Abstract

ISO 10121-2:2013 aims to provide an objective test method to estimate the performance of any full size gas filtration device (GPACD) for general filtration regardless of media or technique used in the device. In fact, the goal of this part of ISO 10121 is to avoid relating the test data to internal parameters altogether. The benefit with this approach is that customers of GPACDs will be able to concentrate on price/performance and suppliers will have access to a normative and objective test standard that will not require the release of proprietary information or reverse engineering of the product. To ensure objectivity for test equipment suppliers, no specific design of the test apparatus is specified. Instead requirements of apparatus properties and validation tests are specified. However, different design examples in present use are outlined. ISO 10121-2:2013 can also be used with technologies such as scrubbers, absorbers, non-sorptive devices or packed columns as long as they fit into the test apparatus, can be meaningfully judged by the test method and are intended for general ventilation applications, both residential and non residential. Nuclear and military applications are specifically excluded.

Status
Not Published
Current Stage
6000 - International Standard under publication
Start Date
18-Nov-2026
Completion Date
21-Nov-2026

Buy Documents

Draft

ISO/FDIS 10121-2 - Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation — Part 2: Gas-phase air cleaning devices (GPACD)

Release Date:08-Sep-2026
English language (41 pages)
sale 15% off
sale 15% off
Draft

REDLINE ISO/FDIS 10121-2 - Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation — Part 2: Gas-phase air cleaning devices (GPACD)

Release Date:08-Sep-2026
English language (41 pages)
sale 15% off
sale 15% off
Draft

ISO/FDIS 10121-2 - Méthodes d'essai pour l'évaluation de la performance des médias et des dispositifs de filtration moléculaire pour la ventilation générale — Partie 2: Dispositifs de filtration moléculaire (GPACD)

Release Date:07-Nov-2026
French language (46 pages)
sale 15% off
sale 15% off

ISO 10121-2 is an International Standard from ISO for testing gas-phase air cleaning devices (GPACD) used in general ventilation. It specifies an objective laboratory method to estimate pressure drop, removal efficiency, capacity and retentivity without relying on the device's internal design, so suppliers, test labs and buyers can compare products on measured performance.

What does ISO 10121-2 specify?

ISO 10121-2 specifies a test method for any full, half or quarter size GPACD intended for general ventilation, regardless of the media or technique used inside the device. The method is intended for residential and non-residential applications and excludes nuclear and military uses.

The standard is organized around:

  • Clause 5 - testing of GPACDs, including the test rig and benchmark setup
  • Clause 6 - the test sequence
  • Clause 7 - validation of the test setup
  • Clause 8 - evaluation and reporting
  • Annex A - normative requirements for equipment, validation and routine operation
  • Annex B - informative guidance on challenge compounds, generation sources and analysis techniques
  • Annex C - informative examples of test equipment designs
AnnexWhat it covers
Annex ATest equipment requirements, validation checks and routine operation
Annex BChallenge compounds, generation sources and recommended analysis techniques
Annex CExample test rig designs and configurations

What are the key requirements of ISO 10121-2?

ISO 10121-2 is built around four measured performance parameters: pressure drop, initial removal efficiency, capacity and retentivity. Clause 5 explains the test conditions, Clause 6 defines the sequence, and Clause 7 requires validation before testing starts.

Test rig and duct requirements

Clause 5 requires a test rig that prevents leakage and bypass around the GPACD, with uniform mixing and even face velocity across the cross-section. The GPACD section of the duct has a fixed internal dimension of 610 mm by 610 mm, and a 300 mm by 300 mm duct is also permitted for an actual size 300 mm by 300 mm GPACD.

This matters because uneven flow or leakage can distort the measured efficiency and pressure drop. The standard also requires upstream and downstream sampling positions, plus a third position for air flow measurement, so the measured data reflect the device rather than the ductwork.

Measured parameters and data quality

Clause 5.3 requires continuous logging of concentration, pressure, temperature, relative humidity and air flow rate, with accuracy and oscillation limits set in Table 1. The document also requires the instrument and sampling performance to be good enough to support the chosen challenge concentration and test duration.

In practice, this means the test is only valid if the analyser, sensors and flow control are stable enough to capture small changes over time. The standard also notes that the test bench should be conductive and grounded, and that the empty duct pressure drop should be documented.

Agreed test conditions and benchmark setup

Clause 5.4 says the user and supplier agree the rated air flow, challenge compound, challenge concentration, temperature, relative humidity and test duration. The standard explains that performance can change with concentration, temperature, humidity and air flow rate, so the selected test conditions must match the intended use or a defined benchmark.

For benchmark screening, Clause 5.5 gives a simplified setup with set values for face velocity, temperature, humidity and three challenge compounds. The benchmark compounds are sulfur dioxide (SO2), ammonia (NH3) and toluene, with corresponding low and high concentrations and recommended analysis techniques in Table 2. This gives buyers and suppliers a common basis for comparing devices before choosing application-specific test conditions.

Test sequence

Clause 6 requires the test sequence to start with conditioning and pressure drop determination. It then covers initial removal efficiency, capacity determination and retentivity determination, and states that capacity determination should at least be performed.

This sequence matters because a device may look good at the start of a test but lose performance as it loads. Pressure drop is measured across the device at 50 %, 75 %, 100 % and 125 % of rated air flow, which helps show how resistance changes with flow.

Capacity and retentivity

Clause 6.4 defines capacity testing at a higher challenge concentration to determine how much contaminant the GPACD can retain before a chosen end point is reached. The clause also allows one analyser with interpolation between upstream and downstream readings, or two analysers if available.

Clause 6.5 then measures retentivity by switching off the challenge compound and observing desorption. This is important for adsorbent GPACDs, because a device can release previously captured contaminant when clean air continues to pass through it.

Validation before testing

Clause 7 requires validation of the rig, generation equipment and analysers before testing. If only one analyser is used, rise time and decay time must be determined for the selected compound, concentration and air flow rate.

This matters because the lag in the sampling system can otherwise make the concentration curves misleading. The validation step ensures that readings taken during transition periods are discarded when needed and that the downstream values truly represent the device.

What terms does ISO 10121-2 define?

  • Gas-phase air cleaning device (GPACD) - a fixed-size assembly that removes specific gas or vapour contaminants from air.
  • Gas-phase air cleaning medium (GPACM) - the solid medium or medium configuration used for filtering the contaminant inside a GPACD.
  • Challenge compound - the chemical compound used as the test contaminant.
  • Removal efficiency - the fraction or percentage of challenge contaminant removed by the GPACD.
  • Capacity - the amount of selected sorbate the GPACD can hold under the test conditions up to a defined end point.
  • Retentivity - the ability of the GPACD to resist desorption after challenge breakthrough, expressed from the residual capacity after purging with clean air.
  • Breakthrough - the amount of gaseous contaminant appearing in the effluent of the GPACD.
  • Rise time / decay time - the time needed for the test system to reach the target concentration after a change, or to fall back near zero after the source is switched off.

Who uses ISO 10121-2?

ISO 10121-2 is used by GPACD suppliers, media suppliers, test laboratories, device manufacturers and end users who need to compare performance in a repeatable way. It is also relevant to test equipment builders and operators because Annex A sets out the equipment checks, calibration and routine validation they must maintain.

In practice, the standard supports product development, type testing, procurement and performance comparison for general ventilation applications. It is especially useful when a buyer wants an objective way to compare price versus performance without requiring disclosure of proprietary design details.

What changed in ISO 10121-2 from the previous edition?

ISO 10121-2:2026, second edition, cancels and replaces ISO 10121-2:2013. The changes stated in the document are:

  • terms and definitions were updated to align with ISO 29464:2024
  • the toluene concentration in the simplified benchmark test for initial efficiency was adjusted
  • other challenge concentrations were aligned with ISO 10121-1 and ISO 10121-3
  • Annex B was reviewed and concentration recommendations were removed for compounds requiring special attention
  • several subclauses were reworded and clarified
  • the wording for challenge gas, challenge species and challenge compound was standardized to challenge compound unless a specific gas is discussed
  • the formulae in 6.3.2 were corrected

Which standards are used with ISO 10121-2?

  • ISO 16890-2:2022 - cited as the normative reference used for the nine-point sampling approach in the concentration homogeneity check during validation.
  • ISO 10121-1 - named in the introduction as the companion part covering gas-phase air cleaning media and the interface between media suppliers and device producers or users.
  • ISO 10121-3 - named in the introduction as the part that provides a classification system for GPACDs in general ventilation.
  • ISO 29464:2024 - used as the source for many of the defined terms and vocabulary in this part.

What does the ISO 10121-2 document contain?

ISO 10121-2 contains a full test sequence, validation steps and reporting structure for GPACD performance testing. It includes Figure 1 for the required test rig layout, Figures 2 to 5 for example plots, and Table 1 for generation parameters and measurement accuracy.

Annex A gives detailed validation and routine-operation checklists. Annex B lists challenge compounds, generation sources and recommended online or ex situ analysis techniques, including acid, base, VOC and other compounds. Annex C shows example test rig designs and compares layouts used in other standards and test systems.

Relations

Effective Date
12-Feb-2026
Effective Date
30-Sep-2023

Buy Documents

Draft

ISO/FDIS 10121-2 - Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation — Part 2: Gas-phase air cleaning devices (GPACD)

Release Date:08-Sep-2026
English language (41 pages)
sale 15% off
sale 15% off
Draft

REDLINE ISO/FDIS 10121-2 - Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation — Part 2: Gas-phase air cleaning devices (GPACD)

Release Date:08-Sep-2026
English language (41 pages)
sale 15% off
sale 15% off
Draft

ISO/FDIS 10121-2 - Méthodes d'essai pour l'évaluation de la performance des médias et des dispositifs de filtration moléculaire pour la ventilation générale — Partie 2: Dispositifs de filtration moléculaire (GPACD)

Release Date:07-Nov-2026
French language (46 pages)
sale 15% off
sale 15% off

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Aboma Certification B.V.

Specialized in construction, metal, and transport sectors.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

ISO 10121-2 is a draft published by the International Organization for Standardization (ISO). Its full title is "Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation — Part 2: Gas-phase air cleaning devices (GPACD)". This standard covers: ISO 10121-2:2013 aims to provide an objective test method to estimate the performance of any full size gas filtration device (GPACD) for general filtration regardless of media or technique used in the device. In fact, the goal of this part of ISO 10121 is to avoid relating the test data to internal parameters altogether. The benefit with this approach is that customers of GPACDs will be able to concentrate on price/performance and suppliers will have access to a normative and objective test standard that will not require the release of proprietary information or reverse engineering of the product. To ensure objectivity for test equipment suppliers, no specific design of the test apparatus is specified. Instead requirements of apparatus properties and validation tests are specified. However, different design examples in present use are outlined. ISO 10121-2:2013 can also be used with technologies such as scrubbers, absorbers, non-sorptive devices or packed columns as long as they fit into the test apparatus, can be meaningfully judged by the test method and are intended for general ventilation applications, both residential and non residential. Nuclear and military applications are specifically excluded.

ISO 10121-2:2013 aims to provide an objective test method to estimate the performance of any full size gas filtration device (GPACD) for general filtration regardless of media or technique used in the device. In fact, the goal of this part of ISO 10121 is to avoid relating the test data to internal parameters altogether. The benefit with this approach is that customers of GPACDs will be able to concentrate on price/performance and suppliers will have access to a normative and objective test standard that will not require the release of proprietary information or reverse engineering of the product. To ensure objectivity for test equipment suppliers, no specific design of the test apparatus is specified. Instead requirements of apparatus properties and validation tests are specified. However, different design examples in present use are outlined. ISO 10121-2:2013 can also be used with technologies such as scrubbers, absorbers, non-sorptive devices or packed columns as long as they fit into the test apparatus, can be meaningfully judged by the test method and are intended for general ventilation applications, both residential and non residential. Nuclear and military applications are specifically excluded.

ISO 10121-2 is classified under the following ICS (International Classification for Standards) categories: 91.140.30 - Ventilation and air-conditioning systems. The ICS classification helps identify the subject area and facilitates finding related standards.

ISO 10121-2 has the following relationships with other standards: It is inter standard links to FprEN ISO 10121-2, ISO 10121-2:2013. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

ISO 10121-2 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


FINAL DRAFT
International
Standard
ISO/FDIS 10121-2
ISO/TC 142
Test methods for assessing the
Secretariat: UNI
performance of gas-phase air
Voting begins on:
cleaning media and devices for
2026-09-22
general ventilation —
Voting terminates on:
2026-11-17
Part 2:
Gas-phase air cleaning devices
(GPACD)
Méthodes d'essai pour l'évaluation de la performance des médias
et des dispositifs de filtration moléculaire pour la ventilation
générale —
Partie 2: Dispositifs de filtration moléculaire (GPACD)
RECIPIENTS OF THIS DRAFT ARE INVITED TO SUBMIT,
WITH THEIR COMMENTS, NOTIFICATION OF ANY
RELEVANT PATENT RIGHTS OF WHICH THEY ARE AWARE
AND TO PROVIDE SUPPOR TING DOCUMENTATION.
IN ADDITION TO THEIR EVALUATION AS
BEING ACCEPTABLE FOR INDUSTRIAL, TECHNO-
ISO/CEN PARALLEL PROCESSING LOGICAL, COMMERCIAL AND USER PURPOSES, DRAFT
INTERNATIONAL STANDARDS MAY ON OCCASION HAVE
TO BE CONSIDERED IN THE LIGHT OF THEIR POTENTIAL
TO BECOME STAN DARDS TO WHICH REFERENCE MAY BE
MADE IN NATIONAL REGULATIONS.
Reference number
ISO/FDIS 10121-2:2026(en) © ISO 2026

FINAL DRAFT
ISO/FDIS 10121-2:2026(en)
International
Standard
ISO/FDIS 10121-2
ISO/TC 142
Test methods for assessing the
Secretariat: UNI
performance of gas-phase air
Voting begins on:
cleaning media and devices for
general ventilation —
Voting terminates on:
Part 2:
Gas-phase air cleaning devices
(GPACD)
Méthodes d'essai pour l'évaluation de la performance des médias
et des dispositifs de filtration moléculaire pour la ventilation
générale —
Partie 2: Dispositifs de filtration moléculaire (GPACD)
RECIPIENTS OF THIS DRAFT ARE INVITED TO SUBMIT,
WITH THEIR COMMENTS, NOTIFICATION OF ANY
RELEVANT PATENT RIGHTS OF WHICH THEY ARE AWARE
AND TO PROVIDE SUPPOR TING DOCUMENTATION.
© ISO 2026
IN ADDITION TO THEIR EVALUATION AS
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
BEING ACCEPTABLE FOR INDUSTRIAL, TECHNO-
ISO/CEN PARALLEL PROCESSING
LOGICAL, COMMERCIAL AND USER PURPOSES, DRAFT
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
INTERNATIONAL STANDARDS MAY ON OCCASION HAVE
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
TO BE CONSIDERED IN THE LIGHT OF THEIR POTENTIAL
or ISO’s member body in the country of the requester.
TO BECOME STAN DARDS TO WHICH REFERENCE MAY BE
MADE IN NATIONAL REGULATIONS.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland Reference number
ISO/FDIS 10121-2:2026(en) © ISO 2026

ii
ISO/FDIS 10121-2:2026(en)
Contents Page
Foreword .v
Introduction .vi
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Symbols and abbreviated terms. 7
4.1 Symbols .7
4.2 Abbreviated terms .8
5 Testing of GPACDs . 8
5.1 General .8
5.2 Test rig and the required design of the GPACD section of test duct .9
5.3 Raw data, sampling accuracy and required generation parameters .10
5.4 Test parameters selected between user and supplier . 12
5.4.1 General . 12
5.4.2 Air flow rate and face velocity . 12
5.4.3 Challenge compound . . 12
5.4.4 Challenge concentration . 12
5.4.5 Temperature and relative humidity . 12
5.4.6 Test duration . 12
5.5 Simplified benchmark setup . 13
5.5.1 General . 13
5.5.2 Initial removal efficiency test . 13
5.5.3 Challenge test concentration . 13
5.5.4 GPACDs for VOC tested with toluene . 13
5.5.5 GPACDs for acids and bases tested with SO and NH , respectively . 13
2 3
5.5.6 Retentivity test .14
6 Test sequence . 14
6.1 General .14
6.2 Conditioning and pressure drop determination . 15
6.2.1 General . 15
6.2.2 Procedure . 15
6.2.3 Calculations . . 15
6.2.4 Reporting and graphs .16
6.3 Initial removal efficiency .16
6.3.1 General .16
6.3.2 Procedure .17
6.3.3 Calculations . .17
6.3.4 Reporting and graphs .18
6.4 Capacity determination .18
6.4.1 General .18
6.4.2 Procedure .18
6.4.3 Calculations . .19
6.4.4 Reporting and graphs . 20
6.5 Retentivity determination .21
6.5.1 General .21
6.5.2 Procedure .21
6.5.3 Calculations . .21
6.5.4 Reporting and graphs .21
7 Validation of test setup.22
7.1 General . 22
7.2 Determination of rise time and decay time . 22
7.2.1 General . 22

iii
ISO/FDIS 10121-2:2026(en)
7.2.2 Procedure . 22
7.2.3 Calculations . . 23
7.2.4 Reporting and graphs . 23
8 Evaluation and report .24
8.1 Test report introduction .24
8.2 Test report example .24
Annex A (normative) Test equipment requirements, equipment validation and routine
operation .29
Annex B (informative) Challenge compounds, generation sources and analysis techniques .33
Annex C (informative) Test equipment designs .38
Bibliography . 41

iv
ISO/FDIS 10121-2:2026(en)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee
has been established has the right to be represented on that committee. International organizations,
governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types
of ISO document should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent
rights in respect thereof. As of the date of publication of this document, ISO had not received notice of (a)
patent(s) which may be required to implement this document. However, implementers are cautioned that
this may not represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 142, Cleaning equipment for air and other gases,
in collaboration with the European Committee for Standardization (CEN) Technical Committee CEN/TC
195, Cleaning equipment for air and other gases, in accordance with the Agreement on technical cooperation
between ISO and CEN (Vienna Agreement).
This second edition cancels and replaces the first edition (ISO 10121-2:2013), which has been technically
revised.
The main changes are as follows:
— terms and definitions have been updated to conform with ISO 29464:2024;
— the toluene concentration has been adjusted in the simplified benchmark test for initial efficiency and all
other challenge concentrations now conform with ISO 10121-1 and ISO 10121-3;
— test compounds have been reviewed in Annex B and concentration recommendations have been removed
for compounds requiring special attention;
— subclauses 5.5.1, 6.2.1, 6.3.1, 6.4, 6.4.1, 6.4.3, 6.5, 6.5.17.2.2 and 7.2.3 have been reworded and clarified;
— the designations challenge gas, challenge species or challenge compound have been changed to challenge
compound unless a specific gas e.g SO is discussed;
— formulae in 6.3.2 have been corrected.
A list of all parts in the ISO 10121 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.

v
ISO/FDIS 10121-2:2026(en)
Introduction
There is an increasing use and need for gas-phase filtration in general filtration applications. This demand
can be expected to increase rapidly due to the increasing pollution problems in the world together with an
increasing awareness that solutions to the problems are available in the form of filtration devices or, phrased
more technically, gas-phase air cleaning devices (GPACD). The performance of devices relies to a large extent
on the performance of a gas-phase air cleaning media (GPACM) incorporated in the device. Still, applications
and device performance are often poorly understood by the users and suppliers of such media and devices.
Media tests can also be adequate to offer data for real applications if actual low concentrations (<100 ppb)
and longer exposure times (>weeks) can be used in the test, provided that the geometrical configuration,
packing density and air flow conditions of the small-scale test specimen are equal to those used in the real
applications. This document attempts to increase understanding and communication by supplying a more
standardized interface between media suppliers, device suppliers and end users. Other standards exist for
[1] [2]
general ventilation (JIS B 9901), automotive filters by ISO 11155-2, in-duct sorptive media gas-phase
[2] [3] [5]
air-cleaning devices (ASHRAE 145.2) and for adsorptive media (ASHRAE 145.1) and ASTM E 300-3.
The first edition of the ISO 10121 series was the first International Standard for general gas phase filtration.
This document prescribes methods, test equipment, data interpretation and reporting for gas-phase
air cleaning devices (GPACDs) intended for the removal of gas-phase contamination from air in general
ventilation applications. The test method enables customers of GPACDs to compare price versus performance
and provide suppliers with access to an equitable standard without requiring the release of proprietary
information or reverse engineering of the product.
In addition, information is given in the following annexes:
— Annex A describes the validation procedure in detail in a tabulated form.
— Annex B gives a list of possible test compounds, generation sources and suggests suitable analysis
equipment for common test compounds in addition to reference techniques given for the simplified
benchmark setup in 5.5.
— Annex C discusses different test rig designs.
The ISO 10121 series consists of three parts:
— ISO 10121-1 covers three different media configurations and aims to provide a standardized interface
between media suppliers and producers of air cleaning devices. It can also be used between media
suppliers and end customers with regards to loose fill media properties.
— ISO 10121-2 (this document) provides a standardized interface between suppliers of air cleaning devices
and end customers seeking the most cost-efficient way to employ gas-phase filtration.
— ISO 10121-3 provides a classification system for the specific application of GPACDs in general, ventilation
systems for cleaning of outdoor air polluted by either local urban sources or long-range transboundary
air pollution, or both.
vi
FINAL DRAFT International Standard ISO/FDIS 10121-2:2026(en)
Test methods for assessing the performance of gas-phase air
cleaning media and devices for general ventilation —
Part 2:
Gas-phase air cleaning devices (GPACD)
1 Scope
This document establishes an objective test method to estimate the performance of any full, half or quarter
size gas-phase air cleaning device (GPACD) for general filtration regardless of media or technique used in the
device.
Design of the test equipment is not specified. Instead, requirements for GPACD section of test duct, apparatus
properties and validation tests are specified.
This document applies to testing of any GPACD, as long as they fit into the test apparatus, can be meaningfully
judged by the test method and are intended for general ventilation applications, both residential and non-
residential.
Nuclear and military applications are specifically excluded.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
ISO 16890-2:2022, Air filters for general ventilation — Part 2: Measurement of fractional efficiency and air flow
resistance
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1
absorption
transport and dissolution of one substance into another to form a mixture having the characteristics of a
solution
[SOURCE: ISO 29464:2024, 3.5.1]
3.2
adsorbate
molecular compound in gaseous or vapour phase that can be retained by the adsorbent medium
[SOURCE: ISO 29464:2024, 3.5.3]

ISO/FDIS 10121-2:2026(en)
3.3
adsorbent
solid material having the ability to retain gases or vapour on its surface through physical or chemical
processes
[SOURCE: ISO 29464:2024, 3.5.4]
3.4
adsorption isotherm
relationship between the amount of a gas physically adsorbed on a surface and the partial pressure of the
gas at constant temperature
3.5
adsorption
process in which the molecules of a gas or vapour adhere by physical or chemical processes to the exposed
surfaces of solid substances, both the outer surface and inner pore surface, with which they come into
contact
[SOURCE: ISO 29464:2024, 3.5.7]
3.6
breakthrough
amount of gaseous contaminant in the effluent of a gas-phase air cleaning medium
Note 1 to entry: See penetration (3.31).
3.7
bypass
proportion of the challenge air stream that passes around the gas-phase air cleaning device without
contacting the media
[SOURCE: ISO 29464:2024, 3.1.5, modified — “air cleaner” replaced with gas-phase air cleaning device” and
“air cleaner” replaced with “media”.]
3.8
capacity
m
s
amount (mass or moles) of a selected sorbate that can be contained in the filter media of a gas-phase air
cleaning device at given test conditions, and a specific end point
Note 1 to entry: Capacity can also be negative during desorption.
3.9
challenge concentration
concentration of the test contaminant(s) of interest in the challenge air stream prior to filtration
[SOURCE: ISO 29464:2024, 3.5.16]
3.10
challenge compound
chemical compound that is being used as the contaminant of interest for any given test
[SOURCE: ISO 29464:2024, 3.5.15]
3.11
challenge air stream
test contaminant(s) of interest diluted to the specified concentration(s) of the test prior to filtration
[SOURCE: ISO 29464:2024, 3.5.14]

ISO/FDIS 10121-2:2026(en)
3.12
chemisorption
trapping of gaseous or vapour contaminants on an adsorbent involving chemical reaction on the adsorbent
surface
[SOURCE: ISO 29464:2024, 3.5.19]
3.13
concentration
C
n
quantity of one substance dispersed in a defined amount of another
Note 1 to entry: Indices “n” denote location.
[SOURCE: ISO 29464:2024, 3.1.11 modified — symbol added as admitted term; note 1 to entry has been
added.]
3.14
contaminant
substance (solid, liquid, or gas) that negatively affects the intended use of a fluid
[SOURCE: ISO 29464:2024, 3.1.12]
3.15
decay time
t
Dn
time required for the gas contaminant monitoring instrument to record a reduction from an initial
value greater than 95 % of the challenge concentration to a final value of less than 5 % of the challenge
concentration (t – t ) at the downstream sampling point for a specific test (n), challenge gas and gas
END VC
flow rate after stopping the injection of the contaminant with no gas-phase air cleaning media or device
present
[SOURCE: ISO 29464:2024, 3.5.21, modified — symbols have been added to the definition.]
3.16
desorption
process in which adsorbate molecules leave the surface of the adsorbent and re-enter the air stream
Note 1 to entry: Desorption is the opposite of adsorption.
[SOURCE: ISO 29464:2024, 3.5.22]
3.17
diffusor
device that forces the air stream to achieve an even face velocity over the entire cross-sectional area of a test
duct
Note 1 to entry: The device can be a perforated plate.
3.18
downstream
area or region into which air flows on leaving an air cleaner
[SOURCE: ISO 29464:2024, 3.1.16]
3.19
removal efficiency versus time curve
plot of the gas-phase air cleaning device medium or device removal efficiency against time over the duration
of a challenge test for a particular challenge concentration and air flow rate
[SOURCE: ISO 29464:2024, 3.5.58, modified — the word "rate" has been added.]

ISO/FDIS 10121-2:2026(en)
3.20
removal efficiency versus capacity curve
plot of the gas-phase air cleaning device removal efficiency against the integrated capacity over the duration
of a challenge test for a particular challenge concentration and air flow rate
[SOURCE: ISO 29464:2024, 3.5.56, modified — the word "rate" has been added.]
3.21
face velocity
volumetric air flow rate divided by the nominal air cleaner face area
Note 1 to entry: air cleaner face velocity is expressed in m/s (fpm).
[SOURCE: ISO 29464:2024, 3.1.20]
3.22
gas
substance whose vapour pressure is greater than the ambient pressure at ambient temperature
[SOURCE: ISO 29464:2024, 3.1.34]
3.23
gas-phase air cleaning device
GPACD
assembly of a fixed size enabling the removal of specific gas- or vapour-phase contaminants
Note 1 to entry: It is normally box shaped or fits into a box of dimensions between 290 mm × 290 mm × 290 mm up to
approximately 610 mm × 610 mm × 610 mm or 2 feet × 2 feet × 2 feet.
[SOURCE: ISO 29464:2024, 3.5.34]
3.24
gas-phase air cleaning device face area
GPACD face area
cross-sectional area of the gas-phase air cleaning (GPAC) device also including a header frame or other
support structure, if so equipped when viewed from the direction of air flow using exact dimensions
[SOURCE: ISO 29464:2024, 3.5.36]
3.25
gas-phase air cleaning medium
GPACM
solid medium or medium configuration used for filtering a contaminant
EXAMPLE A porous film or fibrous layer; a bead shaped, granular or pelletized adsorbent (or chemisorbent); a
support structure of fabric, foam or monoliths containing adsorbent in the form of small sized particles, granules,
spheres or powder; a woven or nonwoven fabric completely made from an adsorbent material.
[SOURCE: ISO 29464:2024, 3.5.37]
3.26
initial removal efficiency
efficiency of an unexposed filter or gas-phase air cleaning device calculated as soon after the start of a test
as is possible
Note 1 to entry: For gas-phase, this should be calculated as soon as a steady reading can be obtained.
[SOURCE: ISO 29464:2024, 3.5.60]

ISO/FDIS 10121-2:2026(en)
3.27
molecular contamination
contamination present in gas or vapour phase in an air stream and excluding compounds in particulate
(solid) phase regardless of their chemical nature
[SOURCE: ISO 29464:2024, 3.5.43]
3.28
ppb(v)
parts per billion by volume concentration measure normally used to record ambient levels of outdoor
pollution
3 3
Note 1 to entry: Units are mm /m .
[SOURCE: ISO 29464:2024, 3.5.46]
3.29
ppm(v)
parts per million by volume concentration measure normally used to record pollution levels in, for example,
work place safety
3 3 3
Note 1 to entry: Units are cm /m and ml/m .
[SOURCE: ISO 29464:2024, 3.5.47]
3.30
penetration
P
ratio of contaminant concentration downstream of an air cleaner to the upstream (challenge) concentration
Note 1 to entry: Sometimes expressed as a percentage.
Note 2 to entry: Penetration (P) related to efficiency (E) by the expression: E = (1 – P) × 100 %.
Note 3 to entry: Penetration is related to the decontamination factor (DF) by the expression, DF = 1/penetration.
[SOURCE: ISO 29464:2024, 3.1.41]
3.31
physisorption
physical adsorption
attraction of an adsorbate to the surface, both outer surface and inner pore surface, of an adsorbent by
physical forces (Van der Waals forces)
[SOURCE: ISO 29464:2024, 3.5.48]
3.32
pore
minute passageway through which fluid can pass or that exposes to the gas stream the internal surfaces of
an adsorbent media
[SOURCE: ISO 29464:2024, 3.5.49]
3.33
pressure drop
Δp
difference in pressure between two points in an air flow system at specified conditions, especially when
measured across a gas-phase air cleaning device

ISO/FDIS 10121-2:2026(en)
3.34
removal efficiency
E
fraction or percentage of a challenge contaminant that is removed by an air cleaner
[SOURCE: ISO 29464:2024, 3.1.17]
3.35
retentivity
m
r
measure of the ability of an adsorbent or gas-phase air cleaning device to resist desorption of an adsorbate
Note 1 to entry: Computed as the residual capacity (fraction remaining) after purging the adsorbent with clean,
conditioned air only, following challenge breakthrough.
[SOURCE: ISO 29464:2024, 3.5.63]
3.36
residence time
t
r
relative time that an increment of fluid (or contaminant) is within the boundaries of the medium volume
Note 1 to entry: An example of the medium volume is a bed of granules or a non-woven sheet.
Note 2 to entry: In typical use and in this document, this value neglects the fact that the media and possible support
structures occupy a significant portion of the volume of the bed (residence time is calculated as total bed volume/air
flow rate).
[SOURCE: ISO 29464:2024, 3.5.63]
3.37
rise time
t
Rn
time between initial injection of contaminant and reaching 95 % of the challenge concentration for an empty
duct (t – t ) measured at the downstream sampling
0 VO
Note 1 to entry: Rise time is specific to a particular test, challenge gas and gas flow rate.
[SOURCE: ISO 29464:2024, 3.5.42]
3.38
sorbate
molecular compounds that are retained in the adsorbent of the device
Note 1 to entry: The sorbate can refer to both intended compounds like the selected challenge gas in a test or pollution
in real service but also any other compound present in the air stream e.g. gases and vapours.
[SOURCE: ISO 29464:2024, 3.5.65]
3.39
vapour
substance whose vapour pressure is less than the ambient pressure at ambient temperature, but is present
in the gas phase through evaporation or sublimation
[SOURCE: ISO 29464:2024, 3.5.71]

ISO/FDIS 10121-2:2026(en)
4 Symbols and abbreviated terms
4.1 Symbols
C downstream concentration [ppb, ppm] measured at a position Y mm after the device
D
C upstream concentration [ppb, ppm] measured at a position X mm before the device
U
Δp pressure drop measured over the tested device [Pa]
E initial removal efficiency [%] for the device measured at a low (<1 ppm) challenge concentration during
I
the initial efficiency test in 6.3
E removal efficiency [%] for the device measured at the challenge concentration selected during the
C
capacity test in 6.4
E removal efficiency recorded at stop test time or value agreed between user and supplier [%]
END
m retentivity [g], [mol]; the amount withheld by the device after ventilating with clean air at the same air
r
flow rate selected during the capacity test until C reaches a specified value close to zero
D
m integrated amount in moles or grams of challenge compound accumulated during the initial efficiency
sEI
test in Formula (2)
m integrated amount in moles or gram of challenge compound accumulated during measurement at the
sU
upstream position in Formula (3)
m integrated amount in moles or grams of challenge compound accumulated during measurement at the
sD
downstream position in Formula (3)
m total integrated amount [g], [mol] of challenge compound accumulated during the whole challenge test
s
p upstream pressure [Pa] measured at a position X mm before the device
U
p downstream pressure [Pa] measured at a position Y mm after the device
D
Q air flow rate used in test (normally the rated air flow for the tested device) [m /h] measured at a posi-
tion Z mm after the device
φ upstream relative humidity [%] measured at a position X mm before the device
U
φ downstream relative humidity [%] measured at a position Y mm after the device
D
t start time. The time when C (contamination concentration upstream) equals the selected challenge
0 U
concentration for an empty duct
t time when a test is stopped. The time when a desired concentration or other termination criteria have
END
been met in any of the prescribed test procedures (The termination criteria are agreed between user
and supplier)
t decay time for challenge concentration
DC
t decay time for initial efficiency concentration
DE
t rise time for challenge concentration
RC
t rise time for initial efficiency concentration
RE
t time noted at challenge gas valve closure
VC
t time noted at challenge gas valve opening
VO
ISO/FDIS 10121-2:2026(en)
T upstream temperature [°C] measured at a position X mm before the device
U
T downstream temperature [°C] measured at a position Y mm after the device
D
v face velocity [m/s] calculated from air flow rate and cross-sectional area of device
f
X a position X positioned sufficiently far ahead of the device to allow undisturbed measurements, deter-
mined in the validation, Annex A. At the distance X, the challenge compound is sufficiently mixed and
uniform over the cross-sectional area of the duct while not being so close to the device that the device
itself obscures the air flow, pressure drop or concentration.
Y a position Y positioned sufficiently far after the device to allow undisturbed measurements, determined
in the validation section, Annex A. At the distance Y the penetrating challenge compound is sufficiently
mixed and uniform to represent the average concentration after the device and not being so close to the
device that the device itself obscures the flow, pressure drop or concentration.
Z a position Z positioned sufficiently far after the device to permit a reliable air flow rate measurement
using an orifice device, verified in the Annex A
4.2 Abbreviated terms
ASHRAE American Society of Heating Refrigerating and Air-conditioning Engineers
ASTM ASTM International, formerly known as the American Society for Testing and Materials (ASTM)
GPAC gas-phase air cleaning
GPACD gas-phase air cleaning device
GPACM gas-phase air cleaning medium/media
HEPA high efficiency particulate air (filter)
JIS Japanese Industrial Standards
JSA Japanese Standards Association
MFC mass flow controller
MSDS material safety data sheet
NMP N-Methyl-2-pyrrolidone
VOC volatile organic compound
5 Testing of GPACDs
5.1 General
This document shows how to measure four key parameters that reflect the performance of a GPACD. The
four parameters are:
— pressure drop, Δp;
— capacity, m ;
s
— removal efficiency, E;
— retentivity, m .
r
ISO/FDIS 10121-2:2026(en)
These parameters are:
— linked to each other;
— different for different challenge compounds (exception: Δp is not affected);
— different for different concentrations of the same challenge compound (exception: Δp is not affected);
— affected by other gases present, by temperature, by humidity and by the air flow rate.
The ideal case would be to test at the exact parameter values and concentration present in the intended
application, but then the test time would be as long as the real service life, e.g. years. One way to accelerate
the test is to increase the concentration. In this document, an increased concentration should be agreed
between the user and supplier. Alternatively, for general benchmark purposes three concentrations
are used, one mildly increased for determination of the removal efficiency and two strongly increased
for determination of capacity. The key performance parameters other important factors should also be
considered. Particles can be emitted downstream, at least during initial start-up, for GPACDs employing
loose fill granular and pelletized adsorbents or adsorbent fibres and possibly for other media types as well.
This can pose a problem depending on the sensitivity of the specific application and on available particle
filtration after the GPACD. Other factors that can be considered are gaseous emissions, corrosion resistance,
weight and depth requirements.
This clause describes the required components of the test rig, the required parameters for generation
of the challenge air stream and suggest test compounds for benchmark purposes and for the case when
the pollution in the real application is not yet defined. Clause 6 describes in detail the test sequence for
conditioning and for determination of pressure drop, initial removal efficiency, capacity and retentivity in
this order.
WARNING — This document does not purport to address all of the safety concerns, if any, associated
with its use. The user of this document is recommended to investigate any possible hazard and to
take the necessary precautions.
5.2 Test rig and the required design of the GPACD section of test duct
The test rig can be designed in various ways and it is not the purpose of this document to enforce a
particular engineering solution or analysis technique. Several designs and analysis techniques are described
in Annexes B and C. The user of this document that should select the solution best fitted to equipment
availability and other concerns. There are some key parameters that can severely skew the data or make
benchmark testing impossible unless they are controlled within specified limits. These parameters are
displayed in the required design of the test duct section in Figure 1 and in Table 1. The adherence to these
levels shall be demonstrated by the tests provided in Clause 7.
The GPACD shall be installed without leakages or bypass. The air stream should be uniformly mixed and with
equal velocity and upstream concentration over the cross-section. Recorded parameters are concentration,
C, pressure, p, temperature, T, and relative humidity, φ, in two positions. The air flow rate is recorded at a
third position that can be upstream or downstream of the GPACD.
The inner dimension (ID) of the duct, width and height as indicated in Figure 1, shall be 610 mm × 610 mm
along the whole GPACD section. Devices in their actual size and configuration shall always be tested. Flat
adaptor plates are used for GPACD < 610 mm × 610 mm. In addition, a duct with internal dimension (ID)
300 mm × 300 mm is permitted for testing of an actual size 300 mm × 300 mm GPACD. Acceptable sizes of
GPACD for testing are specified in Table 1. The length of the GPACD section shall be greater that the inner
dimension (ID) of the duct, ideally 1 × ID to 3 × ID. Any changes in duct diameter before and after the GPACD
section should be designed so that the air flow is uniform over the entire GPACD cross-section.

ISO/FDIS 10121-2:2026(en)
Key
1 diffusor and Δp device
2 sampling points – be of “fork” type or similar with multiple inlet points to make a compounded sample over
the whole cross-section
3 GPACD under test
4 GPACD section of test duct, starting at 1 and ending at 7
5 upstream sampling point for T , φ , p and C at X mm before the GPACD
U U U U
6 downstream sampling point for T , ΦΦ , p and C at Y mm after the GPACD
D D D D
7 example of air flow rate measurement device location at Z mm after the GPACD
W internal width of the test duct along the GPACD section
h internal height of the test duct along the GPACD section
Figure 1 — Test rig and the required design showing ducting, measurement parameters and
sampling points
5.3 Raw data, sampling accuracy and required generation parameters
All measurement parameters in Figure 1 should be measured continuously with a computerized logging
system. The sampling frequency should be fast enough to produce smoothly changing data and not overlook
any events. Required generation parameters and prescribed accuracy are given in Table 1.

ISO/FDIS 10121-2:2026(en)
Table 1 — Required generation parameters, measurement frequency and demands on accuracy
during test
Permissi- Permissible
c
Required ble Mean oscillation
Measurement
Parameter generation Unit Range Accuracy value mean value
frequency
parameters during short-term
test (10 min)
C ±10 ppb
U
(0 – 500 ppb)
selected in 5.4 100 to 5 min, 1 h, 4 h,
ppb(v) ±3 % ±3 %
±2,0 %
a
or 5.5 100 000 12 h
(500 ppb –
100 ppm)
b
C 1 min (or
D
±10 ppb
longer if at
(0 – 500 ppb)
least 100 data
1–2 % of C
U
n.a. pp
...


ISO/FDIS 10121-2:2026 (Ed.2)
ISO/TC142TC 142
Secretariat: UNI
Date: 2026-05-1109-08
Test methods for assessing the performance of gas-phase air cleaning
media and devices for general ventilation — Part 2: Gas phase air
cleaning devices (GPACD)
Part 2:
Gas-phase air cleaning devices (GPACD)
Méthodes d'essai pour l'évaluation de la performance des médias et des dispositifs de filtration moléculaire
pour la ventilation générale — Partie 2: Dispositifs de filtration moléculaire (GPACD)
Partie 2: Dispositifs de filtration moléculaire (GPACD)
FDIS stage
TTTTTThhhhhhiiiiiissssss d d d d d drrrrrraftaftaftaftaftaft i i i i i issssss s s s s s suuuuuubbbbbbmmmmmmiiiiiittttttttttttedededededed t t t t t toooooo   a pa pa pa pa pa pararararararallel vallel vallel vallel vallel vallel vooooootttttte e e e e e iiiiiinnnnnn I I I I I ISSSSSSOOOOOO,,,,,, C C C C C CEEEEEENNNNNN.

ISO/FDIS 10121-2:2026(en)
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication
may be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying,
or posting on the internet or an intranet, without prior written permission. Permission can be requested from either ISO
at the address below or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: + 41 22 749 01 11
EmailE-mail: copyright@iso.org
Website: www.iso.org
Published in Switzerland
© ISO #### 2026 – All rights reserved
ii
ISO/FDIS 10121-2:2026 (Ed.2(en)
Contents
Foreword . iv
Introduction . vi
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Symbols and abbreviated terms . 7
4.1 Symbols . 7
4.2 Abbreviated terms . 9
5 Testing of GPACDs . 9
5.1 General. 9
5.2 Test rig and the required design of the GPACD section of test duct . 10
5.3 Raw data, sampling accuracy and required generation parameters . 12
5.4 Test parameters selected between user and supplier . 13
5.5 Simplified benchmark setup . 14
6 Test sequence . 16
6.1 General. 16
6.2 Conditioning and pressure drop determination . 16
6.3 Initial removal efficiency . 19
6.4 Capacity determination . 20
6.5 Retentivity determination . 25
7 Validation of test setup . 25
7.1 General. 25
7.2 Determination of rise time and decay time . 26
8 Evaluation and report . 29
8.1 Test report introduction . 29
8.2 Test report example . 29
Annex A (normative) Test equipment requirements, equipment validation and routine
operation . 36
Annex B (informative) Challenge compounds, generation sources and analysis techniques . 41
Annex C (informative) Test equipment designs . 47
Bibliography . 53

iii
ISO/FDIS 10121-2:2026(en)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types of
ISO document should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent rights
in respect thereof. As of the date of publication of this document, ISO had not received notice of (a) patent(s)
which may be required to implement this document. However, implementers are cautioned that this may not
represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 142, Cleaning equipment for air and other gases,
in collaboration with the European Committee for Standardization (CEN) Technical Committee CEN/TC 195,
Cleaning equipment for air and other gases, in accordance with the Agreement on technical cooperation
between ISO and CEN (Vienna Agreement).
This second edition cancels and replaces the first edition (ISO 10121-2:2013), which has been technically
revised.
The main changes are as follows:
— terms and definitions have been updated to conform with ISO 29464:2024;
— the toluene concentration has been adjusted in the simplified benchmark test for initial efficiency and all
other challenge concentrations now conform with ISO 10121-1 and ISO 10121-3;
— test compounds have been reviewed in Annex BAnnex B and concentration recommendations have been
removed for compounds requiring special attention;
— subclauses 5.5.1, 6.2.1, 6.3.1, 6.4, 6.4.1, 6.4.3, 6.5, 6.5.17.2.2subclauses 5.5.1, 6.2.1, 6.3.1, 6.4, 6.4.1, 6.4.3,
6.5, 6.5.1 7.2.2 and 7.2.3 and 7.2.3 have been reworded and clarified;
— the designations challenge gas, challenge species or challenge compound have been changed to challenge
compound unless a specific gas e.g SO is discussed;
— formulae in 6.3.26.3.2 have been corrected.
A list of all parts in the ISO 10121 series can be found on the ISO website.
© ISO #### 2026 – All rights reserved
iv
ISO/FDIS 10121-2:2026 (Ed.2(en)
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.

v
ISO/FDIS 10121-2:2026(en)
Introduction
There is an increasing use and need for gas-phase filtration in general filtration applications. This demand can
be expected to increase rapidly due to the increasing pollution problems in the world together with an
increasing awareness that solutions to the problems are available in the form of filtration devices or, phrased
more technically, gas-phase air cleaning devices (GPACD). The performance of devices relies to a large extent
on the performance of a gas-phase air cleaning media (GPACM) incorporated in the device. Still, applications
and device performance are often poorly understood by the users and suppliers of such media and devices.
Media tests can also be adequate to offer data for real applications if actual low concentrations (<100 ppb)
and longer exposure times (>weeks) can be used in the test, provided that the geometrical configuration,
packing density and air flow conditions of the small-scale test specimen are equal to those used in the real
applications. This document attempts to increase understanding and communication by supplying a more
standardized interface between media suppliers, device suppliers and end users. Other standards exist for
[1] [1] [3] [2]
general ventilation in Japan by (JIS, B 9901), automotive filters by ISO, 11155-2, in-duct sorptive
[6] [2] [6]
media gas-phase air-cleaning devices by (ASHRAE 145.2) and for adsorptive media by (ASHRAE
[3] [7] [5]
145.1) and ASTM . E 300-3. The first edition of the ISO 10121 series was the first international
standardInternational Standard for general gas phase filtration.
This document prescribes methods, test equipment, data interpretation and reporting for gas-phase air
cleaning devices (GPACDs) intended for the removal of gas-phase contamination from air in general
ventilation applications. The test method enables customers of GPACDs to compare price versus performance
and provide suppliers with access to an equitable standard without requiring the release of proprietary
information or reverse engineering of the product.
In addition, information is given in the following annexes:
— Annex A— Annex A describes the validation procedure in detail in a tabulated form.
— Annex B— Annex B gives a list of possible test compounds, generation sources and suggests suitable
analysis equipment for common test compounds in addition to reference techniques given for the
simplified benchmark setup in 5.55.5.
— Annex C— Annex C discusses different test rig designs.
A general introduction to molecular filtration and molecular filtration testing can be found in the scientific
literature.
The ISO 10121 series consists of three parts:
— — ISO 10121-1 covers three different media configurations and aims to provide a standardized interface
between media suppliers and producers of air cleaning devices. It can also be used between media
suppliers and end customers with regards to loose fill media properties.
— — ISO 10121-2 (this document) provides a standardized interface between suppliers of air cleaning
devices and end customers seeking the most cost-efficient way to employ gas-phase filtration.
— — ISO 10121-3 provides a classification system for the specific application of GPACDs in general,
ventilation systems for cleaning of outdoor air polluted by either local urban sources or long-range
transboundary air pollution, or both.
© ISO #### 2026 – All rights reserved
vi
FINAL DRAFT International Standard ISO/FDIS 10121-2:2026 (Ed.2)

Test methods for assessing the performance of gas-phase air cleaning
media and devices for general ventilation —
Part 2:
Gas-phase air cleaning devices (GPACD)
1 Scope
This document establishes an objective test method to estimate the performance of any full, half or quarter
size gas-phase air filtrationcleaning device (GPACD) for general filtration regardless of media or technique
used in the device.
Design of the test equipment is not specified. Instead, requirements for GPACD section of test duct, apparatus
properties and validation tests are specified.
This document applies to testing of any GPACD, as long as they fit into the test apparatus, can be meaningfully
judged by the test method and are intended for general ventilation applications, both residential and non-
residential.
Nuclear and military applications are specifically excluded.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
ISO 16890--2:2022, Air filters for general ventilation — Part 2: Measurement of fractional efficiency and air flow
resistance
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— — ISO Online browsing platform: available at https://www.iso.org/obp
— — IEC Electropedia: available at https://www.electropedia.org/
3.1 3.1
absorption
transport and dissolution of one substance into another to form a mixture having the characteristics of a
solution
[SOURCE: ISO 29464:2024;, 3.5.1]
ISO/FDIS 10121-2:2026(en)
3.2 3.2
adsorbate
molecular compound in gaseous or vapour phase that can be retained by the adsorbent medium
[SOURCE: ISO 29464:2024;, 3.5.3]
3.3 3.3
adsorbent
solid material having the ability to retain gases or vapour on its surface through physical or chemical processes
[SOURCE: ISO 29464:2024;, 3.5.4]
3.4 3.4
adsorption isotherm
relationship between the amount of a gas physically adsorbed on a surface and the partial pressure of the gas
at constant temperature
3.5 3.5
adsorption
process in which the molecules of a gas or vapour adhere by physical or chemical processes to the exposed
surfaces of solid substances, both the outer surface and inner pore surface, with which they come into contact
[SOURCE: ISO 29464:2024;, 3.5.7]
3.6 3.6
breakthrough
amount of gaseous contaminant in the effluent of a GPACDgas-phase air cleaning medium
Note 1 to entry: See "penetration (3.31".).
3.7
breakthrough versus time curve
plot of contaminant penetration versus time for a particular challenge concentration and air flow rate
[SOURCE: ISO 29464:2024; 3.5.12]
3.7 3.8
bypass
proportion of the challenge air stream that passes around the GPACDgas-phase air cleaning device without
contacting the media
[SOURCE: ISO 29464:2024;, 3.1.5], modified — “air cleaner” replaced with gas-phase air cleaning device” and
“air cleaner” replaced with “media”.]
3.8 3.9
capacity
ms
amount (mass or moles) of a selected sorbate that can be contained in the filter media of a GPACDgas-phase
air cleaning device at given test conditions, and a specific end point
Note 1 to entry: Capacity can also be negative during desorption.
3.9 3.10
challenge concentration
concentration of the test contaminant(s) of interest in the challenge air stream prior to filtration
© ISO #### 2026 – All rights reserved
ISO/FDIS 10121-2:2026 (Ed. 2(en)
[SOURCE: ISO 29464:2024;, 3.5.16]
3.10 3.11
challenge compound
chemical compound that is being used as the contaminant of interest for any given test
[SOURCE: ISO 29464:2024;, 3.5.15]
3.11 3.12
challenge air stream
test contaminant(s) of interest diluted to the specified concentration(s) of the test prior to filtration
[SOURCE: ISO 29464:2024;, 3.5.14]
3.12 3.13
chemisorption
trapping of gaseous or vapour contaminants on an adsorbent involving chemical reaction on the adsorbent
surface
[SOURCE: ISO 29464:2024;, 3.5.19]
3.13 3.14
concentration
C
n
quantity of one substance dispersed in a defined amount of another
Note 1 to entry: Indices "“n"” denote location.
[SOURCE: ISO 29464:2024;, 3.1.11] modified — symbol added as admitted term; note 1 to entry has been
added.]
3.14 3.15
contaminant
substance (solid, liquid, or gas) that negatively affects the intended use of a fluid
[SOURCE: ISO 29464:2024;, 3.1.12]
3.15 3.16
decay time
t
Dn
time required for the gas contaminant monitoring instrument to record a reduction from an initial value
greater than 95 % of the challenge concentration to a final value of less than 5 % of the challenge concentration
(t – t ) at the downstream sampling point for a specific test (n), challenge gas and gas flow rate after
END VC
stopping the injection of the contaminant with no GPACgas-phase air cleaning media or device present
[SOURCE: ISO 29464:2024;, 3.5.21], modified — symbols have been added to the definition.]
3.16 3.17
desorption
process in which adsorbate molecules leave the surface of the adsorbent and re-enter the air stream
Note 1 to entry: Desorption is the opposite of adsorption.
[SOURCE: ISO 29464:2024;, 3.5.22]
ISO/FDIS 10121-2:2026(en)
3.17 3.18
diffusor
device that forces the air stream to achieve an even face velocity over the entire cross-sectional area of a test
duct
Note 1 to entry: The device can be a perforated plate.
3.18 3.19
downstream
area or region into which air flows on leaving an air cleaner
[SOURCE: ISO 29464:2024;, 3.1.16]
3.19 3.20
removal efficiency versus time curve
plot of the GPACgas-phase air cleaning device medium or device removal efficiency against time over the
duration of a challenge test for a particular challenge concentration and air flow rate
[SOURCE: ISO 29464:2024;, 3.5.58], modified — the word "rate" has been added.]
3.20 3.21
removal efficiency versus capacity curve
plot of the GPACDgas-phase air cleaning device removal efficiency against the integrated capacity over the
duration of a challenge test for a particular challenge concentration and air flow rate
[SOURCE: ISO 29464:2024;, 3.5.56], modified — the word "rate" has been added.]
3.21 3.22
face velocity
volumetric air flow rate divided by the nominal air cleaner face area
Note 1 to entry: air cleaner face velocity is expressed in m/s (fpm).
[SOURCE: ISO 29464:2024;, 3.1.20]
3.22 3.23
gas
substance whose vapour pressure is greater than the ambient pressure at ambient temperature
[SOURCE: ISO 29464:2024;, 3.1.34]
3.23 3.24
gas-phase air cleaning device
GPACD
assembly of a fixed size enabling the removal of specific gas- or vapour-phase contaminants
Note 1 to entry: It is normally box shaped or fits into a box of dimensions between 290 mm × 290 mm × 290 mm up to
approximately 610 mm × 610 mm × 610 mm or 2 feet × 2 feet × 2 feet.
[SOURCE: ISO 29464:2024;, 3.5.34]
© ISO #### 2026 – All rights reserved
ISO/FDIS 10121-2:2026 (Ed. 2(en)
3.25
3.24 GPAC media or
gas-phase air cleaning device face area
GPACD face area
cross-sectional area of the gas-phase air cleaning (GPAC media or) device also including a header frame or
other support structure, if so equipped when viewed from the direction of air flow using exact dimensions
[SOURCE: ISO 29464:2024;, 3.5.36]
3.243.25 3.26
gas-phase air cleaning medium
GPACM
mediasolid medium or mediamedium configuration used for filtering a contaminant
EXAMPLES aEXAMPLE A porous film or fibrous layer; a bead shaped, granular or pelletized adsorbent (or
chemisorbent); a support structure of fabric, foam or monoliths containing adsorbent in the form of small sized particles,
granules, spheres or powder; a woven or nonwoven fabric completely made from an adsorbent material.
[SOURCE: ISO 29464:2024;, 3.5.37]
3.253.26 3.27
initial removal efficiency
efficiency of an unexposed filter or GPACDgas-phase air cleaning device calculated as soon after the start of a
test as is possible
Note 1 to entry: For gas-phase, this should be calculated as soon as a steady reading can be obtained.
[SOURCE: ISO 29464:2024;, 3.5.60]
3.263.27 3.28
molecular contamination
contamination present in gas or vapour phase in an air stream and excluding compounds in particulate (solid)
phase regardless of their chemical nature
[SOURCE: ISO 29464:2024;, 3.5.43]
3.273.28 3.29
ppb(v)
parts per billion by volume concentration measure normally used to record ambient levels of outdoor
pollution
3 3
Note 1 to entry: Units are mm /m .
[SOURCE: ISO 29464:2024;, 3.5.46]
3.283.29 3.30
ppm(v)
parts per million by volume concentration measure normally used to record ambient levels of outdoor
pollution levels in, for example, work place safety
3 3 3
Note 1 to entry: Units are cm /m and ml/m .
[SOURCE: ISO 29464:2024;, 3.5.47]
ISO/FDIS 10121-2:2026(en)
3.293.30 3.31
penetration
P
ratio of contaminant concentration downstream of an air cleaner to the upstream (challenge) concentration
Note 1 to entry: Sometimes expressed as a percentage.
Note 2 to entry: Penetration (P) related to efficiency (E) by the expression: E = = (1 – P) × 100 %.
Note 3 to entry: Penetration is related to the decontamination factor (DF) by the expression, DF = = 1/penetration.
[SOURCE: ISO 29464:2024;, 3.1.41]
3.303.31 3.32
physisorption
physical adsorption
attraction of an adsorbate to the surface, both outer surface and inner pore surface, of an adsorbent by physical
forces (Van der Waals forces)
[SOURCE: ISO 29464:2024;, 3.5.48]
3.313.32 3.33
pore
minute passagewayspassageway through which fluid can pass or that exposeexposes to the fluidgas stream
the internal surfaces of an adsorbent media
[SOURCE: ISO 29464:2024;, 3.5.49]
3.323.33 3.34
pressure drop
Δp
difference in pressure between two points in an air flow system at specified conditions, especially when
measured across a GPACDgas-phase air cleaning device
3.333.34 3.35
removal efficiency
E
fraction or percentage of a challenge contaminant that is removed by an air cleaner
[SOURCE: ISO 29464:2024;, 3.1.17]
3.343.35 3.36
retentivity
m
r
measure of the ability of an adsorbent or GPACDgas-phase air cleaning device to resist desorption of an
adsorbate
Note 1 to entry: Computed as the residual capacity (fraction remaining) after purging the adsorbent with clean,
conditioned air only, following challenge breakthrough.
[SOURCE: ISO 29464:2024;, 3.5.63]
3.353.36 3.37
residence time
t
r
relative time that an increment of fluid (or contaminant) is within the boundaries of the medium volume
© ISO #### 2026 – All rights reserved
ISO/FDIS 10121-2:2026 (Ed. 2(en)
Note 1 to entry: An example of the medium volume is a bed of granules or a non-woven sheet.
Note 2 to entry: In typical use and in this document, this value neglects the fact that the media and possible support
structures occupy a significant portion of the volume of the bed (residence time is calculated as total bed volume/air flow
rate).
[SOURCE: ISO 29464:2024;, 3.5.6263]
3.363.37 3.38
rise time
t
Rn
time between initial injection of contaminant and reaching 95 % of the challenge concentration for an empty
duct (t – t ) measured at the downstream sampling
0 VO
Note 1 to entry: Rise time is specific to a particular test, challenge gas and gas flow rate.
[SOURCE: ISO 29464:2024;, 3.5.42]
3.373.38 3.39
sorbate
molecular compounds that are retained in the adsorbent of the device
Note 1 to entry: The sorbate can refer to both intended compounds like the selected challenge gas in a test or pollution
in real service but also any other compound present in the air stream e.g. gases and vapours.
[SOURCE: ISO 29464:2024;, 3.5.65]
3.40
sorption
process in which gas or liquid molecules are removed by a GPACD media by absorption or adsorption
[SOURCE: ISO 29464:2024; 3.5.67]
3.383.39 3.41
vapour
substance whose vapour pressure is less than the ambient pressure at ambient temperature, but is present in
the gas phase through evaporation or sublimation
[SOURCE: ISO 29464:2024;, 3.5.71]
4 Symbols and abbreviated terms
4.1 Symbols
C downstream concentration [ppb, ppm] measured at a position Y mm after the device
D
C upstream concentration [ppb, ppm] measured at a position X mm before the device
U
Δp pressure drop measured over the tested device [Pa]
E initial removal efficiency [%] for the device measured at a low (<1 ppm) challenge concentration
I
during the initial efficiency test in 6.36.3
E removal efficiency [%] for the device measured at the challenge concentration selected during the
C
capacity test in 6.46.4
E removal efficiency recorded at stop test time or value agreed between user and supplier [%]
END
ISO/FDIS 10121-2:2026(en)
m retentivity [g], [mol]; the amount withheld by the device after ventilating with clean air at the same air
r
flow rate selected during the capacity test until C reaches a specified value close to zero
D
m integrated amount in moles or grams of challenge compound accumulated during the initial efficiency
sEI
test in Formula (2) (2)
m integrated amount in moles or gram of challenge compound accumulated during measurement at the
sU
upstream position in Formula
(3) (3)
m integrated amount in moles or grams of challenge compound accumulated during measurement at the
sD
downstream position in Formula
(3) (3)
m total integrated amount [g], [mol] of challenge compound accumulated during the whole challenge test
s
p upstream pressure [Pa] measured at a position X mm before the device
U
p downstream pressure [Pa] measured at a position Y mm after the device
D
Q air flow rate used in test (normally the rated air flow for the tested device) [m /h] measured at a
position Z mm after the device
φ upstream relative humidity [%] measured at a position X mm before the device
U
φ downstream relative humidity [%] measured at a position Y mm after the device
D
t start time. The time when C (contamination concentration upstream) equals the selected challenge
0 U
concentration for an empty duct
t time when a test is stopped. The time when a desired concentration or other termination criteria have
END
been met in any of the prescribed test procedures (The termination criteria are agreed between user
and supplier)
t decay time for challenge concentration
DC
t decay time for initial efficiency concentration
DE
t rise time for challenge concentration
RC
t rise time for initial efficiency concentration
RE
t time noted at challenge gas valve closure
VC
t time noted at challenge gas valve opening
VO
T upstream temperature [°C] measured at a position X mm before the device
U
T downstream temperature [°C] measured at a position Y mm after the device
D
v face velocity [m/s] calculated from air flow rate and cross-sectional area of device
f
X a position X positioned sufficiently far ahead of the device to allow undisturbed measurements,
determined in the validation, Annex AAnnex A. At the distance X, the challenge compound is
sufficiently mixed and uniform over the cross-sectional area of the duct while not being so close to the
device that the device itself obscures the air flow, pressure drop or concentration.
Y a position Y positioned sufficiently far after the device to allow undisturbed measurements,
determined in the validation section, Annex AAnnex A. At the distance Y the penetrating challenge
compound is sufficiently mixed and uniform to represent the average concentration after the device
and not being so close to the device that the device itself obscures the flow, pressure drop or
concentration.
Z a position Z positioned sufficiently far after the device to permit a reliable air flow rate measurement
using an orifice device, verified in the Annex Anormative Annex A
© ISO #### 2026 – All rights reserved
ISO/FDIS 10121-2:2026 (Ed. 2(en)
4.2 Abbreviated terms
ASHRAE American Society of Heating Refrigerating and Air-conditioning Engineers
ASTM ASTM International, formerly known as the American Society for Testing and Materials (ASTM)
GPAC gas-phase air cleaning
GPACD gas-phase air cleaning device
GPACM gas-phase air cleaning medium/media
HEPA High Efficiency Particulate Airhigh efficiency particulate air (filter)
JIS Japanese Industrial Standards
JSA Japanese Standards Association
MFC Mass Flowmass flow controller
MSDS Material Safety Data Sheetmaterial safety data sheet
NMP nN-Methyl −-2-pyrrolidone
VOC Volatile Organic Compoundvolatile organic compound
5 Testing of GPACDs
5.1 General
This document shows how to measure four key parameters that reflect the performance of a GPACD. The four
parameters are:
— — pressure drop, Δp;
— — capacity, m ;
s
— — removal efficiency, E;
— — retentivity, m .
r
These parameters are:
— — linked to each other;
— — different for different challenge compounds (exception: Δp is not affected);
— — different for different concentrations of the same challenge compound (exception: Δp is not affected);
— — affected by other gases present, by temperature, by humidity and by the air flow rate.
The ideal case would be to test at the exact parameter values and concentration present in the intended
application, but then the test time would be as long as the real service life, e.g. years. One way to accelerate the
test is to increase the concentration. In this document, an increased concentration should be agreed between
the user and supplier. Alternatively, for general benchmark purposes three concentrations are used, one
mildly increased for determination of the removal efficiency and two strongly increased for determination of
capacity. Besides theThe key performance parameters other important factors should also be considered.
Particles can be emitted downstream, at least during initial start-up, for GPACDs employing loose fill granular
and pelletized adsorbents or adsorbent fibres and possibly for other media types as well. This can pose a
problem depending on the sensitivity of the specific application and on available particle filtration after the
ISO/FDIS 10121-2:2026(en)
GPACD. Other factors that can be considered are gaseous emissions, corrosion resistance, weight and depth
requirements.
This clause describes the required components of the test rig, the required parameters for generation of the
challenge air stream and suggest test compounds for benchmark purposes and for the case when the pollution
in the real application is not yet defined. Clause 6Clause 6 describes in detail the test sequence for conditioning
and for determination of pressure drop, initial removal efficiency, capacity and retentivity in this order.
Warning:WARNING — This document does not purport to address all of the safety concerns, if any,
associated with its use. The user of this document is recommended to investigate any possible hazard
and to take the necessary precautions.
5.2 Test rig and the required design of the GPACD section of test duct
The test rig can be designed in various ways and it is not the purpose of this document to enforce a particular
engineering solution or analysis technique. Several designs and analysis techniques are described in
Annexes B and Cthe informative annexes. It is the. The user of this document that should select the solution
best fitted with regard to equipment availability and other concerns. There are some key parameters that can
severely skew the data or make benchmark testing impossible unless they are controlled within specified
limits. These parameters are displayed in the normative required design of the test duct section in
Figure 1Figure 1 and in Table 1Table 1. The adherence to these levels shall be demonstrated by the tests
provided in Clause 7the validation section.
The GPACD shall be installed without leakages or bypass. The air stream should be uniformly mixed and with
equal velocity and upstream concentration over the cross-section. Recorded parameters are concentration, C,
pressure, p, temperature, T, and relative humidity, φ, in two positions. The air flow rate is recorded at a third
position that can be upstream or downstream of the GPACD.
The inner dimension (ID) of the duct, width and height as indicated in Figure 1Figure 1,, shall be
610 mm × 610 mm along the whole GPACD section. Devices in their actual size and configuration shall always
be tested. Flat adaptor plates are used for GPACD < 610 mm × 610 mm. In addition, a duct with internal
dimension (ID) 300 mm × 300 mm is permitted for testing of an actual size 300 mm × 300 mm GPACD.
Acceptable sizes of GPACD for testing are specified in Table 1Table 1. The length of the GPACD section shall
be greater that the inner dimension (ID) of the duct, ideally 1 to3 x× ID to 3 × ID. Any changes in duct diameter
before and after the GPACD section should be designed so that the air flow is uniform over the entire GPACD
cross-section.
© ISO #### 2026 – All rights reserved
ISO/FDIS 10121-2:2026 (Ed. 2(en)

Key
1 diffusor and Δp device
2 sampling points – be of “fork” type or similar with multiple inlet points to make a compounded sample over the whole cross-
section
3 GPACD under test
4 GPACD section of test duct, starting at 1 and ending at 7
5 upstream sampling point for T , φ , p and C at X mm before the GPACD
U U U U
ISO/FDIS 10121-2:2026(en)
6 downstream sampling point for T , ΦΦ , p and C at Y mm after the GPACD
D D D D
7 example of air flow rate measurement device location at Z mm after the GPACD
W internal width of the test duct along the GPACD section
h internal height of the test duct along the GPACD section
Figure 1 — Test rig and the required design showing ducting, measurement parameters and
sampling points
5.3 Raw data, sampling accuracy and required generation parameters
All measurement parameters in Figure 1Figure 1 should be measured continuously with a computerized
logging system. The sampling frequency should be fast enough to produce smoothly changing data and not
overlook any events. Required generation parameters and prescribed accuracy are given in Table 1Table 1.
Table 1 — Required generation parameters, measurement frequency and demands on accuracy
during test
Permis
Permissible
Required sible
c
oscillation Measureme
generation Mean
Parameter Unit Range Accuracy mean value nt
parameter value
short-term frequency
s during
(10 min)
test
CU ±10 ppb
(0 – 500 ppb)
selected in
100 to 5 min, 1 h,
5.45.4 or ppb(v) ±3 % ±3 %
±2,0 %
a
100 000 4 h, 12 h
5.55.5
(500 ppb –
100 ppm)
b
C 1 min (or
D
±10 ppb
longer if at
(0 – 500 ppb)
1–2 % of least 100 data
n.a. ppb(v) C to n.a n.a points can be
U
±2,0 %
100 000 generated
(500 ppb –
down to 50 %
100 ppm)
efficiency)
TU selected in
5.45.4 or ±0,5 °C ±1 °C
°C n.a. ±0,5 ℃ °C same as CD
5.55.5
TD n.a. n.a. n.a.
φ selected in
U
d d
5.45.4 or ±1,5 % ±3 %
d
% n.a. ±2,0 % same as C
D
5.55.5
φ n.a. n.a. n.a.
D
pU, pD – Pa – ±2 Pa n.a. n.a. same as CD
Δp (p – p ) ±2 Pa
U D
(0 – 100 Pa)
device
Pa – ± ± 2 % n.a. n.a. same as CD
specific
(100 – 10000
10 000 Pa)
Q, air flow
rated air
/h n.a. ±2 % ±1,5 % ±3 % same as C
m D
rate
flow
© ISO #### 2026 – All rights reserved
ISO/FDIS 10121-2:2026 (Ed. 2(en)
Permis
Permissible
Required sible
c
oscillation Measureme
generation Mean
Parameter Unit Range Accuracy mean value nt
parameter value
short-term frequency
s during
(10 min)
test
(5.4(5.4)) or
vf, face m/s n.a.
face velocity
velocity
2,5 m/s
(5.5(5.5))
GPACD face n.a. mm 610 n.a. n.a. n.a. n.a.
area for full, × × 610
half and quar-
terquarter
× × 305
e
size
× × 305
a Upstream concentration shall, at a minimum, to be measured before and after an individual test sequence.
b Measurement duration may need to be longer for concentration to permit low level detection using ex situ equipment, e.g.
Tenaxsample adsorption tubes, resulting in less frequent measurements than every 5 min.
c Oscillation refers here to a deviation upstream or downstream of a distinct mean value that returns to the mean value. A ramp-
like steady increase or decrease is not permitted. Mean value during test is calculated during the entire test. A short-term mean
value is calculated during an event being maximum 10 min long. More than one short-term event can be permitted
d The ±% ± % value here refers to percentage points of relative humidity and not to a calculated percentage of a value.
e GPACD face area defines a nominal size but actual minimum size of GPACD to be tested can be down to 590 mm × × 590 mm,
590 mm × × 285 mm and 285 mm × × 285 mm.
Temperature and relative humidity are normatively specified for benchmark tests (see 5.55.5)) but can also
be changed to fit a specific GPACD or application (see 5.45.4).).
5.4 Test parameters selected between user and supplier
5.4.1 General
The normativerequired setup specifies all variables except rated air flow, challenge compound, challenge
concentration, temperature, relative humidity and test duration. These parameters can depend on the
specification and purpose of the device under test and should be agreed upon between supplier and user.
5.4.2 Air flow rate and face velocity
The rated air flow for a GPACD is a construction parameter and the device will not perform as expected if the
air flow rate is different. since this will change the residence time for contact between the medium and the
challenge compound. A device can exhibit improved performance at a lower than rated air flow and reduced
performance at a higher than rated air flow.
5.4.3 Challenge compound
The challenge compound selection shall conform to the intended functionality of the GPACD, i.e. it shall be
established if the device is designed to remove the selected challenge compound. If possible, the best choice is
to use the same compound should be used as in the intended real application. Several known pollutant
compounds are suggestedrecommended in Annex BAnnex B.
ISO/FDIS 10121-2:2026(en)
5.4.4 Challenge concentration
The challenge concentration willis always be a compromise and poseposes a risk for under- or over-estimating
the real life performance of a GPACD. For a GPACD designed to remove organic compounds by physisorption,
the measured performance is a direct function of the selected challenge concentration as described by an
adsorption versus concentration isotherm. In addition, a device that performs best in a high concentration test
cannot be assumed to also be the best in the low concentrations of a real installation. Therefore, the lowest
practical possible challenge concentration should be used for both the initial efficiency and capacity portions
of the test. For a GPACD designed to remove acid or alkaline compounds by chemisorption, a concentration
dependence of capacity is not normally seen for challenge concentrations in the normative range if only a
chemisorptive mechanism is available. However, organic acids and bases can also be removed by
physisorption and also catalytic reactions are known, both phenomena adding to the capacity given by pure
chemisorption. The effects of the selected challenge concentration need toshall be assessed in each individual
case.
5.4.5 Temperature and relative humidity
The air temperature can affect the rate of chemical reactions in chemisorption and the ease of physisorption
of VOCs. The relative humidity needs toshall be over a certain minimum value for chemical reactions involving
water to proceed. In the case of adsorbents for VOC removal through physisorption, the relative humidity can
have quite a strong influence due to competition for adsorption sites between the water in the air and the
contaminants. For applications where either the expected temperature, or relative humidity, or both, is far
from the required values given in 5.55.5,, actual application parameters should be used for the test.
5.4.6 Test duration
The test duration is a function of the challenge compound, challenge concentration, adsorbent and selected
end point of the test. It is possible to define tests with duration from one hour to several months.
Selection of the four parameters in the previous sentence shall be agreed upon in each specific case. However,
for a first screening of suitable devices for general filtration a simplified benchmark setup is
suggestedrecommended in 5.55.5.
5.5 Simplified benchmark setup
5.5.1 General
For benchmark purposes, set values for face velocity, temperature, and relative humidity, along with three
concentration levels and three challenge compounds are suggestedrecommended as a best compromise
between measurement errors, the resolution of available measurement techniques and acceptable testing
times. These are given in Table 2Table 2. The intention of this setup is to aid in an initial screening of different
GPACDs and to establish a performance baseline. The setup is best suited for adsorbent type GPACDs. For
GPACDs using different technologies, it can needbe necessary to use different challenge test concentrations
and; these should be tested according to 5.45.4. It shall be stated that this simplified test cannot be sufficient
enough to determine the best device in a specific application.
5.5.2 Initial removal efficiency test
A low concentration shall be used in the determination of the initial efficiency. Ideally one would use the actual
concentration of the applicatio
...


PROJET FINAL
Norme
internationale
ISO/FDIS 10121-2
ISO/TC 142
Méthodes d'essai pour l'évaluation
Secrétariat: UNI
de la performance des médias et des
Début de vote:
dispositifs de filtration moléculaire
2026-09-22
pour la ventilation générale —
Vote clos le:
2026-11-17
Partie 2:
Dispositifs de filtration moléculaire
(GPACD)
Test methods for assessing the performance of gas-phase air
cleaning media and devices for general ventilation —
Part 2: Gas-phase air cleaning devices (GPACD)
LES DESTINATAIRES DU PRÉSENT PROJET SONT
INVITÉS À PRÉSENTER, AVEC LEURS OBSERVATIONS,
NOTIFICATION DES DROITS DE PROPRIÉTÉ DONT ILS
AURAIENT ÉVENTUELLEMENT CONNAISSANCE ET À
FOURNIR UNE DOCUMENTATION EXPLICATIVE.
OUTRE LE FAIT D’ÊTRE EXAMINÉS POUR
ÉTABLIR S’ILS SONT ACCEPTABLES À DES FINS
INDUSTRIELLES, TECHNOLOGIQUES ET COM-MERCIALES,
AINSI QUE DU POINT DE VUE DES UTILISATEURS, LES
PROJETS DE NORMES
TRAITEMENT PARALLÈLE ISO/CEN
INTERNATIONALES DOIVENT PARFOIS ÊTRE CONSIDÉRÉS
DU POINT DE VUE DE LEUR POSSI BILITÉ DE DEVENIR DES
NORMES POUVANT
SERVIR DE RÉFÉRENCE DANS LA RÉGLEMENTATION
NATIONALE.
Numéro de référence
ISO/FDIS 10121-2:2026(fr) © ISO 2026

PROJET FINAL
ISO/FDIS 10121-2:2026(fr)
Norme
internationale
ISO/FDIS 10121-2
ISO/TC 142
Méthodes d'essai pour l'évaluation
Secrétariat: UNI
de la performance des médias et des
Début de vote:
dispositifs de filtration moléculaire
2026-09-22
pour la ventilation générale —
Vote clos le:
2026-11-17
Partie 2:
Dispositifs de filtration moléculaire
(GPACD)
Test methods for assessing the performance of gas-phase air
cleaning media and devices for general ventilation —
Part 2: Gas-phase air cleaning devices (GPACD)
DOCUMENT PROTÉGÉ PAR COPYRIGHT
© ISO 2026
LES DESTINATAIRES DU PRÉSENT PROJET SONT
Tous droits réservés.
INVITÉS À PRÉSENTER, AVEC LEURS OBSERVATIONS,
NOTIFICATION DES DROITS DE PROPRIÉTÉ DONT ILS
La présente publication de l’ISO est protégée par le droit d’auteur et demeure la propriété de l’ISO et/ou de ses concédants de
AURAIENT ÉVENTUELLEMENT CONNAISSANCE ET À
licence.
FOURNIR UNE DOCUMENTATION EXPLICATIVE.
Le contenu de la présente publication de l’ISO est fourni sous licence, et n’est pas vendu. Son utilisation est soumise aux conditions
OUTRE LE FAIT D’ÊTRE EXAMINÉS POUR
ÉTABLIR S’ILS SONT ACCEPTABLES À DES FINS
de licence applicables définies par l’ISO, un organisme membre de l’ISO, ou un distributeur tiers agréé.
INDUSTRIELLES, TECHNOLOGIQUES ET COM-MERCIALES,
Sous réserve des besoins liés à sa mise en œuvre ou d’une autorisation expresse prévue aux termes d’une licence distincte, aucune
AINSI QUE DU POINT DE VUE DES UTILISATEURS, LES
partie de la présente publication de l’ISO ne peut être reproduite, distribuée, modifiée, utilisée ou mise à disposition sous quelque PROJETS DE NORMES
TRAITEMENT PARALLÈLE ISO/CEN
INTERNATIONALES DOIVENT PARFOIS ÊTRE CONSIDÉRÉS
forme ou par quelque moyen que ce soit – électronique ou mécanique, y compris la photocopie, la numérisation, l’enregistrement
DU POINT DE VUE DE LEUR POSSI BILITÉ DE DEVENIR DES
ou la publication sur des plateformes numériques internes ou externes.
NORMES POUVANT
SERVIR DE RÉFÉRENCE DANS LA RÉGLEMENTATION
Toute utilisation hors du champ d’application des droits accordés est interdite et peut donner lieu à des poursuites judiciaires.
NATIONALE.
ISO copyright office
Case postale 401 • CH-1214 Vernier, Genève
Tél.: +41 22 749 01 11
E-mail: copyright@iso.org
Web: www.iso.org
Publié en Suisse
Numéro de référence
ISO/FDIS 10121-2:2026(fr) © ISO 2026

ii
ISO/FDIS 10121-2:2026(fr)
Sommaire Page
Avant-propos .v
Introduction .vii
1 Domaine d’application . 1
2 Références normatives . 1
3 Termes et définitions . 1
4 Symboles et termes abrégés . 7
4.1 Symboles .7
4.2 Termes abrégés .8
5 Essais de GPACD . 9
5.1 Généralités .9
5.2 Installation d’essai et conception requise de la section du GPACD du conduit d’essai .9
5.3 Données brutes, précision d’échantillonnage et paramètres de génération requis .11
5.4 Paramètres d’essai sélectionnés entre utilisateur et fournisseur . 12
5.4.1 Généralités . 12
5.4.2 Débit d’air et vitesse frontale . 12
5.4.3 Composé d’essai . 12
5.4.4 Concentration d’essai . 13
5.4.5 Température et humidité relative . 13
5.4.6 Durée de l’essai . 13
5.5 Montage de référence simplifié . 13
5.5.1 Généralités . 13
5.5.2 Essai d’efficacité d’élimination initiale . 13
5.5.3 Concentration d’essai .14
5.5.4 GPACD pour COV soumis à essai avec du toluène .14
5.5.5 GPACD pour les acides et les bases soumis à essai respectivement avec du SO et
du NH .14
5.5.6 Essai de pouvoir de rétention . 15
6 Séquence d’essai .15
6.1 Généralités . 15
6.2 Conditionnement et détermination de la perte de charge . 15
6.2.1 Généralités . 15
6.2.2 Mode opératoire . .16
6.2.3 Calculs .16
6.2.4 Rapports et graphiques .16
6.3 Efficacité d’élimination initiale .17
6.3.1 Généralités .17
6.3.2 Mode opératoire . .17
6.3.3 Calculs .18
6.3.4 Rapports et graphiques .18
6.4 Détermination de la capacité .19
6.4.1 Généralités .19
6.4.2 Mode opératoire . .19
6.4.3 Calculs . 20
6.4.4 Rapports et graphiques .21
6.5 Détermination du pouvoir de rétention . 22
6.5.1 Généralités . 22
6.5.2 Mode opératoire . . 22
6.5.3 Calculs . 22
6.5.4 Rapports et graphiques . 23
7 Validation du montage d’essai .23
7.1 Généralités . 23
7.2 Détermination du temps de montée et du temps de décroissance . 23

iii
ISO/FDIS 10121-2:2026(fr)
7.2.1 Généralités . 23
7.2.2 Mode opératoire . . 23
7.2.3 Calculs .24
7.2.4 Rapports et graphiques .24
8 Évaluation et rapport .25
8.1 Introduction du rapport d’essai. 25
8.2 Exemple de rapport d’essai . 25
Annexe A (normative) Exigences relatives à l’équipement d’essai, validation de l’équipement et
fonctionnement de routine .30
Annexe B (informative) Composés d’essai, sources de génération et techniques d’analyse .35
Annexe C (informative) Conceptions des équipements d’essai . 41
Bibliographie .44

iv
ISO/FDIS 10121-2:2026(fr)
Avant-propos
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes nationaux
de normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est en général
confiée aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude a le droit de faire
partie du comité technique créé à cet effet. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec l'ISO participent également aux travaux. L'ISO collabore étroitement avec
la Commission électrotechnique internationale (IEC) en ce qui concerne la normalisation électrotechnique.
Les procédures utilisées pour élaborer le présent document et celles destinées à sa mise à jour sont
décrites dans les Directives ISO/IEC, Partie 1. Il convient, en particulier, de prendre note des différents
critères d’approbation requis pour les différents types de documents ISO. Le présent document a
été rédigé conformément aux règles de rédaction données dans les Directives ISO/IEC, Partie 2 (voir
www.iso.org/directives).
L’ISO attire l’attention sur le fait que la mise en application du présent document peut entraîner l’utilisation
d’un ou de plusieurs brevets. L’ISO ne prend pas position quant à la preuve, à la validité et à l’applicabilité de
tout droit de brevet revendiqué à cet égard. À la date de publication du présent document, l’ISO n’avait pas
reçu notification qu’un ou plusieurs brevets pouvaient être nécessaires à sa mise en application. Toutefois,
il y a lieu d’avertir les responsables de la mise en application du présent document que des informations
plus récentes sont susceptibles de figurer dans la base de données de brevets, disponible à l’adresse
www.iso.org/brevets. L’ISO ne saurait être tenue pour responsable de ne pas avoir identifié tout ou partie de
tels droits de propriété.
Les appellations commerciales éventuellement mentionnées dans le présent document sont données pour
information, par souci de commodité, à l’intention des utilisateurs et ne sauraient constituer un engagement.
Pour une explication de la nature volontaire des normes, la signification des termes et expressions
spécifiques de l’ISO liés à l’évaluation de la conformité, ou pour toute information au sujet de l’adhésion de
l’ISO aux principes de l’Organisation mondiale du commerce (OMC) concernant les obstacles techniques au
commerce (OTC), voir www.iso.org/avant-propos.
Le présent document a été élaboré par le Comité technique ISO/TC 142, Séparateurs aérauliques, en
collaboration avec le comité technique CEN/TC 195, Équipement de nettoyage de l’air et d’autres gaz, du
Comité européen de normalisation (CEN) conformément à l'Accord de coopération technique entre l'ISO et le
CEN (Accord de Vienne).
Cette deuxième édition annule et remplace la première édition (ISO 10121-2:2013), qui a fait l’objet d’une
révision technique.
Les principales modifications sont les suivantes:
— les termes et définitions ont été mis à jour pour se conformer à l’ISO 29464:2024;
— la concentration en toluène a été ajustée dans l’essai de référence simplifié pour l’efficacité initiale et
toutes les autres concentrations d’essai sont désormais conformes à l’ISO 10121-1 et l’ISO 10121-3;
— les composés d’essai ont été révisés à l’Annexe B et les recommandations relatives à la concentration ont
été supprimées pour les composés nécessitant une attention particulière;
— les paragraphes 5.5.1, 6.2.1, 6.3.1, 6.4, 6.4.1, 6.4.3, 6.5, 6.5.1, 7.2.2 et 7.2.3 ont été reformulés et clarifiés;
— les appellations gaz d'essai, espèces d'essai ou composés d’essai ont été remplacés par composé d'essai
sauf lorsqu'il est question d'un gaz spécifique, par exemple SO ;
— la formule en 6.3.2 a été corrigée.
Une liste de toutes les parties de la série ISO 10121 se trouve sur le site Web de l’ISO.

v
ISO/FDIS 10121-2:2026(fr)
Il convient que l’utilisateur adresse tout retour d’information ou toute question concernant le présent
document à l’organisme national de normalisation de son pays. Une liste exhaustive desdits organismes se
trouve à l’adresse www.iso.org/members.html.

vi
ISO/FDIS 10121-2:2026(fr)
Introduction
Il y a une utilisation et un besoin croissants de filtration moléculaire dans les applications de filtration
générales. Cette demande est appelée à augmenter rapidement du fait des problèmes croissants de pollution
dans le monde, ainsi que de la plus forte sensibilisation au fait que des solutions aux problèmes sont
disponibles sous forme de dispositifs de filtration ou, formulé de manière plus technique, de dispositifs
de filtration moléculaire (GPACD). La performance des dispositifs dépend largement de la performance
d’un média de filtration moléculaire (GPACM) incorporé au dispositif. Néanmoins, les applications et les
performances des dispositifs sont souvent peu comprises par les utilisateurs et les fournisseurs de ces médias
et dispositifs. Des essais des médias peuvent également être appropriés afin d’obtenir des données pour des
applications réelles si les concentrations faibles réelles (<100 ppb) et des durées d’exposition plus longues
(>semaines) peuvent être utilisées lors de l’essai, à condition que la configuration géométrique, la densité de
tassement et les conditions d’écoulement d'air de l’éprouvette à échelle réduite soient équivalentes à celles
utilisées dans les applications réelles. Le présent document a pour objectif d’améliorer la compréhension et
la communication en fournissant une interface plus normalisée entre fournisseurs de médias, fournisseurs
[1]
de dispositifs et utilisateurs finaux. D'autres normes existent pour la ventilation générale (JIS B 9901) ,
[2]
pour les filtres automobiles par ISO 11155-2 , pour les dispositifs de filtration moléculaire à média sorbant
[2] [3] [5]
en conduits (ASHRAE 145.2) et pour les médias d’adsorption (ASHRAE 145.1) et ASTM E 300-3 . La
première édition de la série ISO 10121 a été la première norme internationale pour la filtration moléculaire
générale.
Le présent document spécifie les méthodes, l'équipement d’essai, l’interprétation des données et le rapport
pour les dispositifs de filtration moléculaire (GPACD) destinés à l'élimination de la contamination en phase
gazeuse de l’air dans les applications de ventilation générale. La méthode d'essai permet aux clients des
GPACD de comparer le prix par rapport aux performances et offre aux fournisseurs l'accès à une norme
équitable sans nécessiter la divulgation d'informations confidentielles ou la rétro-ingénierie du produit.
De plus, des informations sont données dans les annexes suivantes:
— l’Annexe A décrit de façon détaillée la procédure de validation sous forme de tableau;
— l’Annexe B donne une liste de composés d’essai, de sources de génération possibles et suggère un
équipement d’analyse approprié pour les composés d’essai courants en plus des techniques de référence
données pour le montage de référence simplifié du 5.5;
— l’Annexe C traite des différentes conceptions de bancs d’essai.
La série ISO 10121 se compose de trois parties:
— l’ISO 10121-1 couvre trois configurations de médias différentes et vise à fournir une interface normalisée
entre les fournisseurs de médias et les fabricants de dispositifs de filtration. Elle peut également être
utilisée entre fournisseurs de médias et clients finaux pour ce qui concerne les propriétés des médias en
vrac;
— l’ISO 10121-2 (le présent document) fournit une interface normalisée entre fournisseurs de dispositifs
de filtration et clients finaux à la recherche de la solution la plus rentable pour mettre en œuvre une
filtration moléculaire;
— l’ISO 10121-3 fournit un système de classification pour l’application spécifique des GPACD en général, des
systèmes de ventilation pour l’épuration de l’air extérieur pollué par des sources urbaines locales ou par
la pollution atmosphérique transfrontalière à longue distance, ou les deux.

vii
PROJET FINAL Norme internationale ISO/FDIS 10121-2:2026(fr)
Méthodes d'essai pour l'évaluation de la performance des
médias et des dispositifs de filtration moléculaire pour la
ventilation générale —
Partie 2:
Dispositifs de filtration moléculaire (GPACD)
1 Domaine d’application
Le présent document établit une méthode d’essai objective pour estimer la performance de tout dispositif
de filtration moléculaire (GPACD) de taille réelle, demi-taille ou quart de taille pour la ventilation générale,
quels que soient les médias ou la technique utilisés dans le dispositif.
La conception de l'équipement d'essai n'est pas spécifiée. En revanche, les exigences relatives à la section
GPACD du conduit d'essai, aux propriétés de l'appareil et aux essais de validation sont spécifiées.
Le présent document s'applique aux essais de tout GPACD, à condition que celui-ci puisse être intégré dans
le dispositif d'essai, qu'il puisse faire l'objet d'une évaluation pertinente selon la méthode d'essai et qu'il soit
destiné à des applications de ventilation générale, tant résidentielles que non résidentielles.
Les applications nucléaires et militaires sont explicitement exclues.
2 Références normatives
Les documents suivants sont cités dans le texte de sorte qu’ils constituent, pour tout ou partie de leur
contenu, des exigences du présent document. Pour les références datées, seule l’édition citée s'applique. Pour
les références non datées, la dernière édition de la publication à laquelle il est fait référence s'applique (y
compris tous les amendements).
ISO 16890-2:2022, Filtres à air de ventilation générale — Partie 2: Mesurage de l’efficacité spectrale et de la
résistance à l’écoulement de l’air
3 Termes et définitions
Pour les besoins du présent document, les termes et définitions suivants s’appliquent.
L’ISO et l’IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation,
consultables aux adresses suivantes:
— ISO online browsing platform: disponible à l’adresse https:// www .iso .org/ obp;
— IEC Electropedia: disponible à l’adresse https:// www .electropedia .org/ .
3.1
absorption
transport et dissolution d’une substance dans une autre pour former un mélange présentant les
caractéristiques d’une solution
[SOURCE: ISO 29464:2024, 3.5.1]

ISO/FDIS 10121-2:2026(fr)
3.2
adsorbat
composé moléculaire en phase gazeuse ou vapeur qui peut être retenu par un média adsorbant
[SOURCE: ISO 29464:2024, 3.5.3]
3.3
adsorbant
matériau solide ayant la propriété de retenir les gaz ou la vapeur sur sa surface par des procédés physiques
ou chimiques
[SOURCE: ISO 29464:2024, 3.5.4]
3.4
isotherme d’adsorption
relation entre la quantité d’un gaz physiquement adsorbé sur une surface et la pression partielle du gaz à
température constante
3.5
adsorption
processus dans lequel les molécules d’un gaz ou de vapeur adhèrent par processus physique ou chimique
aux surfaces exposées des substances solides, à la fois la surface externe et la surface poreuse interne, avec
lesquelles elles viennent en contact
[SOURCE: ISO 29464:2024, 3.5.7]
3.6
percée
quantité de contaminants gazeux dans l’effluent d’un média de filtration moléculaire
Note 1 à l'article: Voir pénétration (3.31).
3.7
dérivation
proportion du flux d’air d’essai qui passe autour du dispositif de filtration moléculaire sans contact avec les
médias
[SOURCE: ISO 29464:2024, 3.1.5, modifiée – «épurateur d’air» remplacé par «dispositif de filtration
moléculaire» et «épurateur d’air» remplacé par «médias »]
3.8
capacité
m
s
quantité (masse ou moles) d’un sorbate sélectionné qui peut être contenue dans le médium du filtre d’un
dispositif de filtration moléculaire dans des conditions d’essai données, et un point terminal spécifique
Note 1 à l'article: La capacité peut également être négative pendant la désorption.
3.9
concentration d’essai
concentration du(des) contaminant(s) d’essai examinés contenus dans le flux d’air d’essai préalablement à la
filtration
[SOURCE: ISO 29464:2024, 3.5.16]
3.10
composé d’essai
composé chimique utilisé comme contaminant examiné pour tout essai donné
[SOURCE: ISO 29464:2024, 3.5.15]

ISO/FDIS 10121-2:2026(fr)
3.11
flux d’air d’essai
contaminant(s) d’essai examiné(s) dilué(s) à la (aux) concentration(s) spécifiée(s) de l’essai préalablement à
la filtration
[SOURCE: ISO 29464:2024, 3.5.14]
3.12
chimisorption
captage de contaminants sous forme de gaz ou de vapeurs sur un adsorbant, entraînant une réaction
chimique à la surface de l’adsorbant
[SOURCE: ISO 29464:2024, 3.5.19]
3.13
concentration
C
n
quantité d’une substance dispersée dans une quantité définie d’une autre
Note 1 à l'article: Les indices «n» indiquent l’emplacement.
[SOURCE: ISO 29464:2024, 3.1.11, modifiée – symbole ajouté en tant que terme admis; la Note 1 à l’article a
été ajoutée]
3.14
contaminant
substance (solide, liquide ou gazeuse) qui affecte négativement l’utilisation prévue d’un fluide
[SOURCE: ISO 29464:2024, 3.1.12]
3.15
temps de décroissance
t
Dn
temps nécessaire à l’instrument de contrôle du contaminant sous forme gazeuse pour enregistrer une
réduction par rapport à une valeur initiale de plus de 95 % de la concentration d’essai à une valeur finale
de moins de 5 % de la concentration d’essai (t – t ) au point d’échantillonnage en aval pour un essai
END VC
spécifique (n), un gaz d’essai et un débit de gaz après l’arrêt de l’injection du contaminant en l’absence de
média ou de dispositif de filtration moléculaire
[SOURCE: ISO 29464:2024, 3.5.21, modifiée – les symboles ont été ajoutés à la définition]
3.16
désorption
processus dans lequel les molécules d’adsorbat quittent la surface de l’adsorbant et pénètrent à nouveau
dans le flux d’air
Note 1 à l'article: La désorption est l’inverse de l’adsorption.
[SOURCE: ISO 29464:2024, 3.5.22]
3.17
diffuseur
dispositif qui force le flux d’air à atteindre une vitesse frontale uniforme sur toute la surface de la section
transversale d’un conduit d’essai
Note 1 à l'article: Le dispositif peut être une plaque perforée.
3.18
aval
surface ou zone dans laquelle s’écoule l’air lorsqu’il quitte un épurateur d’air
[SOURCE: ISO 29464:2024, 3.1.16]

ISO/FDIS 10121-2:2026(fr)
3.19
courbe de l’efficacité d’élimination en fonction du temps
tracé de l’efficacité d’élimination du média ou du dispositif de filtration moléculaire en fonction du temps sur
la durée d’un essai pour une concentration d’essai et un débit d’air définis
[SOURCE: ISO 29464:2024, 3.5.58, modifiée – le terme «flux» a été remplacé par «débit».]
3.20
courbe de l’efficacité d’élimination en fonction de la capacité
tracé de l’efficacité d’élimination du dispositif de filtration moléculaire en fonction de la capacité intégrée
sur la durée d’un essai pour une concentration d’essai et un débit d’air définis
[SOURCE: ISO 29464:2024, 3.5.56, modifiée – le terme «flux» a été remplacé par «débit».]
3.21
vitesse frontale
débit d’air volumique divisé par la surface nominale de l’épurateur d’air
Note 1 à l'article: La vitesse frontale de l’épurateur d’air est exprimée en m/s (ft/min).
[SOURCE: ISO 29464:2024, 3.1.20]
3.22
gaz
substance dont la pression de vapeur est plus grande que la pression ambiante à la température ambiante
[SOURCE: ISO 29464:2024, 3.1.34]
3.23
dispositif de filtration moléculaire
GPACD
assemblage de taille fixe permettant l’élimination de contaminants en phase gazeuse ou vapeur spécifiques
Note 1 à l'article: Il est usuellement sous la forme de boîte ou tient dans une boîte de dimensions comprises entre
290 mm × 290 mm × 290 mm jusqu’à approximativement 610 mm × 610 mm × 610 mm ou 2 pieds × 2 pieds × 2 pieds.
[SOURCE: ISO 29464:2024, 3.5.34]
3.24
surface d’un dispositif de filtration moléculaire
surface d’un GPACD
surface frontale du dispositif de filtration moléculaire (GPAC) y compris également un cadre de protection
ou d'autres structures supports s’il en est équipé, lorsqu’elle est observée dans la direction du flux d’air en
utilisant des dimensions exactes
[SOURCE: ISO 29464:2024, 3.5.36]
3.25
média de filtration moléculaire
GPACM
média solide ou configuration de média utilisés pour filtrer un contaminant
EXEMPLE Un film poreux ou une couche fibreuse; un adsorbant (ou chimisorbant) sous forme de billes, de
granulés ou de pastilles; une structure d’appui en tissu, en mousse ou des monolithes contenant un adsorbant sous
forme de particules de petite taille, de granules, de sphères ou de poudre; un textile tissé ou non tissé entièrement
constitué d’un matériau adsorbant.
[SOURCE: ISO 29464:2024, 3.5.37]

ISO/FDIS 10121-2:2026(fr)
3.26
efficacité d’élimination initiale
efficacité d’un filtre ou d’un dispositif de filtration moléculaire non-exposé, calculée dès que possible après
le démarrage d’un essai dans la mesure du possible
Note 1 à l'article: Pour la phase gazeuse, il convient de la calculer dès qu’une lecture stable peut être obtenue.
[SOURCE: ISO 29464:2024, 3.5.60]
3.27
contamination moléculaire
contamination présente en phase gazeuse ou vapeur dans un flux d’air et excluant les composés en phase
particulaire (solide) quelle que soit leur nature chimique
[SOURCE: ISO 29464:2024, 3.5.43]
3.28
ppb(v)
mesure de la concentration en parties par milliard en volume normalement utilisée pour enregistrer les
niveaux ambiants de la pollution extérieure
3 3
Note 1 à l'article: L’unité est le mm /m .
[SOURCE: ISO 29464:2024, 3.5.46]
3.29
ppm(v)
mesure de la concentration en parties par million en volume normalement utilisée pour enregistrer les
niveaux de pollution dans, par exemple, le cadre de la sécurité sur les lieux de travail
3 3 3
Note 1 à l'article: Les unités sont le cm /m et le ml/m .
[SOURCE: ISO 29464:2024, 3.5.47]
3.30
pénétration
P
rapport de la concentration de contaminants en aval d’un épurateur d’air sur la concentration (d’essai) en
amont
Note 1 à l'article: Parfois exprimée en pourcentage.
Note 2 à l'article: La pénétration (P) est associée à l’efficacité (E) par l’expression: E = (1 – P) × 100 %.
Note 3 à l'article: La pénétration est associée au facteur de décontamination (DF) par l’expression: DF = 1/pénétration.
[SOURCE: ISO 29464:2024, 3.1.41]
3.31
physisorption
adsorption physique
attraction d’un adsorbat à la surface, aussi bien la surface externe que la surface poreuse interne, d’un
adsorbant par des forces physiques (forces de Van der Waals)
[SOURCE: ISO 29464:2024, 3.5.48]
3.32
pore
passage infinitésimal par lesquels le fluide peut passer ou qui permet d’exposer au flux gazeux les surfaces
internes d’un média adsorbant
[SOURCE: ISO 29464:2024, 3.5.49]

ISO/FDIS 10121-2:2026(fr)
3.33
perte de charge
Δp
différence de pression entre deux points dans un système de circulation d’air dans des conditions spécifiées,
notamment lorsque mesurée aux bornes d’un dispositif de filtration moléculaire
3.34
efficacité d’élimination
E
fraction ou pourcentage d’un contaminant d’essai qui est éliminé par un épurateur d’air
[SOURCE: ISO 29464:2024, 3.1.17]
3.35
pouvoir de rétention
m
r
mesurage de l’aptitude d’un adsorbant ou d’un dispositif de filtration moléculaire à résister à la désorption
d’un adsorbat
Note 1 à l'article: Calculée comme la capacité résiduelle (fraction restante) après avoir purgé l’adsorbant uniquement
avec de l’air propre conditionné, suite à la percée d'essai.
[SOURCE: ISO 29464:2024, 3.5.63]
3.36
temps de séjour
t
r
temps au cours duquel l’expansion du fluide (ou du contaminant) se situe dans les limites du volume du
média
Note 1 à l'article: Un exemple de volume de média est une couche de granules ou une feuille non tissée.
Note 2 à l'article: Dans le cadre d’une utilisation type et du présent document, cette valeur ne tient pas compte du
fait que les médias et les structures d’appui éventuelles occupent une portion significative du volume de la couche (le
temps de séjour est calculé comme le volume total de la couche/débit d’air).
[SOURCE: ISO 29464:2024, 3.5.63]
3.37
temps de montée
t
Rn
temps entre l’injection initiale du contaminant et l’atteinte des 95 % de la concentration d’essai pour un
conduit vide (t – t ) mesuré lors de l’échantillonnage en aval
0 VO
Note 1 à l'article: Le temps de montée est spécifique à un essai, à un gaz d’essai et à un débit de gaz particuliers.
[SOURCE: ISO 29464:2024, 3.5.42]
3.38
absorbat
composés moléculaires qui sont retenus dans l’adsorbant du dispositif
Note 1 à l'article: L’absorbat peut se référer aux deux composés prévus tels que le gaz d’essai sélectionné dans un essai
ou la pollution en service réel mais également à tout autre composé présent dans le flux d’air, par exemple les gaz et les
vapeurs
[SOURCE: ISO 29464:2024, 3.5.65]

ISO/FDIS 10121-2:2026(fr)
3.39
vapeur
substance dont la pression de vapeur est inférieure à la pression ambiante à la température ambiante, mais
qui est présente dans la phase gazeuse par évaporation ou sublimation
[SOURCE: ISO 29464:2024, 3.5.71]
4 Symboles et termes abrégés
4.1 Symboles
C concentration en aval [ppb, ppm] mesurée à une position Y mm après le dispositif
D
C concentration en amont [ppb, ppm] mesurée à une position X mm avant le dispositif
U
Δp perte de charge mesurée sur le dispositif soumis à essai [Pa]
E efficacité d’élimination initiale [%] du dispositif, mesurée à une faible (<1 ppm) concentration d’essai
I
pendant l’essai d’efficacité initiale du 6.3
E efficacité d’élimination [%] du dispositif, mesurée à la concentration d’essai choisie pendant l’essai de
C
capacité du 6.4
E efficacité d’élimination enregistrée au moment de l'arrêt de l'essai ou valeur convenue entre l’utilisateur
END
et le fournisseur [%]
m pouvoir de rétention, [g], [mol]; quantité retenue par le dispositif après ventilation avec de l’air propre
r
au même débit d’air choisi pendant l’essai de capacité jusqu’à ce que C atteigne une valeur spécifiée
D
proche de zéro
m quantité intégrée en moles ou grammes de composé d’essai, accumulée au cours de l’essai d’efficacité
sEI
initiale dans la Formule (2)
m quantité intégrée en moles ou grammes de composé d’essai, accumulée au cours du mesurage en posi-
sU
tion amont dans la Formule (3)
m quantité intégrée en moles ou grammes de composé d’essai, accumulée au cours du mesurage en posi-
sD
tion aval dans la Formule (3)
m quantité totale intégrée [g], [mol] de composé d’essai, accumulée pendant tout l’essai
s
p pression en amont [Pa] mesurée à une position X mm avant le dispositif
U
p pression en aval [Pa] mesurée à une position Y mm après le dispositif
D
Q débit d’air utilisé dans l’essai (normalement le flux d’air nominal pour le dispositif soumis à essai) [m /h]
mesuré à une position Z mm après le dispositif
φ humidité relative en amont [%] mesurée à une position X mm avant le dispositif
U
φ humidité relative en aval [%] mesurée à une position Y mm après le dispositif
D
t temps de démarrage. Moment auquel C (concentration de contamination en amont) est égale à la
0 U
concentration d’essai choisie pour un conduit vide
t temps auquel un essai est interrompu. Moment auquel une concentration souhaitée ou d’autres critères
END
d’arrêt ont été satisfaits dans un des modes opératoires d’essai spécifiés (Le critères d’arrêt sont conve-
nus entre utilisateur et fournisseur)

ISO/FDIS 10121-2:2026(fr)
t temps de décroissance pour la concentration d’essai
DC
t temps de décroissance pour la concentration d’efficacité initiale
DE
t temps de montée pour la concentration d’essai
RC
t temps de montée pour une concentration d’efficacité initiale
RE
t temps noté à la fermeture de la vanne de gaz d’essai
VC
t temps noté à l’ouverture de la vanne de gaz d’essai
VO
T température en amont [°C] mesurée à une position X m avant le dispositif
U
T température en aval [°C] mesurée à une position Y mm après le dispositif
D
v vitesse frontale [m/s] calculée à partir du débit d’air et de la surface transversale du dispositif
f
X position X située suffisamment en avant du dispositif pour permettre des mesures sans perturbation,
déterminée dans la partie validation, Annexe A. À la distance X, le composé d’essai est suffisamment
mélangé et uniforme sur la section transversale du conduit, sans pour autant être trop proche du dis-
positif pour que le dispositif lui-même masque le flux d’air, la perte de charge ou la concentration.
Y position Y située suffisamment loin après le dispositif pour permettre des mesures sans perturbation,
déterminée dans la partie validation, Annexe A. À la distance Y, le composé d’essai de pénétration est
suffisamment mélangé et uniforme pour représenter la concentration moyenne après le dispositif et
sans pour autant être trop proche du dispositif pour que le dispositif lui-même masque le flux, la perte
de charge ou la concentration.
Z position Z placée suffisamment loin après le dispositif pour permettre une mesure fiable du débit d’air
en utilisant un dispositif à orifice, vérifié à l’Annexe A
4.2 Termes abrégés
ASHRAE American Society of Heating Refrigerating and Air-conditioning Engineers
ASTM ASTM International, anciennement American Society for Testing and Materials (ASTM)
GPAC filtration moléculaire
GPACD dispositif de filtration moléculaire
GPACM média de filtration moléculaire
HEPA (filtre) à air à très haute efficacité
JIS Normes industrielles japonaises
JSA Association japonaise de normalisation
MFC régulateur de débit massique
FDS Fiche de donnée de sécurité
NMP Méthyl-n-pyrrolidone-2
COV composé organique volatile

ISO/FDIS 10121-2:2026(fr)
5 Essais de GPACD
5.1 Généralités
Le présent document indique comment mesurer quatre paramètres clés qui reflètent les performances d’un
GPACD. Les quatre paramètres sont les suivants:
— perte de charge, Δp;
— capacité, m ;
s
— efficacité d’élimination, E;
— pouvoir de rétention, m .
r
Ces paramètres sont:
— liés les uns aux autres;
— différents pour différents composés d’essai (exception: Δp n’est pas affecté);
— différents pour différentes concentrations du même composé d’essai (exception: Δp n’est pas affecté);
— affectés par la présence d’autres gaz, par la température, par l’humidité et par le débit d’air.
Le cas idéal serait d’effectuer les essais aux valeurs exactes des paramètres et à la concentration présentes
dans l’application prévue, mais alors la durée d’essai serait aussi longue que la durée de vie réelle, par
exemple des années. Une façon d’accélérer l’essai est d’augmenter la concentration. Dans le présent
document, il convient qu’une augmentation de concentration fasse l’objet d’un accord entre l’utilisateur et
le fournisseur. Alternativement, pour les besoins généraux de référence trois concentrations sont utilisées,
une légèrement augmentée pour la détermination de l’efficacité d’élimination et deux fortement augmentées
pour la détermination de la capacité. Il convient également que les paramètres clés de performance, autres
facteurs importants, soient également pris en considération. Les particules peuvent être émises en aval,
au moins pendant le démarrage initial, pour les GPACD utilisant des adsorbants granulaires en vrac et en
pastilles ou des fibres d’adsorbant et éventuellement pour d’autres types de médias également. Cela peut
poser un problème en fonction de la sensibilité de l’application spécifique et de la filtration de particules
disponible après le GPACD. Les autres facteurs qui peuvent être pris en compte sont les émissions gazeuses,
la résistance à la corrosion, les exigences de poids et de profondeur.
Le présent article décrit les composants requis du banc d’essai, les paramètres requis pour la génération
du flux d’air d’essai et suggère des composés d’essai à des fins de référence et pour le cas où la polluti
...