Abstract

IEC 61227:2008 identifies the Human-Machine Interface (HMI) requirements for discrete controls, multiplexed conventional systems, and soft control systems. To be used with IEC 60964 and IEC 61772. Is intended for application to the design of new main control rooms in nuclear power plants designed to IEC 60964. This new edition takes into account the fact that computer design engineering techniques have advanced significantly during recent years.

Status
Published
Publication Date
28-Apr-2008
Current Stage
PPUB - Publication issued - 60 Publication
Start Date
29-Apr-2008
Due Date
31-May-2008
Completion Date
31-May-2008

Buy Documents

Standard

IEC 61227:2008 - Nuclear power plants - Control rooms - Operator controls Released:4/29/2008

ISBN:2-8318-9732-7
English and French language (42 pages)
sale 15% off
Preview
sale 15% off
Preview

Overview

IEC 61227:2008 is an essential international standard developed by the International Electrotechnical Commission (IEC) that addresses the Human-Machine Interface (HMI) requirements specific to operator controls within nuclear power plant (NPP) control rooms. This standard works in conjunction with IEC 60964 and IEC 61772 to guide the design of new nuclear power plant main control rooms, emphasizing modern computer design engineering techniques. Its primary focus lies on discrete controls, multiplexed conventional systems, and soft control systems to ensure optimal and safe human interaction with nuclear plant control systems.

Key Topics

The standard covers a comprehensive range of critical design and operational considerations for operator controls in nuclear power plants, emphasizing safety, usability, and ergonomics:

  • Human-Machine Interface (HMI) Requirements
    IEC 61227 details explicit HMI requirements for various control modalities including discrete controls, soft controls, and multiplexed systems, ensuring effective and clear communication between operators and system functions.

  • Control Room Design Principles
    The standard supplements IEC 60964 by focusing narrowly on operator controls while expecting the broader control room design requirements to be met as per IEC 60964. This includes layout, user needs, and verification and validation methods.

  • Individual Controls and Indicators

    • Layout and positioning of control devices
    • Orientation and grouping for ease of use
    • Use of mimic diagrams and appropriate coding for clarity
    • Protection measures against mal-operation of controls
    • Compatibility with Visual Display Unit (VDU) formats as guided in IEC 61772
  • Soft Controls and Touch Panels
    Specifies requirements for display devices, selection displays, input fields, input formats, and user-system interactions to support advanced computer-based control systems.

  • Alignment with International Standards and Safety Guides
    The standard has been updated to align with International Atomic Energy Agency (IAEA) requirements such as NS-R-1 and NS-G-1.3, and incorporates advancements in computer engineering and nuclear safety practices.

Applications

IEC 61227:2008 is primarily tailored for the design and implementation of operator controls in new nuclear power plant main control rooms. The practical applications include:

  • Nuclear Utility Operations:
    Ensures that operator controls are designed for optimal interaction, reducing human error and enhancing safety during normal and emergency plant operations.

  • Control Room Engineering and Design:
    Control room architects and engineers apply IEC 61227 requirements to develop effective HMI control panels that meet international safety and usability standards.

  • Licensing and Regulatory Compliance:
    The standard is referenced by regulators and licensing bodies when evaluating the adequacy of control room operator controls in nuclear facilities, supporting consistent regulatory frameworks.

  • System Evaluation and Validation:
    Systems evaluators and safety assessors use this standard in verification and validation processes to confirm that operator controls meet required ergonomic and interface criteria.

  • Integration with Computerized Control Systems:
    Incorporates modern computerized soft control systems, enabling the use of touch panels and visual display units compatible with complex control room interfaces.

Related Standards

IEC 61227 is part of the IEC SC 45A standard series related to instrumentation and control systems for nuclear facilities and should be considered in the context of the following key standards:

  • IEC 60964 – Nuclear power plants - Control rooms - Design of main control room:
    Provides general design principles for control rooms, setting the foundation on which IEC 61227 builds specific operator control requirements.

  • IEC 61772 – Nuclear power plants - Control rooms - Application of visual display units (VDU):
    Details requirements for display systems incorporated within operator controls, complementing IEC 61227 guidance on soft controls.

  • IEC 61513 – Nuclear power plants - Instrumentation and control for systems important to safety:
    Acts as the top-level document in the IEC SC 45A series, establishing general requirements for safety-related I&C systems.

  • IEC 60073 – Basic and safety principles for man-machine interface, marking and identification:
    Provides coding principles for indicators and actuators, an essential normative reference for operator control design.

  • IAEA Safety Guides (NS-R-1, NS-G-1.3):
    Established nuclear safety requirements and guidance for instrumentation and control systems important to nuclear power plant safety.

Conclusion

IEC 61227:2008 is a critical standard for ensuring the safety, effectiveness, and ergonomic quality of operator controls in nuclear power plant control rooms. By specifying HMI requirements for various control systems and aligning with international safety and design standards, it plays a key role in advancing nuclear plant control room safety and operator performance. For organizations involved in nuclear plant design, operation, or regulation, adherence to IEC 61227 supports compliance with best practices and fosters enhanced safety culture in nuclear power operations.

Keywords: IEC 61227, nuclear power plants, control rooms, operator controls, human-machine interface, HMI, discrete controls, soft control systems, nuclear safety standards, IEC 60964, IEC 61772, nuclear control room design, nuclear instrumentation and control

Buy Documents

Standard

IEC 61227:2008 - Nuclear power plants - Control rooms - Operator controls Released:4/29/2008

ISBN:2-8318-9732-7
English and French language (42 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

DNV

DNV is an independent assurance and risk management provider.

NA Norway Verified

Lloyd's Register

Lloyd's Register is a global professional services organisation specialising in engineering and technology.

UKAS United Kingdom Verified

DNV Energy Systems

Energy and renewable energy certification.

NA Norway Verified

Sponsored listings

Frequently Asked Questions

IEC 61227:2008 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Nuclear power plants - Control rooms - Operator controls". This standard covers: IEC 61227:2008 identifies the Human-Machine Interface (HMI) requirements for discrete controls, multiplexed conventional systems, and soft control systems. To be used with IEC 60964 and IEC 61772. Is intended for application to the design of new main control rooms in nuclear power plants designed to IEC 60964. This new edition takes into account the fact that computer design engineering techniques have advanced significantly during recent years.

IEC 61227:2008 identifies the Human-Machine Interface (HMI) requirements for discrete controls, multiplexed conventional systems, and soft control systems. To be used with IEC 60964 and IEC 61772. Is intended for application to the design of new main control rooms in nuclear power plants designed to IEC 60964. This new edition takes into account the fact that computer design engineering techniques have advanced significantly during recent years.

IEC 61227:2008 is classified under the following ICS (International Classification for Standards) categories: 27.120.20 - Nuclear power plants. Safety. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61227:2008 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


IEC 61227
Edition 2.0 2008-04
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Nuclear power plants – Control rooms – Operator controls

Centrales nucléaires de puissance – Salles de commande – Commandes
opérateurs
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: 0Hinmail@iec.ch
Web: 1Hwww.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
ƒ Catalogue of IEC publications: 2Hwww.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
ƒ IEC Just Published: 3Hwww.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
ƒ Electropedia: 4Hwww.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
ƒ Customer Service Centre: 5Hwww.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: 6Hcsc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
ƒ Catalogue des publications de la CEI: 7Hwww.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
ƒ Just Published CEI: 8Hwww.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
ƒ Electropedia: 9Hwww.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
ƒ Service Clients: 10Hwww.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: 11Hcsc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 61227
Edition 2.0 2008-04
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Nuclear power plants – Control rooms – Operator controls

Centrales nucléaires de puissance – Salles de commande – Commandes
opérateurs
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
S
CODE PRIX
ICS 27.120.20 ISBN 2-8318-9732-7

– 2 – 61227 © IEC:2008
CONTENTS
FOREWORD.0H3
INTRODUCTION.1H5

1 Scope.2H7
2 Normative references .3H7
3 Terms and definitions .4H7
4 Design principles.5H8
4.1 Basic concepts .6H8
4.2 Types of HMI.7H9
4.2.1 Discrete controls .8H9
4.2.2 Soft controls .9H9
4.3 Selection of control system.10H10
5 Design requirements .11H11
5.1 Individual controls and indicators .12H11
5.1.1 Control board layout .13H11
5.1.2 Positioning of groups .14H12
5.1.3 Device layout.15H12
5.1.4 Uniformity of orientation .16H13
5.1.5 Mimic diagrams .17H13
5.1.6 Coding.18H14
5.1.7 Protection against mal-operation of control devices .19H15
5.1.8 Compatibility with VDU formats.20H15
5.2 Soft controls.21H16
5.2.1 Display devices .22H16
5.2.2 Selection displays.23H17
5.2.3 Input Fields .24H17
5.2.4 Input formats .25H17
5.2.5 User-System Interaction .26H17
5.3 Special requirements for touch panels.27H18

28H20
Annex A (informative) Examples for the arrangement of discrete controls .

61227 © IEC:2008 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
NUCLEAR POWER PLANTS –
CONTROL ROOMS –
OPERATOR CONTROLS
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61227 has been prepared by subcommittee 45A: Instrumentation
and control of nuclear facilities, of IEC technical committee 45: Nuclear instrumentation.
This second edition cancels and replaces the first edition published in 1993 and constitutes a
technical revision. This edition includes the following significant technical changes with
respect to the previous edition:
a) account has been taken of the fact that computer design engineering techniques have
advanced significantly in the intervening years;
b) alignment of the standard with the new revisions of IAEA documents NS-R-1 and NS-G-
1.3, which includes as far as possible an adaptation of the definitions;
c) replacement, as far as possible, of the requirements associated with standards published
since the first edition, especially, IEC 60964 (edition 2) and IEC 61772 (edition 2);
d) review of the existing requirements and updating of the terminology and definitions.

– 4 – 61227 © IEC:2008
The text of this standard is based on the following documents:
FDIS Report on voting
45A/694/FDIS 45A/702/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
61227 © IEC:2008 – 5 –
INTRODUCTION
a) Technical background, main issues and organisation of this standard
This IEC standard specifically focuses on operator controls.
It is intended that this standard be used by operators of NPPs (utilities), systems evaluators
and by licensors.
b) Situation of the current standard in the structure of IEC SC 45A standard series
IEC 61227 is the third level IEC SC 45A document tackling the generic issue of operator
controls.
IEC 61227 is to be read in association with IEC 60964 and IEC 61772. IEC 60964 is the
appropriate IEC SC 45A chapeau document for control rooms which provides guidance on
control room design and which references IEC 61227. IEC 61772 establishes requirements for
the application of VDU (Visual Display Units).
For more details on the structure of IEC SC 45A standard series, see item d) of this
introduction.
c) Recommendations and limitations regarding the application of this standard
It is important to note that this standard establishes no additional functional requirements for
safety systems.
To ensure that this standard will continue to be relevant in future years, the emphasis has
been placed on issues of principle, rather than specific technologies.
d) Description of the structure of the IEC SC 45A standard series and relationships
with other IEC documents and other bodies documents (IAEA, ISO)
The top-level document of the IEC SC 45A standard series is IEC 61513. It provides general
requirements for I&C systems and equipment that are used to perform functions important to
safety in NPPs. IEC 61513 structures the IEC SC 45A standard series.
IEC 61513 refers directly to other IEC SC 45A standards for general topics related to
categorization of functions and classification of systems, qualification, separation of systems,
defence against common cause failure, software aspects of computer-based systems,
hardware aspects of computer-based systems, and control room design. The standards
referenced directly at this second level should be considered together with IEC 61513 as a
consistent document set.
At a third level, IEC SC 45A standards not directly referenced by IEC 61513 are standards
related to specific equipment, technical methods, or specific activities. Usually these
documents, which make reference to second-level documents for general topics, can be used
on their own.
A fourth level extending the IEC SC 45A standard series, corresponds to the Technical
Reports which are not normative.
IEC 61513 has adopted a presentation format similar to the basic safety publication
IEC 61508 with an overall safety life-cycle framework and a system life-cycle framework and
provides an interpretation of the general requirements of IEC 61508-1, IEC 61508-2 and
IEC 61508-4, for the nuclear application sector. Compliance with IEC 61513 will facilitate
consistency with the requirements of IEC 61508 as they have been interpreted for the nuclear

– 6 – 61227 © IEC:2008
industry. In this framework IEC 60880 and IEC 62138 correspond to IEC 61508-3 for the
nuclear application sector.
IEC 61513 refers to ISO as well as to IAEA 50-C-QA (now replaced by IAEA 50-C/SG-Q) for
topics related to quality assurance (QA).
The IEC SC 45A standards series consistently implements and details the principles and
basic safety aspects provided in the IAEA code on the safety of NPPs and in the IAEA safety
series, in particular the Requirements NS-R-1, establishing safety requirements related to the
design of Nuclear Power Plants, and the Safety Guide NS-G-1.3 dealing with instrumentation
and control systems important to safety in Nuclear Power Plants. The terminology and
definitions used by SC 45A standards are consistent with those used by the IAEA.

61227 © IEC:2008 – 7 –
NUCLEAR POWER PLANTS –
CONTROL ROOMS –
OPERATOR CONTROLS
1 Scope
This International Standard supplements IEC 60964 which applies to the design for control
rooms of nuclear power plants. It identifies the Human-Machine Interface (HMI) requirements
for discrete controls, multiplexed conventional systems, and soft control systems. For the
main control room of a nuclear power plant, IEC 60964 includes general requirements for
layout, user needs and verification and validation methods, and these aspects are not
repeated in this standard. However, IEC 61772 on Visual Displays Unit (VDU) also provides
some guidance on displays and indications where necessary for the correct application of the
control requirements.
This standard is intended for application to the design of new main control rooms in nuclear
power plants designed to IEC 60964 where this is initiated after the publication of this
standard. If it is desired to apply it to supplementary control points or local control positions,
or to existing control rooms or designs, special caution shall be exercised as it makes
assumptions such as the automation level that may not apply.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60073, Basic and safety principles for man-machine interface, marking and identification
– Coding principles for indicators and actuators
IEC 60964, Nuclear power plants – Control rooms – Design of main control room
IEC 61771, Nuclear power plants – Control rooms – Verification and validation of design
IEC 61772, Nuclear power plants – Control rooms – Application of visual display units (VDU)
IAEA Safety guide NS-G-1.3:2002, Instrumentation and Control Systems Important to Safety
in Nuclear Power Plants
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60964 and the
following definitions apply:
3.1
discrepancy control and indication
binary control with state and discrepancy indication using a single control switch
3.2
discrete (individual) controls
devices to support operator control of plant components, such as pumps, valves, controllers,
with one control being assigned to a single plant component or function

– 8 – 61227 © IEC:2008
3.3
multiplexed
used for several purposes at different times. For example, a start-stop switch may be selected
by another device associated to a number of plant items and used to start or stop the item to
which it is connected at the time
3.4
operator controls
devices which the operator uses to send demand signals to control systems and plant items
3.5
semaphore
electrically driven mechanical device which displays the plant condition (e.g. open or closed
switch position) by the angular position of the visible surface
3.6
soft control
control device for input of operator commands, that has connections with the control system
that are mediated by software rather then direct physical connections. As a result, the
functions of a soft control may be variable and context dependent rather than statically
defined.
NOTE Typically, soft control devices use VDUs for displaying the input options, and pointing devices such as
track ball, mouse, touch capability, or light pen for the selection of the choice.
3.7
touch panel
soft control which uses a position detector to detect the operator's finger pointing at the label
on the VDU (Visual Display Unit). Alternatively, a light pen may be used or a cursor may be
moved over the VDU format to identify a label. The label may describe an item of plant or a
control action.
4 Design principles
4.1 Basic concepts
An overall systems design approach is required for the design of the HMI. IEC 60964 states
the requirements for overall design of the control room system and the establishment of the
principles required for safety, availability and user considerations, and the functional design of
the system as a whole. The designer shall consider his goals, and the relative importance of
the various design factors for his particular application.
Operator controls shall be designed so that operators can perform their tasks easily and
correctly. Consideration shall be given to control-display integration and the type of operating
procedure and its presentation shall be taken into account in the choice of controls to be
used. Particular attention shall be given to the needs of the operator for simple error-proof
systems that will optimize the operator's performance under all conditions. Their design shall
be based on ergonomic principles to ensure ease of operation and to minimize operators'
errors, both of omission and execution. Where conventional systems are used, mechanical
characteristics of control elements, such as size, operating pressure or force, tactile
feedback, etc., shall meet human capabilities and characteristics specified in the
anthropometric data base.
The design of the control panels and controls shall be consistent with the overall system
design and shall comply with the requirements specified in IEC 60964 and, in particular, with
the following subclauses of that standard:
a) Panel layout
b) Location aids
61227 © IEC:2008 – 9 –
c) Information and control systems
d) Control-display integration
e) Communication system
f) Other requirements
Any system shall give immediate feedback to the operator that it has received a control
command, for example, by lighting a device or a mark on a VDU. Appropriate plant feedback
shall indicate when the command has been implemented, for example the valve has closed.
4.2 Types of HMI
The types of operator interface available for control may be classified into two groups,
a) discrete controls comprising dedicated systems / multiplexed conventional systems;
b) soft controls.
The groups have the following characteristics, and the task analysis described in 4.3 is used
to determine the most appropriate type to use.
4.2.1 Discrete controls
Dedicated controls have the disadvantage of being present even when not wanted, thus
increasing the size of the whole control desk and providing "clutter" when other controls are in
use.
Dedicated controls are particularly suitable for controls in constant use, for example electrical
output, or those whose immediate accessibility and reliability are of prime importance, for
example an emergency trip button. Requirements for their layout are described in 5.1.1.
Multiplexed controls, a sub-set of discrete controls, use a single control for the same function
on several equipments, thus reducing the number of controls on the desk or panel so that
they can be made smaller and the controls can be brought closer to the operator. However,
the operator has to make a selection, so the number of operations is increased and the
chances of error and the operator response time may be increased.
Multiplexed controls shall be designed with good feedback to the operator for the function
selected, to permit error recovery. They are particularly suitable for the control of seldom-
used systems that are not required in a hurry, for example, tank filling, and for systems where
the consequences of error are not serious and where time is available for correction in the
event of error.
4.2.2 Soft controls
These controls are a type of multiplexed system where they can have different functions at
different times. Typically, soft controls are implemented using one (or two) VDUs together
with a pointing device (such as mouse, track ball light pen or touch capability), or a
combination of a VDU with a set of dedicated controls. Control actions are performed in the
following way:
– selection of the object to be controlled using the pointing device;
– presentation of the command options on the VDU as menu items or icons, e.g. in a pop-
up-window or on a separate VDU;
– selection and activation of the command option to be executed, again using the pointing
device.
These systems have many of the characteristics of conventional multiplexed systems, but
make it possible to assemble controls related to specific tasks and not offer the operator
controls that are invalid or inappropriate to that task, so guiding the operator to correct

– 10 – 61227 © IEC:2008
actions. All information required by the operator to perform the correct control action shall be
presented to him when required, either on the touch screen or on a related adjacent format.
Selection error rates could be high if the system is not well-designed and, as a hierarchical
selection of several formats may be required to recall the control set required, the process of
selection of a control not already on display may be relatively lengthy. However, it may be
possible to use a single format with changed windows for several control actions.
It is often difficult to optimise the position of the VDU for both monitoring and touching and
two screens may be required. Off-screen pointing devices (e.g. track ball and light pen) are an
alternative solution.
Soft controls can be particularly useful where the task is under the control of the operator.
For using soft controls, suitable consideration shall be needed to satisfy HMI requirements.
For example: software switch selection time, human error rate in selecting the switches, or
system response time. The VDU can display the mimic diagram of the system with the
information required by the operator, who will identify the concerned item in the computer,
and use a touch panel, soft control switch, or pointing device to achieve the desired effect.
For more information on the requirements for soft controls interfaces, see 5.2.
4.3 Selection of control system
The process to select and specify a control system should start from the consideration of the
available technologies on the market and of the available feed-back from the plants.
This process shall clearly distinguish between the selection of the “main control system” and
the selection of the proper control type for every plant component / plant function.
It is also to be considered that, for common cause failure reasons, two different control
systems could be selected to perform the same function.
A task analysis is required as a fundamental part of the control room design and this shall be
documented in a manner that indicates the requirements for the controls in terms of:
a) frequency of use;
b) grouping, and relationship with other controls;
c) speed of access required (when not already in use);
d) reliability;
e) acceptability of common cause faults;
f) importance of consequences of erroneous selection;
g) complexity of system controlled;
h) type of information display proposed (VDU or dedicated instruments);
i) type of control equipment proposed;
j) categorization of control functions by their importance to safety;
k) operating procedures (e.g., normal, testing, emergency).
Bearing in mind the characteristics of the types of control system identified in 4.2, the
designer shall select the most appropriate interface for each control and develop the design
following the requirements of 5.1. The proposed design shall then be validated in accordance
with the method given in IEC 60964 and detailed in IEC 61771. In the design and validation, it
is important that all relevant inputs to the HMI design are taken into account. These will
include contributions from the:

61227 © IEC:2008 – 11 –
a) plant designer;
b) control system equipment designer;
c) information system designer;
d) safety and reliability specialist;
e) topic specialist (e.g. radiation protection specialist, chemist, etc.);
f) operations staff; maintenance staff;
g) existing design criteria (in the case of refits or extension);
h) human factors specialist.
In practice, detailed interface design depends upon thorough task analysis.
Representative operators should be consulted in the selection and development of formats
and control actions. It is highly recommended that live tests are conducted using a simulator.
Post-commissioning operations will also provide much valuable information on design
adequacy. However, the adaptability of the user population and the constraints generated by
operating factors will restrict such feedback to those items which create significant operating
or maintenance problems rather than subjective detail.
5 Design requirements
5.1 Individual controls and indicators
There are three main types of displays and control element combinations to be considered:
a) individual indicators and controls;
b) VDU and individual controls, and
c) VDU only.
Individual indicators and controls shall be laid out as described below, and they shall be
positioned close to VDU giving related information. VDU layout is covered in IEC 61772 (see
also 5.1.8).
5.1.1 Control board layout
Formal rules for the layout of control and indication devices on desk and panel surfaces are
described in IEC 60964 as a distributed set of requirements associated with components.
Layout of control panels and desks with individual controls and individual indicators shall
follow a consistent design concept.
It is not possible to postulate unique design rules which will meet every possible design and
operational circumstance. Certain rules will require conditional application depending on the
exact balance of objectives for any given part of the operator interface. The priority given to
the various principles will be situation dependent. The order given below has been found to
cope with the majority of applications.
The primary classification of control and indication devices on a desk or panel is based on
who has responsibility for use of the device. (Where more than one user requires a piece of
information, consideration shall be given to duplication of displays.) Considered in conjunction
with function and frequency of use, this will determine the general location for a device.
Control room layout will determine the controls and indication functions allocated to the desk
or panel. The layout of devices shall follow a logical sequence. The most general sequence is
that of the plant, i.e. mimic diagram of the plant, but other sequences such as sequence of
use should be considered.
– 12 – 61227 © IEC:2008
Within a given structure (either desk or panel), control devices shall be arranged to form
functional groups irrespective of the nature of the information presented. A functional group
should be specified in terms of the achievement of a given function or process operation. For
certain plant items, for example pumps, the "functional" grouping may equate to a group of
mechanical plant components. The groupings shall take account of "systems" as a series of
plant components which are linked in some functional way e.g. a piped or ducted fluid system,
electrically connected system, or a set of components which are installed to achieve or
maintain a defined plant function, for example, primary and secondary shut-down devices.
(These two sets of plant devices may be functionally independent but are provided to achieve
the same end result, i.e. subcritically.)
Panel layout of one group shall be done consistent with the layout of adjacent functional
groups.
The groups of controls and indications so formed shall normally be laid out logically in the
sequence of use, but if superimposed on a mimic, should be placed in appropriate positions in
relation to the mimic.
5.1.2 Positioning of groups
The position of a group within a desk or panel shall be optimized taking into account the
following factors:
a) the order of use should follow some simple principle, such as left to right in start-up or
power raise, or following the order of energy flow from source on the left to sink on the
right. It should accord with accepted population stereotypes;
b) the order should not be biased in favour of infrequent operating conditions;
c) the devices required for safety and normal minute-to-minute operation should be close to
the operator's monitoring position, and this factor may be an exception to the overall
pattern derived from a);
d) there may be displays which shall be visible from a number of operating positions, such as
an overview, or which require to be easily and reliably located in a fault situation. If desk
mounted they should be located in the near-vertical surface in preference to the near-
horizontal;
e) where more than one functional group contains similar plant items, for example the main
boilers, the groups should be identically laid out and follow in an apha-numeric order.
5.1.3 Device layout
Within a group there shall be a detailed analysis of the relationships between devices and the
sequences of use, and the layout shall be optimized for the following factors:
a) for those groups where there is a unique sequence of use the devices should be arranged
left to right in sequence of use, taking into account the general requirements for safety
and visibility referred to in 5.1.2;
b) controls should be placed below indications, or where not practicable, on the right of the
indication. This does not apply to a control common to many devices, such as "lamp test";
c) where there is no unique sequence of use, devices should be arranged left to right in
order of plant identification or energy flow.
Component layouts shall not be "mirror-imaged" ('handed') unless this is justified by HFE
(Human Factors Engineering) specialist. Also the layout should not be compromised simply to
save space.
A mimic layout may not permit the application of all these requirements.

61227 © IEC:2008 – 13 –
5.1.4 Uniformity of orientation
Similar looking control elements or arrangements shall be operated in a similar manner and
provide similar choice selection. Control movements shall conform with population
stereotypes, but typical examples are given in Annex A.
5.1.5 Mimic diagrams
In cases where indication and control devices are arranged in a diagrammatic or schematic
display (commonly referred to as a mimic diagram), the above layout principles apply to the
functional clusters of controls and displays, but there are a number of additional
considerations.
The schematic should conform to a representational model of the plant that can be used by an
operator. This will have been conditioned by the physical appearance and layout of the plant,
by the layout of controls and indications in the control room and local panels, and by the
drawings most frequently used. All three factors shall be considered. As an example, if only
the physical layout of quadrantized plant around a reactor were taken into account, it would
result in a diagram of these quadrants containing mirror-imaged elements. As a general rule,
mirror imaging is undesirable and should be avoided. Controls and indications should be
positioned to relate to the physical position of the related plant item.
Corresponding information should be placed in the same relative position in all similar
instances. This is the approach taken on control desks, and so the elements showing the
quadrants would be designed identically, being differentiated by titles and labelling or colour.
This standardized layout, for example for a pump set, facilitates recognition by the operator.
Flow paths should be arranged to be as simple as possible and generally should be left-to-
right, and top-to-bottom. In the case of a closed system, the designer shall judge whether a
clockwise or anti- clockwise flow is appropriate, although the former is recommended.
Direction of flow shall be consistent between diagrams. Usually, the most involved part or the
most significant part of the flow path should be arranged to be left-to-right. Flow direction
should be maintained within functional plant areas.
Certain physical aspects of a system shall be taken into account. For instance, in a system
where gravity plays a significant part, for example a low-pressure water system, the diagram
should reflect this in the position of vessels and pumps, etc. Similarly, large physical objects
such as boilers and turbo-generators should be represented in a way which is consistent with
their physical appearance.
The normal rules of graphic design apply, in that the display should lead the user's eye
around the mimic in a continuous manner. Angled lines can lead the user's eye to a particular
point on the display, but in general mimics should be based on a rectilinear framework as
used for single-line flow diagrams. Junctions should be reduced to show flow direction and
cross-overs should be minimized. If flow lines do not join, they shall not touch; the minor flow
line should be broken to give a small separation from the major line. If both are of equal
significance, the vertical line should be broken to give the separation.
The organization of the diagram as a whole should enable the user to identify with the plant
and quickly relate the data on the diagram to give him a clear understanding of what is
happening on the plant and the location of touch panels and controlled items. Where several
plant items operate in parallel, for example a set of boilers or pumps, comparison of their
performance is facilitated if key variables from each are displayed in adjacent positions in
lines or columns.
5.1.5.1 Mimic panels for electrical systems
All circuit-breaker representations should be placed in vertical representations of circuits and
the control or indication device should be placed close to the relevant switchboard symbol.

– 14 – 61227 © IEC:2008
Feeders into switchboards should enter into the top of the switchboard representation.
Circuits fed from a switchboard should descend from the switchboard symbol.
Switchboard inter-connectors should form horizontal lines, broken as necessary to give
precedence to vertical representations. Inter-connector circuit breakers should obey the
general rule for breakers. The order of breakers on a mimic panel need not follow the physical
arrangements in the electrical rooms. Precedence should be given to considerations of
diagram clarity. However, it should be noted that this rule cannot be applied for
representations within the same room as the actual switchboard. Adequate inter-circuit
spacing is required and this will depend upon the physical size of the largest component used.
This could be a control switch or an in-line current display for example. Adequate space is
required between adjacent switchboards to provide the necessary degree of visual
discrimination between non-related circuits.
5.1.6 Coding
Coding techniques shall be applied to the design of controls and shall be consistent for all
related systems and equipment.
The forms of visual coding used in the control room interface include (in order of significance
to the designer):
a) Text
Device functions are marked either on the device or adjacent to it (the relative position of
the text being standardized) using coded forms of text. The formation and application of
nomenclature and abbreviations lies outside the scope of this standard but the consequent
positioning rules are discussed below.
b) Position
Control desk and panel designs may be based on the "dark-board" philosophy, where
normal running conditions produce a completely dark panel. Plant states are indicated by
the position of devices such as the discrepancy indicator and semaphore indicator.
c) Illumination
The need to achieve greater throughput of information across the interface and the need
to enhance the operator's monitoring capacity have led to the use of lit-board systems.
Generally lit-board and dark-board techniques shall not be mixed on the same panel or
desk. Lit-board systems and the use of increased automation have led to increased use of
illuminated push-button systems rather than rotary switch devices.
Abnormal conditions may be indicated by steady lights, for example a change to manual
by illuminating the manual push-button, and flashing lights may be used to denote the
need for operator attention to an alarm or change of plant state.
d) Shape coding
For dedicated rotary controls, shape coding should be specified to take advantage of
feedback to the operator that he has identified the correct control. Selectors could have an
arrow-shaped handle clearly pointing to the item selected, whereas raise-lower controls
could use a T-shaped handle and circuit breakers a "pistol grip".
e) Colour coding
This is a useful technique, but the use of colour as a sole coding medium is fraught with
problems due to colour modified vision, subjective interpretation and the plethora of
"standards" relating to colour. Colour coding should be used only in a redundant mode.
This is almost always achieved by the additional use of such coding techniques as shape,
pattern, or size or the addition of text. Code shall be applied consistently to all controls
throughout a particular NPP.
For current practice on VDU, see IEC 61772 and, for hand controls, IEC 60073 may be
consulted.
61227 © IEC:2008 – 15 –
Special attention shall be paid to the use of red and green colour for coding purposes,
especially when red/green is used for coding switch-gear status, it shall not be used for
coding other information such as equipment availability/failure.
f) Size coding
Size may be used to draw attention to frequently required items or safety items needed
quickly. However, for general use, size coding is not as effective as other methods.
5.1.7 Protection against mal-operation of control devices
To prevent a human-induced event, erroneous activation of controls shall be minimized.
Techniques used to guard against accidental selection or mal-operation of control devices
include device positioning, device protection and inherent device features, and shall be
achieved using the following methods.
a) Proper location: controls shall be located so that the operator is not likely to strike them or
move them accidentally in any sequence of control movements. Devices such as reactor
trip, turbine trip, or protection vetoes which have an immediate and significant effect on
plant state should be placed at the upper part of a control desk to reduce the risk of
inadvertent operation.
Control devices which can have a major effect on
...