ISO 24678-6:2026
(Main)Fire safety engineering — Requirements governing algebraic formulae — Part 6: Flashover-related phenomena
- Abstract
This document specifies the requirements governing the application of a set of explicit algebraic formulae for the calculation of specific characteristics of flashover-related phenomena.
- Status
- Published
- Publication Date
- 06-Aug-2026
- Technical Committee
- ISO/TC 92/SC 4 - Fire safety engineering
- Drafting Committee
- ISO/TC 92/SC 4/WG 9 - Calculation methods for FSE
- Current Stage
- 6060 - International Standard published - 60 Publication
- Start Date
- 07-Aug-2026
- Due Date
- 15-Apr-2027
- Completion Date
- 15-Apr-2027
ISO 24678-6:2026 is an ISO International Standard in the Fire safety engineering series. It specifies requirements for applying explicit algebraic formulae to calculate specific characteristics of flashover-related phenomena. The document is intended for fire safety practitioners and other competent users who use calculation methods in fire safety engineering.
What does ISO 24678-6:2026 specify?
ISO 24678-6:2026 sets the requirements for using algebraic formulae to estimate flashover-related characteristics in fire safety engineering. It focuses on how the formulae are applied, the limits of their use, and how to document the calculation method.
The document is organized into nine clauses plus one informative annex:
| Part of the document | What it covers |
|---|---|
| Clauses 1 to 3 | Scope, normative references, and terms and definitions |
| Clause 4 | Requirements governing the description of physical phenomena |
| Clauses 5 to 8 | Requirements governing the calculation process, limitations, input parameters, and domain of applicability |
| Clause 9 | Example of documentation |
| Annex A | Informative example formula sets for the minimum heat release rate to cause flashover in small enclosures |
In practice, this structure helps the user move from the physical meaning of flashover to the calculation rules, the allowed inputs, and the range of situations where the formulae can be used.
What are the key requirements of ISO 24678-6:2026?
ISO 24678-6:2026 does not stand alone as a general fire model. It builds on the general requirements in ISO 24678-1 and adds flashover-specific guidance for applying formulae to enclosure fires.
Physical phenomena and method selection
Clause 4 requires the general rules in ISO 24678-1 to apply to the description of physical phenomena. It also states that flashover is a complex, highly transient thermo-physical event, with a hot smoke layer forming in the upper part of an enclosure and with radiative and convective heat transfer affecting the fuel. In practice, the user needs to consider interactions between enclosure gases, surfaces, and burning items rather than treating flashover as a single isolated effect.
Clause 4 also requires guidance when more than one method can calculate the same quantity. That matters because different formulae in the annex apply to different scenarios, so the practitioner must choose the method that matches the enclosure, the ventilation condition, and the intended calculation purpose.
Calculation process, limitations, and input data
Clauses 5, 6, 7, and 8 all defer to ISO 24678-1 for the calculation process, limitations, input parameters, and domain of applicability. In practice, that means the user must follow the general ISO 24678-1 rules for setting up the calculation, stating its limits, identifying all inputs, and checking whether the method applies to the case being assessed.
For a reader using the standard in design work, this is important because the flashover formulae are not meant to be applied without stating the scenario assumptions. The document ties the calculation to defined parameters such as enclosure geometry, opening factor, and thermal inertia.
Documentation of the method
Clause 9 says that Annex A provides an example of formula sets that meet the requirements of Clauses 4 to 8. This matters because the document is not just about getting a number - it also supports documented engineering reasoning that can be reviewed in design files, technical reports, or fire safety assessments.
Informative formula sets in Annex A
Annex A gives example formula sets for the minimum heat release rate needed to cause flashover in small enclosures. It includes formulae for heavy constructions, mechanically ventilated enclosures, and formulae that account for thermal properties of the enclosure boundary. It also compares formulae with experimental data and shows where the methods are more conservative or more limited.
What terms does ISO 24678-6:2026 define?
ISO 24678-6:2026 uses the definitions from ISO 13943 and adds five terms relevant to flashover calculations.
- flashover - the rapid transition to total surface involvement of combustible materials within an enclosure.
- fuel-controlled burning - burning where the rate is governed mainly by fuel properties and fuel arrangement.
- opening factor - a parameter based on vent area and vent height that describes how easily air flows through an opening.
- thermal inertia - the ability of a material to absorb heat, expressed as the product of thermal conductivity, density, and specific heat.
- ventilation-controlled burning - burning where the rate is governed mainly by the incoming air flow to the enclosure.
These terms matter because they define the physical state of the fire and the enclosure conditions that determine whether a flashover formula is applicable.
Who uses ISO 24678-6:2026?
ISO 24678-6:2026 is aimed at fire safety practitioners involved in fire safety engineering calculation methods. The introduction says users are expected to be appropriately qualified and competent, and to understand the parameters within which the methods may be used.
It is used in performance-based fire safety design for new built environments such as buildings, ships, and vehicles, and for assessing existing built environments. Engineers use it when estimating the consequences of design fire scenarios, comparing trial designs, and deciding how a design should be modified to meet fire safety goals and performance criteria.
What changed in ISO 24678-6:2026 from the previous edition?
ISO 24678-6:2026 is the second edition and it cancels and replaces ISO 24678-6:2016. The main changes stated in the foreword are:
- the main text has been simplified by referring to ISO 24678-1;
- the distinction between formulae for heavy construction and for variable constructions has been clarified in Annex A;
- comparisons with experimental data have been updated in Annex A.
Which standards are used with ISO 24678-6:2026?
ISO 24678-6:2026 names these standards as part of its technical framework:
- ISO 13943 - provides the fire safety vocabulary used for the terms and definitions.
- ISO 24678-1 - supplies the general requirements for algebraic formulae, and Clauses 4 to 8 defer to it for core calculation rules.
- ISO 24678-4 - supports the description of smoke layers, which is relevant to the hot upper layer that develops before flashover.
- ISO 23932-1 - gives the general fire safety engineering process and the performance-based approach that this part supports.
- ISO 24678-5 - provides the vent flow methods referred to in Annex A when equivalent opening factor and incoming air flow are discussed.
- ISO 16733-2 - is identified in Annex A as referring to this document for the description of flashover.
What does the ISO 24678-6:2026 document contain?
ISO 24678-6:2026 contains the requirements clauses, a short example of documentation, and an informative annex with worked formula sets. Annex A includes the calculation procedure, a description of the flashover phenomenon, applicability limits, input parameter guidance, and the domain of applicability for the formulae.
The annex also provides symbols, example thermal inertia values for enclosure lining materials, and comparison tables for experimental datasets used to develop the formulae. It includes figures that show enclosure fire development and compare formula predictions with test data.
For practical use, the document supports selection and documentation of algebraic methods for estimating the minimum heat release rate for flashover in small enclosures, especially where the user needs to justify the choice of formula and the limits of its use.
Relations
- Effective Date
- 06-Jun-2022
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
ISO 24678-6:2026 is a standard published by the International Organization for Standardization (ISO). Its full title is "Fire safety engineering — Requirements governing algebraic formulae — Part 6: Flashover-related phenomena". This standard covers: This document specifies the requirements governing the application of a set of explicit algebraic formulae for the calculation of specific characteristics of flashover-related phenomena.
This document specifies the requirements governing the application of a set of explicit algebraic formulae for the calculation of specific characteristics of flashover-related phenomena.
ISO 24678-6:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.01 - Protection against fire in general. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO 24678-6:2026 has the following relationships with other standards: It is inter standard links to ISO 24678-6:2016. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ISO 24678-6:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 flashover
- 3.2 fuel-controlled burning
- 3.3 opening factor
- 3.4 thermal inertia
- 3.5 ventilation-controlled burning
- 4 Requirements governing the description of physical phenomena
- 5 Requirements governing the calculation process
- 6 Requirements governing limitations
- 7 Requirements governing input parameters
- 8 Requirements governing the domain of applicability
- 9 Example of documentation
- Annex A
- 1 Babrauskas’ simple formula, Formula (A.3)
- 2 Babrauskas’ complex formula, Formula (A.4)
- 3 Thomas’ Formula (A.5)
- 4 Hägglund’s Formula (A.6)
- 5 Foote’s formula, expressed by equivalent opening factor, Formula (A.9)
- 1 McCaffery’s formulae, Formula (A.10) and Formula (A.11) with t = 1 000 s
- 1 Lee’s formula, Formula (A.12)
- Bibliography
Introduction
The ISO 24678 series is intended to be used by fire safety practitioners involved with fire safety engineering calculation methods. It is expected that the users of this document are appropriately qualified and competent in the field of fire safety engineering. It is particularly important that users understand the parameters within which particular methodologies may be used.
Algebraic formulae conforming to the requirements of this document are used with other engineering calculation methods during a fire safety design. Such a design is preceded by the establishment of a context, including the fire safety goals and objectives to be met, as well as performance criteria when a trial fire safety design is subject to specified design fire scenarios. Engineering calculation methods are used to determine if these performance criteria are met by a particular design and if not, how the design needs to be modified.
The subjects of engineering calculations include the fire-safe design of entirely new built environments, such as buildings, ships or vehicles, as well as the assessment of the fire safety of existing built environments. The algebraic formulae discussed in this document can be useful for estimating the consequences of design fire scenarios. Such formulae are valuable for allowing the practitioner to quickly determine how a proposed fire safety design needs to be modified to meet performance criteria and to compare among multiple trial designs. Detailed numerical calculations can be carried out up until the final design documentation. Examples of areas where algebraic formulae have been applicable include determination of convective and radiative heat transfer from fire plumes, prediction of ceiling jet flow properties governing detector response times, calculation of smoke transport through vent openings, and analysis of compartment fire hazards such as smoke filling and flashover. However, the simple models often have stringent limitations and are less likely to include the effects of multiple phenomena occurring in the design scenarios. The general principles of fire safety engineering are described in ISO 23932-1, which provides a performancebased methodology for engineers to assess the level of fire safety for new or existing built environments. Fire safety is evaluated through an engineered approach based on the quantification of the behaviour of fire and based on knowledge of the consequences of such behaviour on life safety, property and the environment. ISO 23932-1 provides the process (i.e. necessary steps) and essential elements for conducting a robust performance-based fire safety design.
ISO 23932-1 is supported by a set of fire safety engineering documents on the methods and data needed for all the steps in a fire safety engineering design as summarized in Figure 1 (taken from ISO 23932-1:2018, Clause 4). This set of documents is referred to as the Global fire safety engineering analysis and information system. This global approach and system of standards provide an awareness of the interrelationships between fire evaluations when using the set of fire safety engineering documents. The set of documents includes ISO/TS 13447, ISO 16730-1, ISO 16732-1, ISO 16733-1, ISO/TS 16733-2, ISO/TR 16738, ISO 24678-1, ISO 24679-1, ISO/TS 29761 and other supporting Technical Reports that provide examples of and information on the application of these documents.
Each document supporting the global fire safety engineering analysis and information system includes language in the introduction to tie that document to the steps in the fire safety engineering design process outlined in ISO 23932-1. ISO 23932-1 requires that engineering methods be selected properly to predict the fire consequences of specific scenarios and scenario elements (see ISO 23932-1:2018, Clause 12). Pursuant to the requirements of ISO 23932-1, this document provides the requirements governing algebraic formulae for fire safety engineering. This step in the fire safety engineering process is shown as a highlighted box in Figure 1 and described in ISO 23932-1.
ISO 24678-6:2026(en)
a See also ISO/TR 16576 (examples).
b See also ISO 16732-1, ISO 16733-1, ISO/TS 16733-2, ISO/TS 29761.
See also ISO 16732-1, ISO 16733-1, ISO/TS 16733-2, ISO/TS 29761. d See also ISO/TS 13447, ISO 16730-1, ISO/TR 16730-2 to ISO/TR 16730-5 (examples), ISO/TR 16738, ISO 24678-1 to ISO 24678-7 and ISO 24678-9.
e See also ISO/TR 16738, ISO 16733-1, ISO/TS 16733-2.
NOTE Documents linked to large parts of the fire safety engineering design process: ISO 16732-1, ISO 16733-1, ISO 24678-1, ISO 24679-1, ISO/TS 29761, ISO/TR 16732-2 and ISO/TR 16732-3 (examples), ISO/TR 24679-2 to ISO/TR 24679-6, ISO/TR 24679-8 (examples).
SOURCE: ISO 23932-1:2018, Figure 1.
Figure 1 — Flow chart illustrating the fire safety engineering design process
International Standard ISO 24678-6:2026(en) Fire safety engineering — Requirements governing algebraic formulae — Part 6:
Flashover-related phenomena
1 Scope
This document specifies the requirements governing the application of a set of explicit algebraic formulae for the calculation of specific characteristics of flashover-related phenomena.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 13943, Fire safety — Vocabulary ISO 24678-1, Fire safety engineering — Requirements governing algebraic formulae — Part 1: General requirements ISO 24678-4, Fire safety engineering — Requirements governing algebraic formulae — Part 4: Smoke layers
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 13943 and the following apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https:// www .iso .org/ obp
- IEC Electropedia: available at https:// www .electropedia .org/
3.1 flashover
rapid transition to a state of total surface involvement in a fire of combustibles within an enclosure
3.2 fuel-controlled burning
state in which the burning rate is controlled by fuel conditions such as material properties of fuel, surface area and orientation
3.3 opening factor
parameter determining the rate of airflow through a vent, calculated by the product of vent area and square root of vent height
3.4 thermal inertia
ability of material to absorb heat, calculated by the product of thermal conductivity, density and specific heat of the material
ISO 24678-6:2026(en)
3.5 ventilation-controlled burning
state in which the burning rate is controlled by air flow incoming to an enclosure
4 Requirements governing the description of physical phenomena
4.1 The requirements governing the description of physical phenomena as specified in ISO 24678-1 shall apply, in addition to the requirements specified in 4.2 to 4.3. 4.2 The onset of flashover is a complex thermo-physical phenomenon that can be highly transient. As a result of burning in an enclosure, hot smoke layer develops in the upper part. This shall be as stated in ISO 24678-4. Heat and mass transfer in an enclosure takes place. Radiative and convective heat transfer to fuel surface may increase the heat release rate. To calculate the onset of flashover, interactions between phenomena should be considered.
4.3 As different formulae describe different flashover characteristics or apply to different scenarios, if there is more than one method for calculating a given quantity, guidance shall be given on the selection of appropriate methods. A descriptive example is given in Annex A.
5 Requirements governing the calculation process
The requirements specified in ISO 24678-1 governing the calculation process shall apply.
6 Requirements governing limitations
The requirements specified in ISO 24678-1 governing limitations shall apply.
7 Requirements governing input parameters
The requirements specified in ISO 24678-1 governing input parameters shall apply.
8 Requirements governing the domain of applicability
The requirements specified in ISO 24678-1 governing the domain of applicability shall apply.
9 Example of documentation
An example of sets of algebraic formulae meeting the requirements of Clause 4, Clause 5, Clause 6, Clause 7 and Clause 8 is provided in Annex A.
ISO 24678-6:2026(en)
Annex A
(informative)
Algebraic formulae for calculating the minimum heat release rate to cause flashover in small enclosures A.1 General This annex describes formula sets for minimum heat release rate to cause flashover in small enclosures. The formula sets discussed in this annex were all empirically derived using temperature and heat flux measurements from fire tests where different fuels were burned in enclosures of similar size and construction. The tests were generally performed to study enclosure fire behaviour, including the phenomenon of flashover. As combustion products from fires have substantially higher temperature than the ambient air, the enclosure gases stratify with the less dense hot combustion products forming a growing hot layer in the ceiling volume of the enclosure. The consensus threshold heat release rate for flashover, Q , fo is reached when the measured temperature of hot layer exceeds certain values such as 500 °C to 600 °C
(approximately 770 K to 870 K) and radiation heat flux to floor surface exceeds 20 kW/m which is enough [6] to ignite common combustible materials in a short time .
The range of application is limited by the range of experiments from which these formula sets were derived; namely, enclosures that have moderate volume. All of these formula sets were empirically derived based on [6][7] small enclosures. The datasets analysed show wide variations because they are collected from similar experimental enclosures but using different fuel packages and enclosure lining materials. Note that the majority of algebraic relationships discussed in Clauses A.3 to A.9 have been derived from experiments in naturally ventilated enclosures. Only one of the formula sets was developed for forced ventilation conditions. Comparisons with experimental data are included to assess the uncertainties of formulae.
The formulae, all normalized by the opening factorAH , relate Q to the total interior surface area of the fo
enclosure and a factor proportional to the thermal inertia of the enclosure surfaces. A.2 Symbols used in this annex
A area of floor (m ) f
A total internal surface area of the enclosure excluding opening area (m ) T -1/2 ratio of total internal surface area to opening factor (m ) AA/ H T vv
A area of ventilation opening (m )
5/2 opening factor (m ) AH
A area of walls and ceiling (m ) wc −1 −1 c specific heat (kJ·kg ·K ) f(x) function of x −2 −1 h effective heat transfer coefficient (kW·m ·K ) T H height of ventilation opening (m)
ISO 24678-6:2026(en) −1 −1 k thermal conductivity (kW·m ·K ) 2 −4 −2 −1 (kρc) thermal inertia of floor lining (kJ ·m ·K ·s ) f 2 −4 −2 −1 (kρc) thermal inertia of wall and ceiling linings (kJ ·m ·K ·s ) wc −1
m mechanical ventilation rate (kg·s ) e
m mass flow rate of air incoming to an enclosure (kg/s)
Q minimum heat release rate to cause flashover (kW) fo t characteristic time for flashover occurrence (s)
−3 ρ density (kg·m ) A.3 Description of physical phenomena addressed by the formula set A.3.1 General description of the calculation method A.3.1.1 Calculation procedure Estimating the minimum heat release rate for flashover involves the following steps:
- determination of geometry of the enclosure (internal surface area of enclosure, width and height of an opening, etc.);
- determination of characteristics of lining materials, etc., if applicable;
- calculation of minimum heat release rate for flashover.
A.3.1.2 Flashover characteristics to be calculated Consider a growing fire in an enclosure as shown in Figure A.1. A combustible object has just been ignited. Enough air is available for combustion in the early stage of fire growth. The burning is said to be fuelcontrolled because the combustion, including the resultant heat release rate, is primarily influenced by fuel factors such as fuel type (the material) and its configuration (horizontal or vertical). Combustion products tend to form a layer under the ceiling because they are hotter and therefore less dense than the ambient environment. There is often a fairly sharp demarcation between a hot upper smoke layer and a relatively cool lower layer. As burning continues, the hot layer increases in depth and temperature. This increases the radiative and convective heat transfer to burning items below, which in turn increases their heat release rate resulting in an increase in the upper layer temperature, further enhancing heat transfer rates to burning items and enclosure surfaces. If sufficient fuel is present and arranged in such a way that the fire continues to grow, the fire can enter a transitional phase known as flashover. Flashover is the rapid transition to a state of total surface involvement in a fire of combustible materials within an enclosure. Essentially, almost all exposed combustible surfaces ignite and start to burn during flashover. This results in a fully developed fire. Flashover is often associated with a sharp peak of burning rate. After the peak, fire transfers from fuel-controlled burning to ventilation-controlled burning where the heat release rate is limited by oxygen availability, which is provided by the flow of fresh air into the enclosure. After flashover, there is typically no longer any separation between a hot upper layer and a cool lower layer. Rather, a single well-mixed zone of hot gases exists. The occurrence of flashover and transition to post-flashover burning represents the most hazardous stage of an enclosure fire. Due to the incomplete combustion in an enclosure, oxygen concentration in the generated smoke is reduced, while the concentrations of CO and CO are considerably increased. As the smoke is full of soot particles, visibility
through smoke is reduced. Flame may emerge from the opening of the enclosure. Therefore, it is of great practical importance to be able to estimate the onset of flashover by way of the minimum heat release rate at which a fire will show transition to its flashover stage.
...