kSIST FprEN 16941-1:2023
(Main)On-site non-potable water systems - Part 1: Systems for the use of rainwater
On-site non-potable water systems - Part 1: Systems for the use of rainwater
This European Standard specifies the requirements and gives recommendations for the design, sizing, installation, identification, commissioning and maintenance of rainwater harvesting systems for the use of rainwater on-site as non-potable water. This European Standard also specifies the minimum requirements for these systems.
Excluded from the scope of this European Standard are:
- the use as drinking water and for food preparation;
- the use for personal hygiene purposes;
- decentralized attenuation;
- infiltration.
NOTE Conformity with the standard does not exempt from compliance with the obligations arising from local or national regulations.
Vor-Ort-Anlagen für Nicht-Trinkwasser - Teil 1: Anlagen für die Verwendung von Regenwasser
Dieses Dokument legt Anforderungen fest und enthält Empfehlungen für Planung, Bemessung, Einbau, Kennzeichnung, Inbetriebnahme und Wartung von Regenwassernutzungsanlagen zur Verwendung von Regenwasser als Nicht Trinkwasser vor Ort. Dieses Dokument legt auch die Mindestanforderungen an solche Systeme fest.
Vom Anwendungsbereich dieses Dokuments ausgenommen sind
die Verwendung als Trinkwasser und zur Herstellung von Speisen,
die Verwendung für die Körperhygiene,
Rückhaltung und
Versickerung.
ANMERKUNG Konformität mit diesem Dokument entbindet nicht von der Einhaltung der Auflagen, die sich aus örtlichen oder nationalen Vorschriften ergeben können.
Réseaux d’eau non potable sur site - Partie 1 : Systèmes pour l’utilisation de l’eau de pluie
Le présent document spécifie les exigences et fournit des recommandations concernant la conception, le dimensionnement, l’installation, l’identification, la mise en service et l’entretien des systèmes de récupération de l’eau de pluie pour son utilisation sur site en tant qu’eau non potable. Le présent document spécifie également les exigences minimales relatives à ces systèmes.
Sont exclus du domaine d’application du présent document :
- l’utilisation comme eau potable et pour la préparation des aliments ;
- l’utilisation pour l’hygiène personnelle ;
- la rétention et la régulation à débit contrôlé ; et
- l’infiltration.
NOTE La conformité au présent document ne dispense pas de se conformer aux obligations découlant des réglementations nationales ou locales.
Sistemi za vodo, ki ni namenjena pitju, nameščeni na terenu - 1. del: Sistemi za uporabo deževnice
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN 16941-1:2022
01-oktober-2022
Sistemi za vodo, ki ni namenjena pitju, nameščeni na terenu - 1. del: Sistemi za
uporabo deževnice
On-site non-potable water systems - Part 1: Systems for the use of rainwater
Vor-Ort-Anlagen für Nicht-Trinkwasser - Teil 1: Anlagen für die Verwendung von
Regenwasser
Réseaux d’eau non potable sur site - Partie 1 : Systèmes pour l’utilisation de l’eau de
pluie
Ta slovenski standard je istoveten z: prEN 16941-1
ICS:
93.025 Zunanji sistemi za prevajanje External water conveyance
vode systems
oSIST prEN 16941-1:2022 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
oSIST prEN 16941-1:2022
---------------------- Page: 2 ----------------------
oSIST prEN 16941-1:2022
DRAFT
EUROPEAN STANDARD
prEN 16941-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
August 2022
ICS 93.025 Will supersede EN 16941-1:2018
English Version
On-site non-potable water systems - Part 1: Systems for
the use of rainwater
Réseaux d'eau non potable sur site - Partie 1 : Systèmes Vor-Ort-Anlagen für Nicht-Trinkwasser - Teil 1:
pour l'utilisation de l'eau de pluie Anlagen für die Verwendung von Regenwasser
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 165.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16941-1:2022 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 16941-1:2022
prEN 16941-1:2022 (E)
Contents
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 Functional elements of rainwater harvesting systems . 8
5 Design . 8
5.1 Collection . 8
5.1.1 General. 8
5.1.2 Collection surfaces . 9
5.1.3 Collection piping system .
...