IEC 60669-2-2:2006
(Main)Switches for household and similar fixed electrical installations - Part 2-2: Particular requirements - Electromagnetic remote-control switches (RCS)
Switches for household and similar fixed electrical installations - Part 2-2: Particular requirements - Electromagnetic remote-control switches (RCS)
This part of IEC 60669 applies to electromagnetic remote-control switches (hereinafter referred to as RCS) with a rated voltage not exceeding 440 V and a rated current not exceeding 63 A, intended for household and similar fixed electrical installations, either indoors or outdoors.
Interrupteurs pour installations électriques fixes domestiques et analogues - Partie 2-2: Exigences particulières - Interrupteurs à commande à distance (télérupteurs)
La présente partie de la CEI 60669 s'applique aux interrupteurs à commande à distance (désignés ci-après télérupteurs) de tension assignée ne dépassant pas 440 V et de courant assigné ne dépassant pas 63 A, prévus
General Information
- Status
- Published
- Publication Date
- 28-Aug-2006
- Technical Committee
- SC 23B - Plugs, socket-outlets and switches
- Drafting Committee
- MT 8 - TC 23/SC 23B/MT 8
- Current Stage
- DELPUB - Deleted Publication
- Start Date
- 12-Mar-2024
- Completion Date
- 18-Feb-2022
Relations
- Effective Date
- 05-Sep-2023
- Effective Date
- 05-Sep-2023
- Effective Date
- 05-Sep-2023
Overview
IEC 60669-2-2:2006 is an international standard that specifies the particular requirements for electromagnetic remote-control switches (RCS) used in household and similar fixed electrical installations. The standard covers RCS devices with a rated voltage up to 440 V and a rated current not exceeding 63 A, intended for both indoor and outdoor fixed electrical installations. Developed by the International Electrotechnical Commission (IEC), this third edition revises and consolidates previous editions to ensure up-to-date technical requirements and compliance guidance.
This standard is essential for manufacturers, designers, and installers of electromagnetic remote-control switches to ensure safety, reliability, and interoperability in residential and similar electrical systems.
Key Topics
Scope and Application
Defines the usage limits of RCS devices including voltage and current ratings and distinguishes electromagnetic remote-control switches from electronic variants covered under IEC 60669-2-1.General and Constructional Requirements
Specifies design parameters, construction features, and mechanical mechanisms that these switches must meet to ensure proper function and durability.Safety Measures
Includes protection against electric shock, earthing provisions, insulation resistance, dielectric strength, and resistance to aging, humidity, and heat.Performance Testing
Details tests for temperature rise, mechanical strength, making and breaking capacities, and resistance to abnormal operating conditions.Marking and Classification
Stipulates required markings for correct identification and classification of switches, including new symbols introduced in this edition to aid standardization and user understanding.Electromagnetic Compatibility (EMC)
Addresses EMC requirements ensuring that RCS devices operate without causing or suffering from electromagnetic interference.Additional Requirements
Covers resistance to rust, fire safety of insulating materials, screw and connection quality, and other parameters essential for long-term reliability.
Applications
IEC 60669-2-2:2006 applies primarily to electromagnetic remote-control switches used in:
Residential Fixed Electrical Installations
Remote control of lighting circuits, household appliances, and other fixed electrical equipment that require safe and reliable switching.Outdoor and Indoor Installations
Suitable for a range of environments where electromagnetic switches must function regardless of exposure to moisture or temperature variations.Building Automation and Smart Homes
Provides baseline requirements for integrating RCS in remote control systems, facilitating automation, energy management, and convenience in household settings.Manufacturing and Product Development
Enables manufacturers to design compliant switches meeting international safety and performance criteria, aiding market access and consumer trust.
By adhering to IEC 60669-2-2, professionals ensure the deployment of switches that enhance safety, minimize fire risk, and deliver reliable long-term performance.
Related Standards
- IEC 60669-1 – General requirements for switches intended for household and similar fixed electrical installations.
- IEC 60669-2-1 – Particular requirements for electronic remote-control switches, distinct from electromagnetic types covered in IEC 60669-2-2.
- IEC 61000 Series – Standards addressing electromagnetic compatibility relevant to switch operation and interference mitigation.
- IEC 60364 Series – Electrical installations for buildings, providing overarching guidelines for safe electrical system design and installation.
- ISO/IEC 17025 – Related standard for testing laboratories performing compliance testing as per IEC 60669-2-2 requirements.
Keywords: IEC 60669-2-2, electromagnetic remote-control switches, RCS, household electrical installations, fixed electrical installations, switch standards, electrical safety, electrical switch testing, electromagnetic compatibility, remote-control switch requirements.
Frequently Asked Questions
IEC 60669-2-2:2006 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Switches for household and similar fixed electrical installations - Part 2-2: Particular requirements - Electromagnetic remote-control switches (RCS)". This standard covers: This part of IEC 60669 applies to electromagnetic remote-control switches (hereinafter referred to as RCS) with a rated voltage not exceeding 440 V and a rated current not exceeding 63 A, intended for household and similar fixed electrical installations, either indoors or outdoors.
This part of IEC 60669 applies to electromagnetic remote-control switches (hereinafter referred to as RCS) with a rated voltage not exceeding 440 V and a rated current not exceeding 63 A, intended for household and similar fixed electrical installations, either indoors or outdoors.
IEC 60669-2-2:2006 is classified under the following ICS (International Classification for Standards) categories: 29.120.40 - Switches. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 60669-2-2:2006 has the following relationships with other standards: It is inter standard links to IEC 60669-2-2:1996/AMD1:1997, IEC 60669-2-2:2024, IEC 60669-2-2:1996. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase IEC 60669-2-2:2006 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of IEC standards.
Standards Content (Sample)
NORME CEI
INTERNATIONALE
IEC
60669-2-2
INTERNATIONAL
Troisième édition
STANDARD
Third edition
2006-08
Interrupteurs pour installations électriques
fixes domestiques et analogues –
Partie 2-2:
Exigences particulières –
Interrupteurs à commande à distance
(télérupteurs)
Switches for household and similar
fixed electrical installations –
Part 2-2:
Particular requirements –
Electromagnetic remote-control switches
(RCS)
Numéro de référence
Reference number
CEI/IEC 60669-2-2:2006
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE
IEC
60669-2-2
INTERNATIONAL
Troisième édition
STANDARD
Third edition
2006-08
Interrupteurs pour installations électriques
fixes domestiques et analogues –
Partie 2-2:
Exigences particulières –
Interrupteurs à commande à distance
(télérupteurs)
Switches for household and similar
fixed electrical installations –
Part 2-2:
Particular requirements –
Electromagnetic remote-control switches
(RCS)
IEC 2006 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
P
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 60669-2-2 CEI:2006
SOMMAIRE
AVANT-PROPOS.4
1 Domaine d’application .8
2 Références normatives.8
3 Termes et définitions .10
4 Exigences générales .12
5 Généralités sur les essais .14
6 Valeurs assignées .14
7 Classification.14
8 Marques et indications.16
9 Vérification des dimensions .18
10 Protection contre les chocs électriques.18
11 Dispositions pour assurer la mise à la terre .18
12 Bornes.18
13 Exigences constructives .18
14 Mécanisme.18
15 Résistance au vieillissement, protection procurée par les enveloppes des
interrupteurs et résistance à l'humidité .20
16 Résistance d'isolement et rigidité diélectrique .20
17 Echauffement .20
18 Pouvoir de fermeture et de coupure.22
19 Fonctionnement normal .22
20 Résistance mécanique .24
21 Résistance à la chaleur .24
22 Vis, parties transportant le courant et connexions.24
23 Lignes de fuite, distances d'isolement dans l'air et distances à travers la matière
de remplissage .24
24 Résistance de la matière isolante à une chaleur anormale, au feu et aux courants
de cheminement .28
25 Protection contre la rouille.28
26 Exigences de compatibilité électromagnétique.28
101Fonctionnement anormal du circuit de commande .28
Tableau 101 – Limites d’échauffement des bobines isolées dans l’air .22
60669-2-2 IEC:2006 – 3 –
CONTENTS
FOREWORD.5
1 Scope.9
2 Normative references .9
3 Terms and definitions .11
4 General requirements .13
5 General notes on tests .15
6 Ratings.15
7 Classification.15
8 Marking .17
9 Checking of dimensions.19
10 Protection against electric shock .19
11 Provision for earthing .19
12 Terminals .19
13 Constructional requirements .19
14 Mechanism .19
15 Resistance to ageing, protection provided by enclosures of switches and
resistance to humidity.21
16 Insulation resistance and electric strength .21
17 Temperature rise .21
18 Making and breaking capacity .23
19 Normal operation.23
20 Mechanical strength .25
21 Resistance to heat.25
22 Screws, current-carrying parts and connections.25
23 Creepage distances, clearances and distances through sealing compound .25
24 Resistance of insulating material to abnormal heat, to fire and to tracking .29
25 Resistance to rusting.29
26 EMC requirements.29
101Abnormal operation of the control circuit .29
Table 101 – Temperature-rise limits for insulated coils in air.23
– 4 – 60669-2-2 CEI:2006
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
INTERRUPTEURS POUR INSTALLATIONS ÉLECTRIQUES FIXES
DOMESTIQUES ET ANALOGUES –
Partie 2-2: Exigences particulières –
Interrupteurs à commande à distance (télérupteurs)
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60669-2-2 a été établie par le sous-comité 23B: Prises de
courant et interrupteurs, du comité d'études 23 de la CEI: Petit appareillage.
Cette troisième édition annule et remplace la seconde édition publiée en 1996 et son
amendement 1 (1997) et constitue une révision technique.
La présente édition présente, par rapport à l'édition antérieure, les modifications suivantes:
– clarification du domaine d’application afin d’exclure les interrupteurs électroniques à
commande à distance relevant de la CEI 60669-2-1;
– addition de symboles à l'Article 8;
– addition d’exigences pour la TBTP et la TBTS.
60669-2-2 IEC:2006 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED
ELECTRICAL INSTALLATIONS –
Part 2-2: Particular requirements –
Electromagnetic remote-control switches (RCS)
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60669-2-2 has been prepared by subcommittee 23B: Plugs,
socket-outlets and switches, of IEC technical committee 23: Electrical accessories.
This third edition cancels and replaces the second edition published in 1996 and amendment 1
(1997) of which it constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
– clarification of the scope to exclude electronic RCS (to be covered by IEC 60669-2-1);
– introduction of symbols under Clause 8;
– introduction of requirements for SELV/PELV.
– 6 – 60669-2-2 CEI:2006
Le texte de la présente norme est issu des documents suivants:
FDIS Rapport de vote
23B/825/FDIS 23B/839/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.
La présente partie de la CEI 60669 doit être utilisée conjointement avec la CEI 60669-1. Elle
liste les modifications nécessaires pour convertir cette norme en une norme particulière pour
les interrupteurs à commande à distance (télérupteurs).
Dans cette publication, les caractères d'imprimerie suivants sont employés:
– exigences proprement dites: caractères romains;
– modalités d'essais: caractères italiques;
– notes: petits caractères romains.
Les paragraphes, figures ou tableaux complémentaires à ceux de la Partie 1 sont numérotés
à partir de 101.
Une liste de toutes les parties de la série CEI 60669, présentées sous le titre général
Interrupteurs pour installations électriques fixes domestiques et analogues, peut être
consultée sur le site web de la CEI.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous «http://webstore.iec.ch» dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
60669-2-2 IEC:2006 – 7 –
The text of this standard is based on the following documents:
FDIS Report on voting
23B/825/FDIS 23B/839/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This part of IEC 60669 is to be used in conjunction with IEC 60669-1. It lists the changes
necessary to convert that standard into a specific standard for electromagnetic remote-control
switches.
In this publication, the following print types are used:
– requirements proper: in roman type;
– test specifications: in italic type;
– notes: in smaller roman type.
Subclauses, figures or tables which are additional to those in part 1 are numbered starting
from 101.
A list of all parts of IEC 60669 series, under the general title Switches for household and
similar fixed-electrical installations, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under “http://webstore.iec.ch” in the
data related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
– 8 – 60669-2-2 CEI:2006
INTERRUPTEURS POUR INSTALLATIONS ÉLECTRIQUES FIXES
DOMESTIQUES ET ANALOGUES –
Partie 2-2: Exigences particulières –
Interrupteurs à commande à distance (télérupteurs)
1 Domaine d’application
L’article de la partie 1 s'applique avec les exceptions suivantes:
Remplacement de la première phrase par:
La présente partie de la CEI 60669 s'applique aux interrupteurs à commande à distance
(désignés ci-après télérupteurs) de tension assignée ne dépassant pas 440 V et de courant
assigné ne dépassant pas 63 A, prévus pour installations électriques fixes domestiques et
analogues intérieures ou extérieures.
La bobine du télérupteur peut être alimentée en permanence ou non.
Les télérupteurs électroniques sont couverts par le domaine d'application de la CEI 60669-2-1.
Les télérupteurs comportant uniquement des composants passifs tels que des résistances,
des capacités, des composants CTP et CTN et des cartes électroniques de circuit imprimé ne
sont pas considérés comme des télérupteurs électroniques.
Les contacteurs ne sont pas couverts par la présente norme.
2 Références normatives
L'article de la partie 1 s'applique avec les additions suivantes:
CEI 60085:2004, Evaluation et classification thermiques de l'isolation électrique
CEI 60317, Spécifications pour types particuliers de fils de bobinage
CEI 60445:1999, Principes fondamentaux et de sécurité pour les interfaces homme-machines,
le marquage et l'identification – Identification des bornes de matériels et des extrémités de
certains conducteurs désignés et règles générales pour un système alphanumérique
CEI 60669-2-1:2002, Interrupteurs pour installations électriques fixes domestiques et
analogues – Partie 2: Prescriptions particulières – Section 1: Interrupteurs électroniques
CEI 61140, Protection contre les chocs électriques – Aspects communs aux installations et
aux matériels
CEI 61558-2-6:1997, Sécurité des transformateurs, blocs d'alimentation et analogues – Partie
2-6: Règles particulières pour les transformateurs de sécurité pour usage général
60669-2-2 IEC:2006 – 9 –
SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED
ELECTRICAL INSTALLATIONS –
Part 2-2: Particular requirements –
Electromagnetic remote-control switches (RCS)
1 Scope
This clause of part 1 is applicable except as follows:
Replacement of the first sentence:
This part of IEC 60669 applies to electromagnetic remote-control switches (hereinafter
referred to as RCS) with a rated voltage not exceeding 440 V and a rated current not
exceeding 63 A, intended for household and similar fixed electrical installations, either indoors
or outdoors.
The RCS coil may or may not be permanently energized.
Electronic RCS are within the scope of IEC 60669-2-1.
RCS including only passive components such as resistors, capacitors, PTC and NTC
components and printed wiring boards are not considered to be electronic RCS.
Contactors are not covered by this standard.
2 Normative references
This clause of part 1 is applicable with the following additions:
IEC 60085:2004, Electrical insulation - Thermal classification
IEC 60317, Specifications for particular types of winding wires
IEC 60445:1999, Basic and safety principles for man-machine interface, marking and
identification – Identification of equipment terminals and of terminations of certain designated
conductors, including general rules for an alphanumeric system
IEC 60669-2-1:2002, Switches for household and similar fixed electrical installations −
Part 2-1: Particular requirements − Electronic switches
IEC 61140, Protection against electric shock – Common aspects for installation and
equipment
IEC 61558-2-6:1997 Safety of power transformers, power supply units and similar – Part 2-6:
Particular requirements for safety isolating transformers for general use
– 10 – 60669-2-2 CEI:2006
3 Termes et définitions
L'article de la partie 1 s'applique avec les additions suivantes:
3.17 Addition de la note suivante:
NOTE Cette définition s’applique seulement au circuit de l’interrupteur.
3.18 Addition de la note suivante:
NOTE Cette définition s’applique seulement au circuit de l’interrupteur.
Addition des nouvelles définitions suivantes:
3.101
télérupteur
RCS
interrupteur destiné à être commandé à distance
3.101.1
télérupteur électromagnétique
télérupteur pourvu d’une bobine qui est commandée au moyen d’impulsions ou qui peut être
alimentée en permanence au moyen d’un circuit de commande
3.101.2
télérupteur électronique
télérupteur comportant un ou plusieurs composants électroniques
3.102
tension de commande assignée
tension assignée au circuit de commande par le fabricant. Généralement, c’est la tension de
fonctionnement de la bobine de commande électromagnétique
3.103
circuit de l'interrupteur
circuit comportant les parties permettant le passage du courant assigné dans le télérupteur
3.104
circuit de commande
circuit comportant les parties électriques pour la commande du mécanisme de commutation
3.105
mécanisme de commande
mécanisme comprenant toutes les parties destinées au fonctionnement du télérupteur
3.106
commande manuelle incorporée
dispositif qui permet de faire fonctionner le circuit de coupure directement ou indirectement.
Ce dispositif n'est pas prévu pour le fonctionnement normal du télérupteur
3.107
télérupteur à verrouillage
télérupteur verrouillé mécaniquement dans chacune des deux positions et disposant d'une
bobine séparée pour chaque position
60669-2-2 IEC:2006 – 11 –
3 Terms and definitions
This clause of part 1 is applicable with the following additions:
3.17 Addition of the following note:
NOTE This definition is only applicable to the switching circuit.
3.18 Addition of the following note:
NOTE This definition is only applicable to the switching circuit.
Addition of the following new definitions:
3.101
remote control switch
RCS
switch intended to be operated from a distance
3.101.1
electromagnetic RCS
RCS provided with a coil which is operated by means of impulses or which may be
permanently energized by means of a control circuit
3.101.2
electronic RCS
RCS containing electronic component(s)
3.102
rated control voltage
voltage assigned to the control circuit by the manufacturer. This is generally the operating
voltage of the electromagnetic control coil
3.103
switching circuit
circuit which contains the parts which allow the rated current to flow through the RCS
3.104
control circuit
circuit which includes electrical parts to actuate the switching mechanism
3.105
control mechanism
mechanism which includes all the parts which are intended for the operation of the RCS
3.106
incorporated hand-operated device
device which allows the switching circuit to be operated, directly or indirectly. This device is
not intended for the normal operation of the RCS
3.107
latching RCS
RCS which is mechanically locked in either of the two positions, having a separate coil for
each position
– 12 – 60669-2-2 CEI:2006
3.108
télérupteur débrochable
télérupteur composé de deux parties, l’une servant de base et comportant les bornes, l’autre
amovible comportant le circuit de l’interrupteur et le circuit de commande, les deux parties
s’adaptant l’une dans l’autre par des connexions élastiques, en utilisant un moyen permettant
de les solidariser ou les séparer avec ou sans l’aide d’un outil
3.109
courant de commande assigné
courant nécessaire pour l’excitation du télérupteur, assigné par le fabricant à la bobine du
circuit de commande (seulement pour les télérupteurs pourvus d’une bobine de courant)
3.110
télérupteur bistable
télérupteur contenant un mécanisme de commande qui, en l’absence d’excitation électrique
ou de manœuvre mécanique, reste dans sa position de fonctionnement et qui, sur excitation
électrique ou manœuvre mécanique, modifie sa position de fonctionnement
3.111
télérupteur monostable
télérupteur comprenant un mécanisme de commande qui, sous une excitation électrique ou
une manœuvre mécanique, change la position de fonctionnement de l’interrupteur qui reste
dans cette condition tant que le télérupteur est excité ou manœuvré et qui retourne à la
position initiale après que l’excitation ou la manœuvre est interrompue
3.112
télérupteur à priorité
télérupteur utilisé pour faire fonctionner directement ou indirectement un premier circuit de
charge ou un groupe de circuits de charge dont l’utilisation peut être arrêtée à certains
moments, le circuit de commande du télérupteur étant influencé par ou raccordé à un second
circuit ou groupe de circuit (circuits prioritaires ou circuits) qui, lorsqu’ils sont mis sous
tension, activent le circuit de commande du télérupteur qui coupe l’alimentation du premier
circuit de charge ou des premiers circuits pour une durée correspondant à la durée
d’alimentation du second circuit ou groupe de circuits
NOTE 1 Le télérupteur peut disposer de moyens pour régler la sensibilité du circuit de commande du télérupteur
en fonction de la charge totale ou du courant fourni à tous les éléments des circuits (interrupteur à priorité avec
bobine ampérométrique) ou être sensible à la tension (interrupteur à priorité avec bobine de tension) appliquée à
la seconde charge ou au groupe de charges.
NOTE 2 Ces dispositifs sont utilisés pour limiter le courant total dans une installation de foyer domestique pour
déconnecter/connecter certains circuits de charge de l'installation tandis que d'autres (les circuits prioritaires)
demeurent connectés.
3.113
télérupteur à fonctionnement séquentiel
télérupteur qui inclut plusieurs contacts interrupteurs ou inverseurs généralement mis en
fonctionnement au moyen d’une came permettant différentes combinaisons de circuit par
impulsions successives. Le nombre d’impulsions est donné par le nombre de bossages de la
came
4 Exigences générales
L'article de la partie 1 s'applique avec l'addition suivante:
Addition après le premier alinéa:
Le fonctionnement d’un télérupteur ne doit pas être perturbé quand il est monté avec un angle
ne s'écartant pas de plus de 5° de la position spécifiée d’utilisation.
60669-2-2 IEC:2006 – 13 –
3.108
disconnectable RCS
RCS including two parts, the first being used as a base and including the terminals, the other
being removable and including the switching and the control circuits, the two parts being
resiliently connected together using a means which allows joining and/or separating with or
without the use of a tool
3.109
rated control current
current required for initiation of the RCS, assigned to the current coil in the control circuit by
the manufacturer (only for an RCS provided with a current sensitive coil)
3.110
bistable RCS
RCS containing a control mechanism which, when not initiated electrically or actuated
mechanically, remains stable in its operating position and will change its operating position on
initiation or actuation
3.111
monostable RCS
RCS containing a control mechanism which, on electrical initiation or mechanical actuation,
changes the operating position of the switch which remains in this condition while the RCS is
initiated or actuated, and returns to the position prior to initiation or actuation of the RCS after
initiation or actuation is discontinued
3.112
priority RCS
RCS used to operate directly or indirectly a first load circuit or group of load circuits the use of
which at times can be dispensed with, and where the control circuit of the RCS is influenced
by or connected to a second circuit or group of circuits (priority circuits or circuits) which when
energized will thus initiate the control circuit of the RCS to de-energize the first load circuit or
circuits for the time during which the second circuit or group of circuits is energized
NOTE 1 The RCS may have a means for adjusting the sensitivity of the RCS control circuit to initiate the RCS
depending on the total load or current delivered to any part of the circuits (priority switch with current coil) or be
sensitive to the voltage (priority switch with voltage coil) applied to the second load or group of loads.
NOTE 2 These devices are used to limit the total current into a home installation by disconnecting/connecting
certain load circuits in the installation while leaving others (the priority circuits) connected.
3.113
sequential operated RCS
RCS which includes several switching or reversing contacts generally operated by means of a
cam allowing different circuit combinations by successive impulses. The number of impulses
is given by the number of lobes
4 General requirements
This clause of part 1 is applicable with the following addition:
Addition after the first paragraph:
The operation of an RCS shall not be impaired when it is mounted at an angle deviating by
not more than 5° from the specified position of use.
– 14 – 60669-2-2 CEI:2006
5 Généralités sur les essais
L'article de la partie 1 s'applique avec les additions suivantes:
5.4 Addition après le dernier alinéa:
Pour les essais de l’Article 101, trois échantillons supplémentaires sont nécessaires.
Addition du nouveau paragraphe suivant:
5.101 Si un télérupteur est équipé d’une commande manuelle incorporée, il doit être essayé
conformément aux exigences de l’Article 19.
NOTE 1 Lors des essais de pouvoir de fermeture et de coupure et des essais de fonctionnement normal, on
évitera d’appliquer la tension à la bobine du télérupteur toujours au même angle de phase, ce qui aurait pour
conséquence de fausser les résultats.
NOTE 2 Il convient de prendre des précautions lors de l’utilisation de combinateurs équipés de moteurs
synchrones et de dispositifs de commande ayant des caractéristiques similaires.
6 Valeurs assignées
L’article de la partie 1 s'applique avec les exceptions suivantes:
6.1 Remplacement:
Les tensions assignées préférentielles sont:
– en courant alternatif: 6 V, 8 V, 9 V, 12 V, 24 V, 42 V, 48 V, 110 V, 130 V, 220 V, 230 V et
240 V.
6.2 Addition, après le dernier alinéa, de la note suivante:
NOTE Dans certains types de télérupteurs, des contacts auxiliaires de courant plus faible que le courant assigné
au circuit de interrupteur peuvent être ajoutés. Les valeurs assignées et les exigences s’y rapportant sont à
l’étude.
Addition du nouveau paragraphe suivant:
6.101 Les tensions de commande assignées préférentielles sont:
– en courant alternatif: 6 V, 8 V, 9 V, 12 V, 24 V, 42 V, 48 V, 110 V, 130 V, 220 V, 230 V et
240 V ;
– en courant continu: 6 V, 9 V, 12 V, 24 V, 48 V, 60 V, 110 V et 220 V.
7 Classification
L'article de la partie 1 s'applique avec les additions suivantes:
7.1.5 Addition de ce qui suit:
– bobine de courant (pour télérupteur à priorité);
– bobine de tension (pour télérupteur à priorité).
7.1.7 Addition de ce qui suit:
– télérupteur débrochable;
60669-2-2 IEC:2006 – 15 –
5 General notes on tests
This clause of part 1 is applicable with the following additions:
5.4 Addition after the last paragraph:
For the tests of clause 101, three additional specimens are necessary.
Addition of the following new subclause:
5.101 If an RCS is provided with an incorporated hand-operated device, it shall be tested as
specified in Clause 19.
NOTE 1 During the making and breaking capacity tests and the normal operation tests, the application of the
voltage to the RCS coil always at the same phase angle is to be avoided, as this application may give misleading
results.
NOTE 2 Precautions should be taken when using combinations equipped with synchronous motors and devices
having similar operating characteristics.
6 Ratings
This clause of part 1 is applicable except as follows:
6.1 Replacement:
Preferred rated voltages are:
– a.c. : 6 V, 8 V, 9 V, 12 V, 24 V, 42 V, 48 V, 110 V, 130 V, 220 V, 230 V and 240 V.
6.2 Addition, after the last paragraph, of the following note:
NOTE In certain types of RCS, auxiliary contacts designed for a current lower than the rated current of the
switching circuit may be added. Relevant ratings and requirements are under consideration.
Addition of the following new subclause:
6.101 Preferred rated control voltages are:
– a.c. : 6 V, 8 V, 9 V, 12 V, 24 V, 42 V, 48 V, 110 V, 130 V, 220 V, 230 V and 240 V;
– d.c. : 6 V, 9 V, 12 V, 24 V, 48 V, 60 V, 110 V and 220 V.
7 Classification
This clause of part 1 is applicable with the following additions:
7.1.5 Addition of the following:
– current coil (for priority RCS);
– voltage coil (for priority RCS).
7.1.7 Addition of the following:
– disconnectable RCS;
– 16 – 60669-2-2 CEI:2006
Addition des nouveaux paragraphes suivants:
7.101 Selon le type de mécanisme de commutation:
– mécanisme à action simple;
– mécanisme à action séquentielle;
– mécanisme bistable;
– mécanisme monostable.
NOTE 1 Les télérupteurs à mécanisme à action simple sont ceux qui, à chaque impulsion, donnent un état soit
fermé soit ouvert, ces états se répétant à chaque impulsion sur 1, 2, 3 ou 4 pôles, soit en interrupteur, soit en
inverseur.
NOTE 2 Cela permet de classer les télérupteurs d’après le numéro de fonction de 7.1.1.
NOTE 3 La fonction numéro 5 peut être réalisée par deux télérupteurs de numéro de fonction 1 ou 6 et câblés
conformément à la Figure 8 de la CEI 60669-1.
NOTE 4 La fonction numéro 7 peut être réalisée par la fonction 6/2 en réalisant le câblage avec connexions
extérieures conformément à la Figure 8 de la CEI 60669-1.
7.102 Selon le mode d’excitation du circuit de commande:
– télérupteurs excités par impulsions;
– télérupteurs excités en permanence.
8 Marques et indications
L'article de la partie 1 s'applique avec les additions suivantes:
8.1 Addition après le deuxième tiret:
– la tension de commande assignée en volts, si celle-ci diffère de la tension assignée.
8.2 Addition des symboles suivants:
Mécanisme de commande .
Interrupteur.
ou ou ou
Mécanisme monostable .
Mécanisme bistable .
Télérupteur à priorité .
> ou >
I U
8.4 Addition après le dernier alinéa:
Si nécessaire, le schéma de câblage où est indiqué clairement le repérage des bornes doit
être fixé sur l’appareil ou à l’intérieur du couvercle de protection des bornes.
60669-2-2 IEC:2006 – 17 –
Addition of the following new subclauses:
7.101 According to the type of switching mechanism:
– directly operated mechanism;
– sequentially operated mechanism;
– bistable mechanism;
– monostable mechanism.
NOTE 1 Directly operated RCS are those which, for each impulse, show an ON or OFF state, these states
occurring for each impulse
...