Fire-fighting hoses - Semi-rigid hoses for fixed systems

This European standard specifies the requirements and the tests methods for semi-rigid reel hoses for fire fighting purposes for use with fixed systems. The hoses are intended for use at a maximum working pressure of 1,2 MPa for hoses of 19 mm and 25 mm inside diameter and 0,7 MPa for hoses of 33 mm inside diameter. Hoses conforming to this standard are intended for applications where long intervals can occur between the occasions of use, for example on fixed fire hose reels in buildings and other construction works.

Feuerlöschschläuche - Formstabile Schläuche für Wandhydranten

Anwendungsbereich
In dieser Europäischen Norm werden die Anforderungen und Prüfverfahren für formstabile Haspel-schläuche,
die an Wandhydranten angeschlossen sind und zu Feuerlöschzwecken eingesetzt werden,
festgelegt. Schläuche mit einem Innendurchmesser von 19 mm und 25 mm sind für einen maximalen
Arbeitsdruck von 1,2 MPa, Schläuche mit einem Innendurchmesser von 33 mm für einen maximalen
Arbeitsdruck von 0,7 MPa vorgesehen.
Schläuche, die die Anforderungen dieser Norm erfüllen, sind für Verwendungen vorgesehen, bei denen
lange Zeiträume zwischen den einzelnen Gebrauchsfällen liegen können, z. B. auf fest installierten
Schlauchhaspeln in Gebäuden oder anderen baulichen Anlagen.
Die Norm gilt ausschließlich für Feuerlöschschläuche zur Brandbekämpfung, die für einen Einsatz bei
Umgebungsbedingungen in nicht-aggressiven und nicht-korrosiven Atmosphären innerhalb des
Temperaturbereichs von -20 °C bis +60 °C vorgesehen sind.
ANMERKUNG 1 Schläuche für die Verwendung bei Temperaturen unter -20 °C dürfen auf Kundenanfrage geliefert
werden.
ANMERKUNG 2 Sämtliche Drücke werden in Megapascal angegeben. 1 MPa = 10 bar.

Tuyaux de lutte contre l'incendie - Tuyaux semi-rigides pour systemes fixes

1 Domaine d'application
La présente Norme européenne spécifie les exigences et méthodes d'essai s'appliquant aux tuyaux semi-rigides de lutte contre l'incendie prévus pour des systemes fixes. Les tuyaux sont prévus pour etre utilisés sous une pression maximale de service de 1,2 MPa pour les diametres intérieurs 19 mm et 25 mm et de 0,7 MPa pour le diametre intérieur 33 mm.
Les tuyaux conformes a la présente norme sont destinés a des applications ou il peut s'écouler de longues périodes entre deux utilisations, par exemple sur robinets d'incendie armés dans les bâtiments et autres constructions.
La présente Norme concerne uniquement les tuyaux de lutte contre l'incendie prévus pour etre utilisés dans les conditions ambiantes - atmospheres agressives ou corrosives exclues - dans une plage de température comprise entre - 20 °C et + 60 °C.
NOTE 1   Des tuyaux pour utilisation a des température inférieure a - 20 °C peuvent etre fournis sur demande de l'acheteur.
NOTE 2   Toutes les pressions sont exprimées en mégapascals : 1 MPa = 10 bars.

Gasilske cevi - Poltoge cevi za vgrajene sisteme

General Information

Status
Withdrawn
Publication Date
31-May-2002
Withdrawal Date
02-Jul-2007
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
02-Jul-2007
Due Date
25-Jul-2007
Completion Date
03-Jul-2007

Relations

Buy Standard

Standard
EN 694:2002
English language
20 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Fire-fighting hoses - Semi-rigid hoses for fixed systemsGasilske cevi - Poltoge cevi za vgrajene sistemeTuyaux de lutte contre l'incendie - Tuyaux semi-rigides pour systemes fixesFeuerlöschschläuche - Formstabile Schläuche für WandhydrantenTa slovenski standard je istoveten z:EN 694:2001SIST EN 694:2002en23.040.70Gumene cevi in armatureHoses and hose assemblies13.220.10Gašenje požaraFire-fightingICS:SLOVENSKI
STANDARDSIST EN 694:200201-junij-2002







EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 694May 2001ICS 13.220.10English versionFire-fighting hoses - Semi-rigid hoses for fixed systemsTuyaux de lutte contre l'incendie - Tuyaux semi-rigides poursystèmes fixesFeuerwehrschläuche - Formstabile Schläuche fürWandhydrantenThis European Standard was approved by CEN on 31 August 2000.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2001 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 694:2001 E



Page 2EN 694:2001ContentsForeword.3Introduction.41Scope.52Normative references.53Definitions.64Classification.64.1General.64.2Classification by types (hose construction).64.3Classification by class (materials for lining and cover).65Dimensions, tolerances and maximum mass.75.1Inside diameter and maximum mass.75.2Length and tolerances on length.76Performance requirements of finished hose.76.1Hydrostatic requirements.76.1.1Deformation under maximum working pressure.76.1.2Deformation under proof pressure.86.1.3Minimum burst pressure.86.1.4Kink pressure.86.2Adhesion.96.3Accelerated ageing.96.4Low temperature flexibility.96.5Hot surface resistance.96.6Ozone resistance.96.7Bending and crush resistance.96.8UV-resistance (xenon arc lamp).96.9Loss in mass on heating.107Marking.10Annex A (normative)
Kink pressure test.11Annex B (normative)
Accelerated ageing test.12Annex C (normative)
Hot surface resistance test.13Annex D (normative)
Bending and crush resistance test.17Annex E (informative)
Recommended minimum frequencies of testing.19Bibliography.20



Page 3EN 694:2001ForewordThis European Standard has been prepared by Technical Committee CEN/TC 192 "Fire serviceequipment", the secretariat of which is held by BSI.This European Standard shall be given the status of a national standard, either by publication of anidentical text or by endorsement, at the latest by November 2001, and conflicting national standardsshall be withdrawn at the latest by November 2001.The standard is based on recommendations from CEN/TC 191 “Fixed fire-fighting systems” andshould be read in conjunction with EN 671-1.At present there is no existing ISO Standard on the same subject but ISO 4642:1978 “Rubberproducts - Hoses, non-collapsible, for fire-fighting service” is under revision by ISO/TC 45.Requirements for semi-rigid hoses for use with fire-fighting pumps and vehicles are given in EN 1947;those for non-percolating layflat hoses are given in EN 1924-1 (pumps and vehicles) and EN 1924-2(fixed systems).Recommendations on the frequency at which tests specified in this standard should be carried out aregiven in annex E.Users of this European Standard are advised to consider the desirability of independent certificationof product conformity with this European Standard based on testing and continuing surveillance,which may be coupled with assessment of a supplier’s quality system against EN ISO 9001.According to the CEN/CENELEC Internal Regulations, the national standards organizations of thefollowing countries are bound to implement this European Standard: Austria, Belgium, CzechRepublic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg,Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.



Page 4EN 694:2001IntroductionA fixed system is a manually operated unit installed in a building in order to make it possible for theoccupants to control and extinguish a small fire. The system consists of fixed units mounted on wallsor in cabinets permanently connected to a water supply. The fixed units are composed of a coupling,a valve, a semi-rigid water filled hose with its support and a nozzle.



Page 5EN 694:20011 ScopeThis European Standard specifies the requirements and test methods for semi-rigid reel hoses for fire-fighting purposes for use with fixed systems. The hoses are intended for use at a maximum workingpressure of 1,2 MPa for hoses of 19 mm and 25 mm inside diameter and 0,7 MPa for hoses of 33 mminside diameter.Hoses conforming to this standard are intended for applications where long intervals can occurbetween the occasions of use, for example on fixed fire hose reels in buildings and other constructionworks.The standard applies exclusively to hoses for fire-fighting purposes intended for use at ambientconditions in non-aggressive or non-corrosive atmospheres within the temperature range -20 °C to+60 °C.NOTE 1Hoses for use at temperatures lower than -20 °C may be supplied at the request of the purchaser.NOTE 2All pressures are expressed in megapascals. 1 MPa = 10 bar.2 Normative referencesThis European Standard incorporates by dated or undated reference, provisions from otherpublications. These normative references are cited at the appropriate places in the text and thepublications are listed hereafter. For dated references, subsequent amendments to or revisions of anyof these publications apply to this European Standard only when incorporated in it by amendment orrevision. For undated references, the latest edition of the publication referred to applies (includingamendments).EN 24672:1993, Rubber and plastics hoses - Sub-ambiant temperature flexibility tests(ISO 4672:1988)EN 27326:1993, Rubber and plastics hoses - Assessment of ozone resistance under static conditions(ISO 7326:1991)EN 28033, Rubber and plastics hose - Determination of adhesion between components(ISO 8033:1991)EN ISO 1307, Rubber and plastics hoses for general-purpose industrial applications - Bore diametersand tolerances, and tolerances on length (ISO 1307:1992)EN ISO 1402, Rubber and plastics hoses and hose assemblies - Hydrostatic testing (ISO 1402:1994)ISO 176:1976, Plastics - Determination of loss of plasticizers - Activated carbon methodISO 188, Rubber, vulcanized or thermoplastic - Accelerated ageing and heat-resistance testsISO 4671:1984, Rubber and plastics hose and hose assemblies - Methods of measurement ofdimensionsISO 8330:1998, Rubber and plastics hoses and hose assemblies - Vocabulary



Page 6EN 694:20013 DefinitionsFor the purposes of this standard the following definition applies, together with those for workingpressure, proof pressure and burst pressure given in ISO 8330:1998.3.1semi-rigid hosehose which maintains its round cross-section even when unpressurized4 Classification4.1 GeneralAll types and classes of hoses shall be so flexible that they can be rolled and kept on a drum ofminimum diameter 200 mm for 19 mm and 25 mm inside diameter hose and of minimum diameter280 mm for 33 mm inside diameter hose.Hoses shall be one of two types distinguished by their construction. Each hose type shall be furtherdivided into classes distinguished by the materials used for lining and cover.4.2 Classification by types (hose construction)Type A hoses shall consist of:a) a seamless rubber or plastics lining;b) a textile reinforcement with or without a rigid spiral helix;c) a rubber or plastics cover.Type B hoses shall consist of:a) a seamless rubber or plastics lining;b) a circular woven textile reinforcement with a rigid spiral helix;c) an uncovered or rubber or plastics cover.4.3 Classification by class (materials for lining and cover)The hose types shall be further subdivided into six classes dependent on the materials used in theconstruction in accordance with Table 1.



Page 7EN 694:2001Table 1 — Classes and materialsClassLining materialCover material1rubberrubber2plasticsplastics3rubberplastics4plasticsrubber5rubberno cover6plasticsno cover5 Dimensions, tolerances and maximum mass5.1 Inside diameter and maximum massThe inside diameter of the hose, when measured in accordance with ISO 4671, shall conform to therequirements given in Table 2. The mass per metre length of the hose shall be in accordance withTable 2.Table 2 — Inside diameter, tolerances on inside diameter and maximum mass per unit lengthInside diameterTolerances for insidediameterMass per unit lengthmmmmkg/mType AType Bmax.max.19-0,5 to +1,00,750,2525±1,00,900,3533-1,0 to +1,51,000,505.2 Length a
...

Questions, Comments and Discussion