal explosion of an explosive mixture, b) prevent the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure, and c) not have external surface temperatures that are capable of igniting a surrounding explosive gas atmosphere
3.2 enclosure volume
<flameproof enclosure> total internal volume of the enclosure of flameproof "d" equipment Note 1 to entry: For enclosures in which the contents are essential in service, the volume to be considered is the remaining free volume.
Note 2 to entry: For luminaires, the volume is determined without lamps fitted.
3.3 flameproof joint
flamepath place where the corresponding surfaces of two parts of an enclosure, or the conjunction of enclosures, come together and which is intended to prevent the transmission of an internal explosion to the explosive gas atmosphere surrounding the enclosure
3.4 length
width of flameproof joint L <flameproof joint> shortest path through a flameproof joint from the inside to the outside of an enclosure
3.5 distance
<flameproof joint> shortest path through a flameproof joint, when the length of the flameproof joint L is interrupted by holes intended for the passage of fasteners for assembling the parts of the flameproof enclosure
3.6 gap
<flameproof joint> distance between the corresponding surfaces of a flameproof joint when the flameproof enclosure has been assembled Note 1 to entry: i is the maximum flameproof joint gap, as specified on the schedule drawings. C Note 2 to entry: i is the test gap.
E
3.7 maximum experimental safe gap
MESG maximum gap of a flameproof joint of 25 mm in length which prevents any transmission of an explosion during 10 tests made under the conditions specified in ISO/IEC 80079-20-1 [2] [SOURCE: ISO/IEC 80079-20-1:2017, 3.4, modified – the number of tests is added and reference to ISO/IEC 80079-20-1 is made in place of “this standard.” ]
3.8 shaft
part of circular cross-section used for the transmission of rotary movement
3.9 operating rod
part used for the transmission of control movements which can be rotary or linear or a combination of the two
3.10 pressure piling
results of an ignition, in a compartment or subdivision of an enclosure, of a gas mixture precompressed, for example, due to a primary ignition in another compartment or subdivision Note 1 to entry: There is presumption of pressure-piling when either (1) the pressure values obtained during a series of tests involving the same configuration, deviate from one to another by a factor of ≥1,5, or (2) the pressure rise time is less than 5 ms. Two graphs are provided below for guidance on how to consider pressure rise time. When referring to these two graphs below, the pressure rise time is based on the elapsed time at the point of the maximum rate of rise of the pressure. This is normally the elapsed time between 10 % and 90 % of the maximum pressure. Actual waveforms sometimes exhibit a more regular shape as shown in Figure 1, or an irregular shape as shown in Figure 2. When determining the pressure rise time, a plateau such as shown at the beginning of the waveform in Figure 2 is excluded.
Key
1 Pressure Rise Time
2 Maximum Rate of Rise
3 Explosion Pressure Curve
Figure 1 – Example of a regular shaped waveform
Key
1 Pressure Rise Time
Figure 2 – Example of an irregular shaped waveform
3.11 quick-acting door
quick-acting cover door or cover provided with a device which permits opening or closing by a simple operation, such as the movement of a lever or the rotation of a wheel Note 1 to entry: The device is arranged so that the operation has two stages: one for locking or unlocking, and another for opening or closing.
3.12 door fixed by threaded fasteners
cover fixed by threaded fasteners door or cover, the opening or closing of which requires the manipulation of one or more threaded fasteners (screws, studs, bolts or nuts)
3.13 sealed joint
place where the corresponding surfaces of two parts of an enclosure, or the conjunction of enclosures, come together and which are sealed by a material intended to prevent the transmission of an internal explosion to the explosive gas atmosphere surrounding the enclosure
3.14 threaded door
threaded cover door or cover which is assembled to a flameproof enclosure by a threaded flameproof joint
3.15 containment system
part of the equipment containing the flammable or non-flammable substance that can constitute an internal source of release Note 1 to entry: The requirements for containment systems as part of flameproof enclosures also apply to the use of non-flammable substances, due to the possibility of increasing the pressure within the flameproof enclosure above the reference pressure to which the enclosure has been tested (see Annex G).
3.16 flammable substance
substance which is itself flammable, or is capable of producing a flammable gas, vapour or mist [SOURCE: IEC 60079-10-1:2020 [3], 3.6.1]
3.17 internal source of release
point or location from which a flammable substance or non-flammable substance can be released into the enclosure such that in the presence of air an explosive gas atmosphere could be formed Note 1 to entry: The requirements for containment systems as part of flameproof enclosures also apply to the use of non-flammable substances, due to the possibility of increasing the pressure within the flameproof enclosure above the standard atmospheric conditions.(see Annex G).
4 Level of Protection
4.1 General
Equipment with flameproof enclosure "d" shall be one of the following:
a) Level of Protection "da" (EPL "Ma" or "Ga"); b) Level of Protection "db" (EPL "Mb" or "Gb"); or c) Level of Protection "dc" (EPL "Gc").
The requirements of this document shall apply to all Levels of Protection unless otherwise stated.
4.2 Requirements for Level of Protection "da"
Level of Protection "da" is only applicable to catalytic sensors of:
a) portable, transportable or fixed gas detection equipment for Group I; and b) portable gas detection equipment for Group II.
NOTE 1 For anticipated applications, these sensors are not intended to be exposed to explosive mixtures of gases or vapours for extended periods of time since alarm actions are intended to mitigate exposure to explosive mixtures upon detection. In typical Group I applications, these sensors and associated detectors are used to monitor for the explosive atmosphere during release or ventilation failure conditions. In a typical Group II application, these sensors and associated detectors are used to verify that an explosive gas atmosphere does not exist in order to permit maintenance activities.
The following are the additional specific requirements for Level of Protection "da" that modify or supplement the requirements of this document:
a) the maximum free internal volume shall not exceed 5 cm ; b) the electrical conductors into the sensor shall employ a sealed joint, in accordance with Clause 6, directly in the wall of the sensor enclosure; c) the breathing device of the sensor shall comply with Clause 10, but shall be bonded to the wall of the enclosure so as to eliminate any gaps (such as cementing per 6.1 or sinter bonding) or shall be press-fitted to the wall of the enclosure with supplemental mechanical means of securing (such as swaging); d) shall be supplied by a circuit of Level of Protection "ia", with a maximum dissipated power limited to 3,3 W for Group I and 1,3 W for Group II; and NOTE 2 Catalytic elements operate normally at a high temperature. If the power dissipation is increased beyond normal operating levels, the element fails to an open circuit. Therefore, the required power limitation provides a limitation of the external surface temperature.
e) the non-transmission tests of 16.3 or 16.4.4 (if applicable) are modified to increase the number of non-transmission tests as shown in Table 1.
Table 1 – Number of non-transmission tests for Level of Protection "da" Equipment group Number of non-transmission tests I 50 IIA 50 IIB 50 IIC 50 hydrogen and 50 acetylene
4.3 Requirements for Level of Protection "db"
Other than specific requirements for Level of Protection "da" and "dc", all other requirements of this document shall apply to Level of Protection "db".
4.4 Requirements for Level of Protection "dc"
4.4.1 General
Level of Protection "dc" is only applicable to Ex Equipment and Ex Components with electrical switching contacts. The requirements for Level of Protection "dc" are found in 4.4.2 through 4.4.3.
4.4.2 Construction
4.4.2.1 General
The requirements of 4.4.2.2 through 4.4.2.5 replace those of Clause 5 through Clause 13. For equipment in Level of Protection "dc" that is intended for connection to field wiring, Clause 13 applies.
As a minimum the schedule drawings shall include the manufacturer and model number, along with the electrical ratings and COT for Level of Protection "dc" equipment.
4.4.2.2 Free internal volume
The free internal volume shall not exceed 20 cm .
4.4.2.3 COT requirements
Poured seals and encapsulating compounds shall have a COT that includes a minimum temperature that is below, or equal to, the minimum service temperature and a maximum temperature that is at least 10 K above the maximum service temperature.
4.4.2.4 Ratings
Devices shall be limited to a maximum rating of 16 A at 1 000 V AC or 1 500 V DC.
4.4.2.5 Connection facilities
Equipment shall be provided with connection facilities employing one of the following:
a) Field wiring connection facilities in accordance with Clause 13 intended to be connected using an appropriate EPL Gc connection method; b) Factory wiring connection facilities employing individual conductors (flying leads) intended to be connected using appropriate EPL Gc connection methods; or c) Factory wiring connection facilities employing integral terminations intended to be connected using an appropriate EPL Gc connection method (for example, pins soldered to a printed wiring board).
NOTE The most commonly applied connection facility uses Level of Protection "ec".
4.4.3 Type tests
Level of Protection "dc" equipment shall be subjected to the type test specified in 16.5. After the test, the equipment shall show no visible damage, no external ignition shall occur, and there shall be no failure to clear the arc when the switch contacts are opened.
5 Flameproof joints
5.1 General requirements
All flameproof joints, whether permanently closed or designed to be opened during installation or maintenance, shall comply, in the absence of pressure, with the appropriate requirements of Clause 5 and shall be subjected to the tests specified in Clause 15 through Clause 17 as applicable.
A material that hardens after the flameproof joint is assembled (for example, a locking compound on threaded flameproof joints) shall not be used on a flameproof joint that is designed to be opened during installation or maintenance. See Clause 22. When thread locking compound for fasteners is used to secure flameproof joints, it shall be such that the compound does not migrate onto flamepath surfaces. The design of flameproof joints shall be appropriate to the mechanical constraints applied to them.
The dimensions given in 5.2 to 5.5 specify the essential parameters of flamepaths. In instances where any of the following apply (for example, in order to comply with the test for nontransmission of an internal ignition):
a) the minimum length of the flameproof joint as stated by the documentation is greater than the relevant minimum; b) the maximum gap of the flameproof joint as stated by the documentation is less than the relevant maximum; or c) the minimum number of threads engaged for the flameproof joint as stated by the documentation is more than the relevant minimum, NOTE IEC 60079-0 defines the documentation as the documents that give a full and correct specification of the explosion safety aspects of the Ex Equipment and Ex Components. the Ex Equipment certificate number shall include the "X" suffix in accordance with the marking requirements of IEC 60079-0 and the Specific Conditions of Use listed on the certificate shall detail one of the following:
- dimensions of the flameproof joints shall be detailed;
- a specific drawing referenced that details the dimensions of the flameproof joints;
- specific guidance noted to contact the original manufacturer for information on the dimensions of the flameproof joints, and when applicable, specific guidance for repairing threaded flameproof joints having a thread locking compound; or
- specific indication that the flameproof joints are not intended to be repaired. The surface of a flamepath may be protected against corrosion.
- Paint or powder-coat finish shall not be applied to flameproof joint surfaces.
- Other coating materials may be used if the material and application procedure have been shown not to adversely affect the flameproof properties of the flameproof joint.
- Corrosion inhibiting grease, such as petrolatum or soap-thickened mineral oils, may be applied to flameproof joint surfaces before assembly. The grease, if applied, shall be of a type that does not harden because of ageing, does not contain an evaporating solvent, and does not cause corrosion of the flameproof joint surfaces. Verification of suitability shall be in accordance with the grease manufacturer's specifications.
Flameproof joint surfaces may be electroplated. The metal plating, if applied, shall be in accordance with the following:
- if not more than 0,008 mm thick, no additional consideration is necessary; or
- if more than 0,008 mm thick, then the maximum gap without the plating shall still be in accordance with the applicable flameproof joint requirements and shall be tested for flame transmission based on the gap dimension that would exist without the plating. Where equipment is rated for a specific gas and a specific equipment group (for example, IIB + H ), the enclosure shall comply with the requirements for the specific gas, and the requirements
for the lower equipment group.
5.2 Non-threaded flameproof joints
5.2.1 Length of flameproof joints (L)
The length of flameproof joints shall not be less than the minimum values given in Table 2 and Table 3 as applicable.
For volume ≤ 10 cm , the flameproof joint lengths need not comply with the values given in Table 2 or Table 3, provided the requirements of Clauses 14 through 16 are satisfied and the compliant construction is detailed in the schedule drawings.
The length of flameproof joints for cylindrical metallic parts press-fitted into the walls of a
metallic flameproof enclosure of a volume not greater than 2 000 cm may be reduced to 5 mm, if a) the design does not rely only on an interference fit to prevent the part being displaced during the type tests of Clause 16, b) the assembly meets the impact test requirements of IEC 60079-0, taking the worst-case interference fit tolerances into account, and c) the external diameter of the press-fitted part, where the length of the flameproof joint is measured, does not exceed 60 mm.
NOTE There is no prohibition of press-fit combinations of other than metallic parts into metallic flameproof enclosures. In these other combinations, the minimum length of flameproof joint requirements of Table 2 or Table 3 apply.
5.2.2 Gap (i)
The gap at any point, if one exists, between the surfaces of a flameproof joint shall not exceed the maximum values given in Table 2 or Table 3 as applicable.
NOTE 1 The average of the gap is not applied when determining gap (i).
For volume ≤ 10 cm , the flameproof joint gaps need not comply with the values given in Table 2 or Table 3, provided the requirements of Clauses 14 through 16 are satisfied and the compliant construction is detailed in the schedule drawings.
The surfaces of flameproof joints shall be such that their average roughness R does not exceed a 6,3 μm.
NOTE 2 Average roughness determination can be made by visual comparison to a reference plate. For flanged flameproof joints of other than quick-acting doors or covers, there shall be no intentional gap between the surfaces other than that created by the flatness tolerances of the mating parts.
For equipment of Group I, it shall be possible to check, directly or indirectly, the gaps of flanged flameproof joints of covers and doors designed to be opened.
Figure 3 shows an example of construction for indirect checking of a flameproof joint.
Key
1 Flameproof enclosure
2 Cylindrical dowel driven into hole
3 Cover
L Length of flameproof joint Surface of cover and dowel shall be in the same plane Figure 3 – Example of construction for indirect checking of a flanged Group I flameproof joint
...
Contents
- 1 Domaine d’application
- 2 Références normatives
- 3 Termes et définitions
- 3.1 enveloppe antidéflagrante "d"
- 3.2 volume de l’enveloppe
- 3.3 joint antidéflagrant
- 3.4 longueur
- 3.5 distance
- 3.6 interstice
- 3.7 interstice expérimental maximal de sécurité
- 3.8 arbre
- 3.9 tige de commande
- 3.10 phénomène de précompression
- 1 Temps d’augmentation de la pression
- 2 Vitesse maximale de montée
- 3 Courbe de la pression de l’explosion
- 1 Temps d’augmentation de la pression
- 3.11 porte à manœuvre rapide
- 3.12 porte à vis
- 3.13 joint scellé
- 3.14 porte vissée
- 3.15 système de confinement
- 3.16 substance inflammable
- 3.17 source interne de dégagement
- 4 Niveau de protection
- 4.1 Généralités
- 4.2 Exigences qui s’appliquent au niveau de protection "da"
- 4.3 Exigences qui s’appliquent au niveau de protection "db"
- 4.4 Exigences qui s’appliquent au niveau de protection "dc"
- 5 Joints antidéflagrants
- 5.1 Exigences générales
- 5.2 Joints non filetés antidéflagrants
- 1 Enveloppe antidéflagrante
- 2 Goujon cylindrique enfoncé dans l’orifice
- 3 Couvercle
- 1 Intérieur de l’enveloppe
- 1 Intérieur de l’enveloppe
- 1 Intérieur de l’enveloppe
- 1 Intérieur de l’enveloppe
- 1 Intérieur de l’enveloppe
- 1 Intérieur de l’enveloppe
- 5.3 Joints filetés antidéflagrants
- 5.4 Garnitures d’étanchéité (y compris les joints toriques)
- 1 Intérieur de l’enveloppe
- 2 Joint torique
- 3 Garniture d’étanchéité
- 4 Garniture d’étanchéité métallique ou à gaine métallique
- 5.5 Appareils utilisant des capillaires
- 6 Joints scellés
- 6.1 Joints scellés (collés)
- 6.2 Joints en verre fondu
- 6.3 Joints soudés ou brasés
- 6.4 Joints enrobés
- 7 Tiges de commande
- 8 Exigences supplémentaires pour machines électriques
- 8.1 Joints antidéflagrants des arbres
- 1 Interstice k Jeu radial minimal admissible sans frottement
- 8.2 Paliers
- 9 Parties transparentes ou translucides
- 10 Dispositifs de respiration et de drainage faisant partie d’une enveloppe
- 10.1 Généralités
- 10.2 Ouvertures pour respiration ou drainage
- 10.3 Teneurs limites
- 10.4 Dimensions
- 10.5 Éléments avec passages mesurables
- 10.6 Éléments avec passages non mesurables
- 10.7 Dispositifs démontables
- 10.8 Dispositions de montage des éléments
- 10.9 Résistance mécanique
- 10.10 Dispositifs de respiration et de drainage utilisés comme composants Ex
- 11 Fermetures et ouvertures
- 11.1 Généralités
- 11.2 Composition
- 11.3 Essais de type
- 11.4 Trous borgnes
- 11.5 Ouvertures
- 11.6 Inserts filetés utilisés pour les trous taraudés
- 12 Matériaux
- 12.1 Généralités
- 12.2 Métaux
1 Domaine d’application
La présente partie de l’IEC 60079 contient les exigences spécifiques de construction et d’essai des appareils Ex et des composants Ex du mode de protection "d", destinés à être utilisé dans les atmosphères explosives gazeuses.
Le présent document complète et modifie les exigences générales de l’IEC 60079-0. Si une exigence du présent document est en conflit avec une exigence de l’IEC 60079-0, l’exigence du présent document prévaut.
2 Références normatives
Les documents suivants sont cités dans le texte de sorte qu’ils constituent, pour tout ou partie de leur contenu, des exigences du présent document. Pour les références datées, seule l’édition citée s’applique. Pour les références non datées, la dernière édition du document de référence s’applique (y compris les éventuels amendements).
IEC 60061 (toutes les parties), Culots de lampes et douilles ainsi que calibres pour le contrôle de l’interchangeabilité et de la sécurité IEC 60079-0, Atmosphères explosives - Partie 0: Matériel - Exigences générales IEC 60079-7, Atmosphères explosives - Partie 7: Protection du matériel par sécurité augmentée "e" IEC 60079-11, Atmosphères explosives - Partie 11: Protection de l’équipement par sécurité intrinsèque "i" IEC 60086-1, Piles électriques - Partie 1: Généralités IEC 60127 (toutes les parties), Coupe-circuit miniatures ISO 185:2020, Fontes à graphite lamellaire - Classification (disponible en anglais seulement) ISO 228-1, Filetages de tuyauterie pour raccordement sans étanchéité dans le filet - Partie 1:
Dimensions, tolérances et désignation ISO 965-1:2013, Filetages métriques ISO pour usages généraux - Tolérances - Partie 1:
Principes et données fondamentales ISO 965-3:2021, Filetages métriques ISO pour usages généraux - Tolérances - Partie 3: Écarts limites pour filetages ISO 2859-1:1999, Règles d’échantillonnage pour les contrôles par attributs - Partie 1:
Procédures d’échantillonnage pour les contrôles lot par lot, indexés d’après le niveau de qualité acceptable (NQA) ISO 4003:1977, Matériaux en métal fritté perméable - Détermination de la dimension des pores - Méthode bulloscopique ISO 80000-1:2022, Grandeurs et unités – Partie 1: Généralités ANSI/ASME B1.20.1, Pipe threads, general purpose (inch) ANSI/UL 248 (toutes les parties), Low-Voltage Fuses
ASTM F316, Standard Test Methods for Pore Size Characteristics of Membrane Filters by Bubble Point and Mean Flow Pore Test
3 Termes et définitions
Pour les besoins du présent document, les termes et les définitions de l’IEC 60079-0, ainsi que les suivants, s’appliquent.
L’ISO et l’IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation, consultables aux adresses suivantes:
- IEC Electropedia: disponible à l’adresse https://www.electropedia.org/ - ISO Online browsing platform: disponible à l’adresse https://www.iso.org/obp NOTE Des définitions supplémentaires qui s’appliquent aux atmosphères explosives peuvent être consultées dans le Vocabulaire Électrotechnique International, IEC 60050-426.
3.1 enveloppe antidéflagrante "d"
enveloppe dans laquelle les pièces qui peuvent enflammer une atmosphère explosive gazeuse sont enfermées et qui est destinée à:
a) résister à la pression développée lors d’une explosion interne d’un mélange explosif; b) empêcher la transmission de l’explosion à l’atmosphère explosive gazeuse environnante de l’enveloppe; et c) ne pas présenter de températures de surface externe susceptible d’enflammer une atmosphère explosive environnante
3.2 volume de l’enveloppe
<enveloppe antidéflagrante> volume interne total de l’enveloppe d’un appareil antidéflagrant "d" Note 1 à l’article: Pour les enveloppes dont le contenu est absolument nécessaire en service, le volume à prendre en considération est le volume libre restant.
Note 2 à l’article: Dans le cas des luminaires, le volume est déterminé sans lampe dans le luminaire.
3.3 joint antidéflagrant
passage de flamme endroit où les surfaces correspondantes de deux éléments d’une enveloppe ou la partie commune d’enveloppes se rejoignent et qui est destiné à empêcher la transmission d’une explosion interne à l’atmosphère explosive gazeuse environnante de l’enveloppe
3.4 longueur
longueur du joint antidéflagrant L <joint antidéflagrant> chemin le plus court à travers un joint antidéflagrant entre l’intérieur et l’extérieur d’une enveloppe
3.5 distance
<joint antidéflagrant> chemin le plus court à travers un joint antidéflagrant, lorsque la longueur du joint antidéflagrant, L, est interrompue par des orifices destinés au passage de vis d’assemblage des éléments de l’enveloppe antidéflagrante
3.6 interstice
<joint antidéflagrant> distance entre les surfaces correspondantes d’un joint antidéflagrant lorsque l’enveloppe antidéflagrante a été assemblée Note 1 à l’article: i est l’interstice maximal du joint antidéflagrant, tel que spécifié sur les dessins annexés. C Note 2 à l’article: i est l’interstice d’essai.
E
3.7 interstice expérimental maximal de sécurité
IEMS interstice maximal d’un joint antidéflagrant de 25 mm de longueur qui empêche toute transmission d’une explosion pendant 10 essais réalisés dans les conditions spécifiées dans l’ISO/IEC 80079-20-1 [2] [SOURCE: ISO/IEC 80079-20-1:2017, 3.4, modifié – le nombre d’essais a été ajouté et la référence à l’ISO/IEC 80079-20-1 a été faite à la place de "la présente norme"]
3.8 arbre
organe de section circulaire utilisé pour la transmission d’un mouvement de rotation
3.9 tige de commande
organe pour la transmission de mouvements de commande qui peuvent être de rotation ou de translation ou une combinaison des deux
3.10 phénomène de précompression
résultat de l’inflammation, dans un compartiment ou une division de l’enveloppe, d’un mélange gazeux précomprimé, par exemple par une première inflammation dans un autre compartiment ou une autre division Note 1 à l'article: Il y a présomption d’un phénomène de précompression lorsque soit (1) les valeurs de pression obtenues au cours d’une série d’essais dans la même configuration s’écartent les unes des autres d’un facteur ≥ 1,5, soit (2) le temps d’augmentation de la pression est inférieur à 5 ms. Deux graphiques sont fournis ci-dessous à titre de recommandations sur la manière de prendre en compte le temps d’augmentation de la pression. Dans les deux graphiques ci-dessous, le temps d’augmentation de la pression est fondé sur le temps écoulé au point correspondant à la vitesse maximale d’augmentation de la pression. Il s’agit normalement du temps écoulé entre 10 % et 90 % de la pression maximale. Les formes d’onde réelles présentent parfois une forme plus régulière comme représenté à la Figure 1, ou une forme irrégulière comme représenté à la Figure 2. Lors de la détermination du temps d’augmentation de la pression, un palier tel que celui représenté au début de la forme d’onde à la Figure 2 est exclu.
Légende
1 Temps d’augmentation de la pression
2 Vitesse maximale de montée
3 Courbe de la pression de l’explosion
Figure 1 – Exemple de forme d’onde régulière
Légende
1 Temps d’augmentation de la pression
Figure 2 – Exemple de forme d’onde irrégulière
3.11 porte à manœuvre rapide
couvercle à manœuvre rapide porte ou couvercle équipé d’un dispositif permettant d’en effectuer l’ouverture ou la fermeture par une opération simple, telle que le mouvement d’un levier ou la rotation d’un volant Note 1 à l'article: Un tel dispositif est agencé de manière que l’opération comporte deux phases: une pour le verrouillage ou le déverrouillage, et l’autre pour l’ouverture ou la fermeture.
3.12 porte à vis
couvercle à vis porte ou couvercle dont l’ouverture et la fermeture exigent la manipulation d’une ou de plusieurs fermetures vissées (vis, goujons, boulons ou écrous)
3.13 joint scellé
endroit où les surfaces correspondantes de deux éléments d’une enveloppe ou la partie commune d’enveloppes se rejoignent et sont scellées par un matériau destiné à empêcher la transmission d’une explosion interne à l’atmosphère explosive gazeuse environnante de l’enveloppe
3.14 porte vissée
couvercle vissé porte ou couvercle assemblé à une enveloppe antidéflagrante par un joint fileté antidéflagrant
3.15 système de confinement
partie des appareils contenant la substance inflammable ou ininflammable qui peut constituer une source interne de dégagement Note 1 à l'article: Les exigences relatives aux systèmes de confinement faisant partie des enveloppes antidéflagrantes s’appliquent également à l’utilisation de substances ininflammables, en raison de la possibilité d’augmentation de la pression à l’intérieur de l’enveloppe antidéflagrante au-delà de la pression de référence à laquelle l’enveloppe a été soumise à essai (voir Annexe G).
3.16 substance inflammable
substance inflammable par elle-même ou capable de produire un gaz, une vapeur ou un brouillard inflammable [SOURCE: IEC 60079-10-1:2020 [3], 3.6.1]
3.17 source interne de dégagement
point ou emplacement où une substance inflammable ou ininflammable peut se dégager dans l’enveloppe, de telle façon qu’en présence d’air une atmosphère explosive gazeuse puisse se former Note 1 à l'article: Les exigences relatives aux systèmes de confinement faisant partie des enveloppes antidéflagrantes s’appliquent également à l’utilisation de substances ininflammables, en raison de la possibilité d’augmentation de la pression à l’intérieur de l’enveloppe antidéflagrante au-delà des conditions atmosphériques normales (voir Annexe G).
4 Niveau de protection
4.1 Généralités
L’appareil à enveloppe antidéflagrante "d" doit avoir:
a) un niveau de protection "da" (EPL "Ma" ou "Ga"), b) un niveau de protection "db" (EPL "Mb" ou "Gb"), ou c) un niveau de protection "dc" (EPL "Gc").
Les exigences du présent document doivent s’appliquer à tous les niveaux de protection, sauf spécification contraire.
4.2 Exigences qui s’appliquent au niveau de protection "da"
Le niveau de protection "da" s’applique uniquement aux capteurs catalytiques:
a) équipements de détection de gaz portables, transportables ou fixes pour le groupe I, et b) équipements de détection de gaz portables du groupe II.
NOTE 1 Pour les applications prévues, ces capteurs ne sont pas destinés à être exposés à des mélanges explosifs de gaz ou de vapeurs pendant de longues périodes, car les actions d’alarme sont destinées à limiter l’exposition à des mélanges explosifs lors de leur détection. Dans les applications types du groupe I, ces capteurs et les détecteurs associés sont utilisés pour surveiller l’atmosphère explosive pendant des conditions de dégagement ou de défaillance de ventilation. Dans une application type du groupe II, ces capteurs et les détecteurs associés sont utilisés pour vérifier qu’il n’existe pas d’atmosphère explosive gazeuse afin de permettre des activités de maintenance. Les exigences suivantes sont des exigences spécifiques supplémentaires qui s’appliquent au niveau de protection "da" qui modifient ou complètent les exigences du présent document:
a) le volume interne libre maximal ne doit pas dépasser 5 cm ; b) les conducteurs électriques dans le capteur doivent employer un joint scellé, conformément à l’Article 6, directement dans la paroi de l’enveloppe; c) le dispositif de respiration du capteur doit être conforme à l’Article 10, et doit être scellé à la paroi de l’enveloppe afin d’éliminer tout interstice (comme le scellement selon 6.1 ou un collage fritté) ou doit être monté en force dans la paroi de l’enveloppe avec des moyens mécaniques supplémentaires de fixation (comme l’emboutissage); d) l’alimentation doit se faire par un circuit de niveau de protection "ia", avec une puissance maximale dissipée limitée à 3,3 W pour le groupe I et à 1,3 W pour le groupe II; et NOTE 2 Les éléments catalytiques fonctionnent normalement à une température élevée. Si la dissipation de puissance est augmentée au-delà des niveaux de fonctionnement normaux, l’élément ne parvient pas à établir un circuit ouvert. Par conséquent, la limitation de la puissance exigée entraîne une limitation de la température de la surface externe.
e) les essais de non-transmission de 16.3 ou 16.4.4 (le cas échéant) sont modifiés pour augmenter le nombre d’essais de non-transmission indiqués dans le Tableau 1. Tableau 1 – Nombre d’essais de non-transmission pour le niveau de protection "da" Groupe d’appareils Nombre d’essais de non-transmission I 50 IIA 50 IIB 50 IIC 50 pour l’hydrogène et 50 pour l’acétylène
4.3 Exigences qui s’appliquent au niveau de protection "db"
Hormis les exigences spécifiques qui s’appliquent aux niveaux de protection "da" et "dc", toutes les autres exigences du présent document doivent s’appliquer au niveau de protection "db".
4.4 Exigences qui s’appliquent au niveau de protection "dc"
4.4.1 Généralités
Le niveau de protection "dc" s’applique uniquement aux appareils Ex et aux composants Ex équipés de contacts de coupure électrique. Les exigences qui s’appliquent au niveau de protection "dc" sont spécifiées de 4.4.2 à 4.4.3.
4.4.2 Composition
4.4.2.1 Généralités
Les exigences spécifiées de 4.4.2.2 à 4.4.2.5 remplacent celles de l’Article 5 à l’Article 13. Pour les appareils de niveau de protection "dc" destinés à être connectés au câblage in situ, l’Article 13 s’applique.
Au minimum, le constructeur et le numéro de modèle, ainsi que les caractéristiques électriques assignées et la température de fonctionnement continu (COT), pour les appareils du niveau de protection "dc", doivent figurer dans les dessins annexés.
4.4.2.2 Volume interne libre
Le volume interne libre ne doit pas dépasser 20 cm .
4.4.2.3 Exigences relatives à la COT
Les joints d’étanchéité et les produits d’enrobage doivent avoir une COT qui comprend une température minimale inférieure ou égale à la température minimale de service et une température maximale supérieure d’au moins 10 K à la température maximale de service.
4.4.2.4 Caractéristiques assignées
Les appareils doivent être limités à une caractéristique assignée maximale de 16 A sous 1 000 V en courant alternatif ou 1 500 V en courant continu.
4.4.2.5 Éléments de raccordement
L’équipement doit être équipé d’éléments de raccordement utilisant l’une des méthodes suivantes:
a) des éléments de raccordement de câblage in situ conformément à l’Article 13 destinés à être connectés en utilisant une méthode de connexion EPL Gc appropriée; b) des éléments de raccordement de câblage d’usine utilisant des conducteurs individuels (câbles volants) destinés à être connectés en utilisant des méthodes de connexion EPL Gc appropriées; ou c) des éléments de raccordement de câblage d’usine utilisant des terminaisons intégrées destinées à être connectées en utilisant une méthode appropriée de connexion EPL Gc (par exemple broches soudées à une carte de circuit imprimé).
NOTE L’élément de raccordement le plus couramment appliqué utilise le niveau de protection "ec".
4.4.3 Essais de type
Les appareils relevant du niveau de protection "dc" doivent être soumis à l’essai de type spécifié en 16.5. À l’issue de l’essai, l’appareil ne doit présenter aucun dommage visible, aucune inflammation externe ne doit se produire et aucune défaillance ne doit provoquer des arcs lorsque les contacts de coupure sont ouverts.
5 Joints antidéflagrants
5.1 Exigences générales
Tous les joints antidéflagrants, qu’ils soient fermés en permanence ou conçus pour être ouverts lors de l’installation ou de la maintenance, doivent satisfaire, en l’absence de pression, aux exigences appropriées de l’Article 5 et doivent être soumis aux essais spécifiés de l’Article 15 à l’Article 17, suivant le cas.
Un matériau qui durcit après assemblage du joint antidéflagrant (par exemple un frein de filet sur des joints filetés antidéflagrants) ne doit pas être utilisé sur un joint antidéflagrant conçu pour être ouvert pendant l’installation ou la maintenance. Voir l’Article 22. Lorsque du frein de filet pour fermetures est utilisé pour fixer les joints antidéflagrants, cela doit être de telle sorte que le composé ne migre pas sur les surfaces des passages de flamme.
La conception des joints antidéflagrants doit être appropriée aux contraintes mécaniques qui s’exercent sur eux.
Les dimensions données de 5.2 à 5.5 spécifient les paramètres essentiels des passages de flamme. Dans les cas où un des éléments suivants s’applique (par exemple pour être conforme aux essais de non-transmission d’une inflammation interne):
a) la longueur minimale du joint antidéflagrant spécifiée par la documentation est supérieure à la valeur minimale pertinente; b) l’interstice maximal du joint antidéflagrant spécifié par la documentation est inférieur à la valeur maximale pertinente; ou c) le nombre minimal de filets engagés pour le joint antidéflagrant spécifié par la documentation est supérieur à la valeur minimale pertinente.
NOTE L’IEC 60079-0 définit la documentation comme l’ensemble des documents qui fournissent une spécification complète et correcte des aspects de la sécurité de l’appareil Ex et des composants Ex vis-à-vis du risque d’explosion. Le numéro de certificat de l’appareil Ex doit comprendre le suffixe "X" conformément aux exigences de marquage de l’IEC 60079-0 et les conditions particulières d’utilisation figurant sur le certificat et dans les instructions doivent préciser l’un des éléments suivants:
- les dimensions des joints antidéflagrants doivent être précisées;
- un dessin spécifique référencé qui donne des précisions sur les dimensions des joints antidéflagrants;
- des recommandations spécifiques indiquant de contacter le constructeur d’origine afin d’obtenir des informations sur les dimensions des joints antidéflagrants et, le cas échéant, des recommandations spécifiques pour la réparation des joints filetés antidéflagrants qui comportent du frein de filet; ou
- une indication qui spécifie que les joints antidéflagrants ne sont pas destinés à être réparés. La surface d’un passage de flamme peut être protégée contre la corrosion:
- la peinture ou le revêtement de poudre ne doit pas être appliqué sur les surfaces des joints antidéflagrants;
- d’autres matériaux de revêtement peuvent être utilisés s’il a été démontré que ceux-ci et la méthode d’application n’affectent pas d’une manière défavorable les propriétés antidéflagrantes du joint antidéflagrant;
- une graisse qui empêche la corrosion, telle que des huiles minérales épaissies à la vaseline ou au savon, peut être appliquée sur les surfaces du joint antidéflagrant avant assemblage. La graisse, si elle est appliquée, doit être d’un type qui ne durcit pas en raison du vieillissement, qui ne contient pas de solvant s’évaporant et qui ne conduit pas à une corrosion des surfaces du joint antidéflagrant. La vérification de l’aptitude à l’emploi doit être conforme aux spécifications du constructeur de la graisse. Les surfaces du joint antidéflagrant peuvent être métallisées par galvanoplastie. Le placage de métal, lorsqu’il est appliqué, doit être conforme à ce qui suit:
- si l’épaisseur maximale est de 0,008 mm, aucune disposition supplémentaire n’est nécessaire; ou
- si l’épaisseur est supérieure à 0,008 mm, l’interstice maximal sans le placage doit toujours être conforme aux exigences qui s’appliquent au joint antidéflagrant. Il doit être soumis à l’essai de transmission de la flamme en fonction de la dimension de l’interstice qui existerait sans le placage.
Si l’appareil est assigné pour un gaz spécifique et un groupe d’appareils spécifique (par exemple IIB + H ), l’enveloppe doit satisfaire aux exigences relatives au gaz spécifique et aux
exigences relatives au groupe d’appareils inférieur.
...







