Chimneys - Execution standard for metal chimneys - Part 1: Chimneys for non-roomsealed heating appliances

This European Standard describes the method of specifying the design criteria and the installation method for building custom built chimneys with rigid metal liners, for relining a chimney with rigid or flexible metal liners and for system chimneys with rigid metallic liners used to convey the products of combustion from heating appliances to the outside atmosphere. It also gives information on commissioning, cleaning and maintenance of an installed chimney.

Abgasanlagen - Ausführungsbestimmungen für Metallabgasanlagen - Teil 1: Abgasanlagen für raumluftabhängige Feuerstätten

Diese Europäische Norm beschreibt das Verfahren zur Festlegung der Bemessungskriterien und das Montageverfahren für System-Abgasanlagen mit starren Metallinnenrohren, die Innenrohrerneuerung einer Abgasanlage mit starren oder flexiblen Metallinnenrohren und von System-Abgasanlagen mit starren Metallinnenrohren, welche zur Ableitung von Verbrennungsprodukten von Feuerstätten an die Außenluft verwendet werden.  Sie enthält auch Angaben über die Inbetriebnahme, Reinigung und Instandhaltung einer eingebauten Abgasanlage.
Diese Norm gilt nicht für die Bemessung, den Einbau, die Inbetriebnahme, Reinigung und Instandhaltung von Abgasanlagen mit der Bezeichnung H (Abgasanlagen mit Überdruck) oder Abgasanlagen für raumluftunabhängige Feuerstätten.
Diese Norm enthält auch Festlegungen zur Begrenzung der Stütze einer Abgasanlage sowie die höchstzulässige freitragende Abgasanlagenhöhe von System- und Montage-Abgasanlagen.
Diese Europäische Norm gilt nicht für Abgasanlagen, die von Tragkonstruktionen unabhängig errichtet werden können (freistehend oder selbststützend).

Conduits de fumée - Norme de mise en oeuvre pour conduits de fumée métalliques - Partie 1: Conduits de fumée pour chaudieres non étanches

La présente Norme européenne spécifie la méthode permettant de préciser les criteres de conception ainsi que la méthode d'installation pour construire un conduit de fumée sur site au moyen de parois intérieure métallique rigide, pour tuber un conduit de fumée au moyen de parois intérieure métallique rigide ou flexible et pour les conduits de fumée simple paroi ou multiparois munis de parois intérieure métallique rigide utilisés pour évacuer les produits de combustion de l'appareil vers l'atmosphere extérieure. Elle donne aussi des informations sur la mise en service, le ramonage et l'entretien d'un conduit de fumée installé.
La présente norme ne traite pas de la conception, de l'installation, de la mise en service, du ramonage et de l'entretien des conduits de fumée portant la désignation H (conduit de fumée fonctionnant sous pression positive élevé) ou des conduits de fumée pour chaudieres étanches (ventouses).
La présente norme prescrit également des limites pour les supports de conduit de fumée et la hauteur maximale non supportée des conduits de fumée et conduits de fumée construits sur site a l'intérieur ou contre un bâtiment, et destinés a etre supportés par un mât ou une structure autre qu'un bâtiment.
Cette Norme européenne ne s'applique pas aux conduits de fumée structurellement indépendants (autoporteurs).

Dimniki – Standard za izvedbo kovinskih dimnikov – 1. del: Dimniki za ogrevalne naprave v odprtih prostorih

General Information

Status
Withdrawn
Publication Date
31-Mar-2004
Withdrawal Date
30-Nov-2010
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
20-Oct-2010
Due Date
12-Nov-2010
Completion Date
01-Dec-2010

Relations

Buy Standard

Standard
EN 12391-1:2004
English language
74 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 12391-1:2004
01-april-2004
Dimniki – Standard za izvedbo kovinskih dimnikov – 1. del: Dimniki za ogrevalne
naprave v odprtih prostorih
Chimneys - Execution standard for metal chimneys - Part 1: Chimneys for non-
roomsealed heating appliances
Abgasanlagen - Ausführungsbestimmungen für Metallabgasanlagen - Teil 1:
Abgasanlagen für raumluftabhängige Feuerstätten
Conduits de fumée - Norme de mise en oeuvre pour conduits de fumée métalliques -
Partie 1: Conduits de fumée pour chaudieres non étanches
Ta slovenski standard je istoveten z: EN 12391-1:2003
ICS:
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
SIST EN 12391-1:2004 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 12391-1:2004

---------------------- Page: 2 ----------------------

SIST EN 12391-1:2004
EUROPEAN STANDARD
EN 12391-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
December 2003
ICS 91.060.40
English version
Chimneys - Execution standard for metal chimneys - Part 1:
Chimneys for non-roomsealed heating appliances
Conduits de fumée - Norme de mise en oeuvre pour Abgasanlagen - Ausführungsbestimmungen für
conduits de fumée métalliques - Partie 1: Conduits de Metallabgasanlagen - Teil 1: Abgasanlagen für
fumée pour chaudières non étanches raumluftabhängige Feuerstätten
This European Standard was approved by CEN on 3 November 2003.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2003 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12391-1:2003 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
Contents
page
Foreword.5
1 Scope .6
2 Normative references .6
3 Terms and definitions.7
4 Design criteria .13
4.1 Data requirements .13
4.1.1 Sources of data and information.13
4.1.2 Heating appliance information .13
4.1.3 Building construction and chimney route information.14
4.1.4 Local conditions.17
4.1.5 Combustion air supply.17
4.1.6 Chimney product specification .17
4.2 Design requirements .17
4.2.1 General.17
4.2.2 Designation.17
4.2.3 Determination of designation of the chimney and connecting flue pipe.18
4.2.4 Materials of construction .18
4.2.5 Flue size.20
4.2.6 Chimney route.20
5 Installation .28
5.1 General.28
5.2 Construction.28
5.2.1 System chimney.28
5.2.2 Relined chimney.29
5.2.3 Custom-built-chimney.29
5.3 Chimney plate.30
6 Commissioning .31
7 Inspection, cleaning and maintenance.32
7.1 General.32
7.2 Inspection and cleaning .32
7.3 Maintenance .33
Annex A (informative)  Example of a metal chimney plate .34
A.1 Example of a metal system chimney plate.34
A.2 Example of relined metal chimney plate .35
A.3 Example of a custom-built chimney plate .36
Annex B (informative)  Example for the determination of the designation of a relined chimney .37
B.1 Input data for a typical relined chimney .37
B.1.1 Existing chimney.37
B.1.2 Relining.37
B.1.3 Insulation .37
B.2 Temperature class designation.38
B.2.1 General.38
B.2.2 Material characteristic .38
B.2.3 Resistance to fire .38
B.2.4 Human contact .39
B.2.5 Determination of temperature class .40
B.3 Pressure class designation .40
B.4 Resistance to condensate class designation .40
2

---------------------- Page: 4 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
B.5 Corrosion resistance class designation.40
B.6 Soot fire resistance class and distance to combustible material designation .40
B.7 Designation of the relined chimney.40
B.8 Example of chimney plate of the relined chimney in this Example.41
Annex C (informative)  Example of metal chimney product designation.42
Annex D (normative)  Determination of the chimney designation for an installed system chimney.43
D.1 General.43
D.2 Temperature class .43
D.3 Pressure class.43
D.4 Resistance to condensate class .43
D.5 Corrosion resistance class.43
D.6 Soot fire resistance class and distance to combustible material.43
Annex E (normative)  Determination of the chimney designation for relined of custom-built chimneys .44
E.1 General.44
E.2 Temperature class .44
E.3 Pressure class.47
E.4 Resistance to condensate class .47
E.5 Corrosion resistance class.47
E.6 Soot fire resistance class and distance to combustible material.48
Annex F (informative)  Material characteristics .49
Annex G (informative)  Location of the chimney outlet.54
Annex H (informative)  Method for calculating the temperature of adjacent materials .56
H.1 Example for calculation the temperature of adjacent materials .57
Annex I (informative)  Checking, handling and site storage of materials and components .59
I.1 General.59
I.2 Checking, handling and site storage of materials and components.59
I.2.1 Checking on delivery of materials .59
I.2.2 Checking before installation.59
I.2.3 Check of existing chimney.59
I.2.4 Site handling and storage.59
I.2.5 Coordination of work.60
Annex J (informative)  Chimney commissioning test procedure.61
J.1 General.61
J.2 Flue flow test.61
J.3 Smoke test.61
J.4 Pressure test .62
Annex K (informative)  Example for the determination of the designation of a custom-built chimney .63
K.1 Input data for a typical custom-built chimney .63
K.1.1 Liner .63
K.1.2 Insulation .63
K.1.3 Enclosure.63
K.2 Temperature class designation.63
K.2.1 General.63
K.2.2 Material characteristic.63
K.2.3 Resistance to fire.64
K.2.4 Human contact.65
K.2.5 Determination of temperature class .65
K.3 Pressure class designation .65
K.4 Resistance to condensate class designation .65
K.5 Corrosion resistance class designation.65
K.6 Soot fire resistance class and distance to combustible material designation .65
K.7 Designation of the custom-built chimney .66
K.8 Example of chimney plate of the custom-built chimney in this Example.66
Annex L (informative)  Example of chimney designation.67
3

---------------------- Page: 5 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
Annex M (informative)  Correlation between liner material specification and corrosion load in Member
States .68
Bibliography .74
4

---------------------- Page: 6 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
Foreword
This document (EN 12391-1:2003) has been prepared by Technical Committee CEN/TC 166 "Chimneys", the
secretariat of which is held by UNI.
This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by June 2004, and conflicting national standards shall be withdrawn at the latest by
June 2004.
This European Standard is one of a series of standards as listed below.
Chimneys – Execution standard for metal chimneys – Part 1: Chimneys for non-roomsealed heating appliances.
Chimneys – Execution standard for metal chimneys – Part 2: Chimneys for roomsealed heating appliances.
The annexes A, B, C, F, G, H, I, J, K, L and M are informative, the annexes D and E are normative.
This document includes a bibliography.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal,
Slovakia, Spain, Sweden, Switzerland and the United Kingdom.
5

---------------------- Page: 7 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
1 Scope
This European Standard specifies the method of specifying the design criteria and the installation method for
building custom-built chimneys with rigid metal liners, for relining a chimney with rigid or flexible metal liners and for
single wall system chimneys or multi-wall system chimneys with rigid metallic liners, used to convey the products of
combustion from heating appliances to the outside atmosphere. It also gives information on commissioning,
cleaning and maintenance of an installed chimney.
This standard does not cover the design, installation, commissioning, cleaning and maintenance of chimneys
designated H (high positive pressure chimney) and chimneys for roomsealed appliances.
This standard also specifies limitations for supporting a chimney, and the maximum unsupported chimney height
for system chimneys and custom-built chimneys within or against a building, and for supporting by a mast or other
structures than a building.
This European Standard does not apply to structurally independent (free-standing or self-supporting) chimneys.
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other publications. These
normative references are cited at the appropriate places in the text, and the publications are listed hereafter. For
dated references, subsequent amendments to or revisions of any of these publications apply to this European
Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the
publication referred to applies (including amendments).
EN 1443, Chimneys – General requirements.
EN 1806, Chimneys – Clay/ceramic flue blocks for single wall chimneys - Requirements and test methods.
EN 1856-1, Chimneys – Requirements for metal chimneys – Part 1: System chimney products.
prEN 1856-2, Chimneys – Requirements for metal chimneys – Part 2: Metal liners and connecting flue pipes.
EN 1858, Chimneys – Components – Concrete flue blocks.
EN 1859, Chimneys – Metal chimneys – Test methods.
EN 13084-1, Free-standing industrial chimneys – Part 1: General requirements.
ENV 1993-3-2, Eurocode 3: Design of steel structures – Part 3-2: Towers, masts and chimneys – Chimneys.
EN 12446, Chimneys – Components – Concrete outer wall elements.
prEN 13069, Chimneys – Clay/ceramic outer walls for system chimneys – Requirements and test methods.
EN 13384-1, Chimneys – Thermal and fluid dynamic calculation methods – Part 1: Chimneys serving one
appliance.
EN 13501-2:2003, Fire classification of construction products and building elements – Part 2: Classification using
data from fire resistance tests, excluding ventilation services.
EN 61024-1-2, Protection of structures against lightning – Part 1-2: General principles – Guide B – Design,
installation, maintenance and inspection of lightning protection systems (IEC 61024-1-2:1998).
6

---------------------- Page: 8 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
3 Terms and definitions
For the purposes of this European Standard, the terms and definitions given in EN 1443, EN 1856-1, prEN1856-2
and EN 1859 together with the following apply.
Examples of chimney construction identifying individual component terminology and definitions are given in Figures
1, 2 and 3.
3.1
heating appliance adapter
component which connects the connecting flue pipe or the chimney to a heating appliance
3.2
chimney adapter
component which connects a chimney to a connecting flue pipe or an heating appliance
3.3
fire compartment
part of the building being isolated to provide resistance to fire
3.4
flashing
component or site fabricated materials used for weatherproofing the penetration of the roof by the chimney
3.5
storm collar
component attached and sealed to the outer wall of the chimney immediately above the flashing in order to prevent
the entry of rain into the building
3.6
fire stop
component intended to provide resistance to fire spread between rooms or compartments
3.7
fire stop spacer
component intended to locate a chimney at the correct distance from combustible material, when penetrating a wall
or a floor, which separates compartments, and to provide resistance to the spread of fire between rooms or fire
compartments
3.8
sleeve
component which provides an aperture through a wall, ceiling or floor through which the chimney passes
3.9
back ventilation
ventilation in the space between flue liner and the outer wall of the chimney or an enclosure
3.10
draught regulator
balanced hinged flap in a flue opening to allow airflow into the chimney to control draught at the boiler outlet
3.11
ventilating air flap
automatically operated flap used to introduce ventilation air for the purpose of drying the chimney
NOTE This can be a draught regulator.
3.12
damper
device used to close or partially close the flue
7

---------------------- Page: 9 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
3.13
explosion relief
device that protects the chimney against overpressure arising from deflagration or explosion in the flue
3.14
expansion component
component used to accommodate thermal movement
3.15
silencer
component installed to provide noise attenuation
3.16
access component
component installed in the chimney or in the connecting flue pipe to provide access to the flue for the purpose of
inspection or cleaning
3.17
test point
component that provides access for gas sampling and measuring
3.18
closure component
any component used to shut off an opening in the chimney, e.g. base plug, tee piece plug
3.19
common header
horizontal or inclined common connecting flue pipe to which more than one heating appliance is connected
3.20
condensate drain
component to facilitate the disposal of condensate
3.21
rigid liner
straight metal liner that cannot bend without permanent deformation
3.22
rain cap
part of the chimney that protects against the entry of rain. This may be a part of a terminal
3.23
rain seal
part of the chimney that stops the entry of rain into the insulation space
3.24
centralising spacer
component to centralise the liner
3.25
T-piece
chimney fitting which allows an appliance, connecting flue pipe or accessory to be connected to the chimney flue at
an angle
3.26
elbow
chimney fitting which provides a change of direction of the flue
3.27
infill insulation
insulation which is poured into the gap between the liner and the outer wall of the chimney
8

---------------------- Page: 10 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
3.28
preformed insulation
insulation prefabricated to fit the insulation space
3.29
air gap insulation
closed air space between the liner and the outer wall
3.30
flexible liner
metal tube having a single or multi-skin construction that is able to bend in any direction without permanent
deformation
3.31
back ventilation air inlet
opening in the outer wall of a chimney used for the intake of room air for back ventilation
3.32
back ventilation air outlet
opening in the outer wall of a chimney or at the top of the chimney to exhaust the back ventilation air
3.33
seal
device that joins two elements in such a way as to prevent leakage
3.34
sealant
material which, applied in an unformed state to a joint, seals it by adhering to appropriate surfaces within the joint
9

---------------------- Page: 11 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
a.) double wall insulated metal chimney in a solid block shaft
b.) internal or external insulated metal chimney without enclosure
c.) double wall insulated metal chimney in a cavity block
d.) double wall insulated metal chimney in an enclosure as a part of the building structure
e.) double wall insulated metal chimney in a specified material
Figure 1 — Terminology for a system chimney
10

---------------------- Page: 12 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
Figure 2 — Terminology for a relined chimney
11

---------------------- Page: 13 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
a.) double wall insulated metal chimney in a solid block shaft
b.) internal or external insulated metal chimney without enclosure
c.) double wall insulated metal chimney in a cavity block
d.) double wall insulated metal chimney in an enclosure as a part of the building structure
e.) double wall insulated metal chimney in a specified material
Figure 3 — Technology for a custom-built chimney
12

---------------------- Page: 14 ----------------------

SIST EN 12391-1:2004
EN 12391-1:2003 (E)
4 Design criteria
4.1 Data requirements
4.1.1 Sources of data and information
The data and information specified in 4.1.2 to 4.1.6 shall be obtained and documented as appropriate.
NOTE The sources may be:
- heating appliance manufacturers catalogues and literature;
- chimney manufacturers literature including installation instructions;
- architects drawings or plans and/or site surveys;
- annex A of this document;
- local building rules.
A possible source of typical or average data is EN 13384-1.
4.1.2 Heating appliance information
The following information for the heating appliance(s) shall be obtained from the documentation of the heating
appliance manufacturer or if not available the source of the data shall be documented in the design:
For selecting the chimney type (required designation):
kind/type of appliance/burner;
kind of fuel;
maximum (nominal) flue gas temperature;
maximum allowable condensate back flow rate (from the chimney).
For calculation (sizing):
kind/type of appliance/burner;
kind of fuel;
minimum and maximum flue gas mass flow (or burning rate
...

Questions, Comments and Discussion