Electrical accessories - Circuit-breakers for overcurrent protection for household and similar installations - Part 1: Circuit-breakers for a.c. operation (IEC 60898-1:2015/AMD1:2019)

This part of IEC 60898 applies to a.c. air-break circuit-breakers for operation at 50 Hz, 60 Hz or 50/60 Hz, having a rated voltage not exceeding 440 V (between phases), a rated current not exceeding 125 A and a rated short-circuit capacity not exceeding 25 000 A.

Elektrisches Installationsmaterial - Leitungsschutzschalter für Hausinstallationen und ähnliche Zwecke - Teil 1: Leitungsschutzschalter für Wechselstrom (AC)

Petit appareillage électrique - Disjoncteurs pour la protection contre les surintensités pour installations domestiques et analogues - Partie 1: Disjoncteurs pour le fonctionnement en courant alternatif

Le contenu du corrigendum de mars 2020 a été pris en considération dans cet exemplaire.

Električni pribor - Odklopniki za nadtokovno zaščito za gospodinjske in podobne inštalacije - 1. del: Odklopniki za izmenični tok (IEC 60898-1:2015/AMD1:2019)

General Information

Status
Not Published
Public Enquiry End Date
29-Sep-2022
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
16-Jul-2024
Due Date
20-Sep-2024

Relations

Buy Standard

Draft
EN 60898-1:2019/oprA1:2022
English language
30 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
SIST EN 60898-1:2019/oprA1:2022
01-september-2022
Električni pribor - Odklopniki za nadtokovno zaščito za gospodinjske in podobne
inštalacije - 1. del: Odklopniki za izmenični tok (IEC 60898-1:2015/AMD1:2019)
Electrical accessories - Circuit-breakers for overcurrent protection for household and
similar installations - Part 1: Circuit-breakers for a.c. operation (IEC 60898-
1:2015/AMD1:2019)
Elektrisches Installationsmaterial - Leitungsschutzschalter für Hausinstallationen und
ähnliche Zwecke - Teil 1: Leitungsschutzschalter für Wechselstrom (AC)
Petit appareillage électrique - Disjoncteurs pour la protection contre les surintensités
pour installations domestiques et analogues - Partie 1: Disjoncteurs pour le
fonctionnement en courant alternatif
Ta slovenski standard je istoveten z: EN 60898-1:2019/prA1
ICS:
29.120.50 Varovalke in druga Fuses and other overcurrent
nadtokovna zaščita protection devices
SIST EN 60898-1:2019/oprA1:2022 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

SIST EN 60898-1:2019/oprA1:2022

SIST EN 60898-1:2019/oprA1:2022

EUROPEAN STANDARD DRAFT
EN 60898-1:2019
NORME EUROPÉENNE
EUROPÄISCHE NORM
prA1
July 2022
ICS 29.120.50 -
English Version
Electrical accessories - Circuit-breakers for overcurrent
protection for household and similar installations - Part 1:
Circuit-breakers for a.c. operation
(IEC 60898-1:2015/AMD1:2019)
Petit appareillage électrique - Disjoncteurs pour la Elektrisches Installationsmaterial - Leitungsschutzschalter
protection contre les surintensités pour installations für Hausinstallationen und ähnliche Zwecke - Teil 1:
domestiques et analogues - Partie 1: Disjoncteurs pour le Leitungsschutzschalter für Wechselstrom (AC)
fonctionnement en courant alternatif (IEC 60898-1:2015/AMD1:2019)
(IEC 60898-1:2015/AMD1:2019)
This draft amendment prA1, if approved, will modify the European Standard EN 60898-1:2019; it is submitted to CENELEC members for
enquiry.
Deadline for CENELEC: 2022-09-30.

The text of this draft consists of the text of IEC 60898-1:2015/AMD1:2019.

If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

This draft amendment was established by CENELEC in three official versions (English, French, German).
A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to
the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Project: 75781 Ref. No. EN 60898-1:2019/prA1 E

SIST EN 60898-1:2019/oprA1:2022
EN 60898-1:2019/prA1:2022 (E)
European foreword
This document (EN 60898-1:2019/prA1:2022) consists of the text of document
IEC 60898-1:2015/AMD1:2019, prepared by IEC/SC 23E, “Circuitbreakers and similar equipment for
household use”, of IEC/TC 23 " Electrical accessories".
This document is currently submitted to the Enquiry.
The following dates are proposed:
• latest date by which the existence of this document (doa) dor + 6 months
has to be announced at national level
• latest date by which this document has to be (dop) dor + 12 months
implemented at national level by publication of an
identical national standard or by endorsement
• latest date by which the national standards (dow) dor + 36 months
conflicting with this document have to be withdrawn (to be confirmed or
modified when voting)
This document has been prepared under a Standardization Request given to CENELEC by the
European Commission and the European Free Trade Association, and supports essential requirements
of EU Directive(s) / Regulation(s).
For relationship with EU Directive(s) / Regulation(s), see informative Annex ZZ, which is an integral part
of EN 60898-1:2019/prAA:2022.
SIST EN 60898-1:2019/oprA1:2022

IEC 60898-1 ®
Edition 2.0 2019-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
A MENDMENT 1
AM ENDEMENT 1
Electrical accessories – Circuit-breakers for overcurrent protection

for household and similar installations –

Part 1: Circuit-breakers for a.c. operation

Petit appareillage électrique – Disjoncteurs pour la protection

contre les surintensités pour installations domestiques et analogues –

Partie 1: Disjoncteurs pour le fonctionnement en courant alternatif

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.120.50 ISBN 978-2-8322-7634-1

SIST EN 60898-1:2019/oprA1:2022
– 2 – IEC 60898-1:2015/AMD1:2019
© IEC 2019
FOREWORD
This amendment has been prepared by subcommittee 23E: Circuit-breakers and similar
equipment for household use, of IEC technical committee 23: Electrical accessories.
The text of this amendment is based on the following documents:
FDIS Report on voting
23E/1156/FDIS 23E/1157/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC website under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
___________
FOREWORD
Add the following paragraph after the sentence "This publication has been drafted in
accordance with the ISO/IEC Directives, Part 2":
The following differing practices of a less permanent nature exist in the countries indicated
below.
– Annex J, Clause J.1: Upper limit of current for use of screwless terminals is 16 A (CZ, DK,
NL and CH; upper limit of current for use of screwless terminals is 30 A (Japan).
– J.3.3: Only universal screwless-type terminals are accepted (AT, BE, CN, DK, DE, ES, FR,
IT, PT, SE and CH).
1 Scope
Replace in the third paragraph "for not being maintained" with "do not require maintenance".
Add, at the end of the fourth paragraph, after "pollution degree 2", the following text "and
overvoltage category III".
Add, after the second paragraph, the following note:
NOTE 1 Additional requirements are necessary for circuit-breakers used in locations having more severe
overvoltage conditions.
SIST EN 60898-1:2019/oprA1:2022
IEC 60898-1:2015/AMD1:2019 – 3 –
© IEC 2019
Add, after the fourth paragraph, the following text:
For an environment with a higher pollution degree, enclosures giving the appropriate degree
of protection are used.
Add, after the tenth paragraph, the following text:
This document does not apply to circuit-breakers for DC operation that are covered by
IEC 60898-3.
Delete paragraph 13: "For an environment […] should be used.".
Renumber the existing note in paragraph 14 "NOTE 2".
2 Normative references
Add the following reference to Clause 2:
IEC 60664-3, Insulation coordination for equipment within low-voltage systems – Part 3: Use
of coating, potting or moulding for protection against pollution
3 Terms and definitions
3.2.13
Replace "operation sequence" by "operating sequence".
Insert the following new terms and definitions:
3.2.15
type test
test of one or more devices made to a certain design to show that the design meets certain
requirements
[SOURCE: IEC 60050-411:1996, 411-53-01, modified – "machines" and "specifications" have
been replaced by "devices" and "requirements", respectively.]
3.2.16
routine test
test to which each individual device is subjected during or after manufacture to ascertain
whether it complies with certain criteria
[SOURCE: IEC 60050-411:1996, 411-53-02, modified – "machine" has been replaced with
"device".]
3.5.14.2
Replace the source text by the following:
[SOURCE: IEC 60947-2:2016, 2.17.1, modified – "in series" has been added.]
3.5.16
Replace, in the definition, "to trip" by "to operate".

SIST EN 60898-1:2019/oprA1:2022
– 4 – IEC 60898-1:2015/AMD1:2019
© IEC 2019
5.1 List of characteristics
Replace list items:
– range of instantaneous tripping current (see 4.5 and 5.3.5);
– I²t classification (see 4.6).
with the following:
– range of instantaneous tripping current (see 4.6 and 5.3.5);
– I²t classification (see 4.7).
5.2.4 Rated short-circuit capacity (I )
cn
Replace the reference to "Table 17" in the note, by "Table 18".
5.3.1 Preferred values of rated voltage
Table 1 – Preferred values of rated voltage
Delete NOTE 1 in Table 1 and renumber the other notes accordingly.
5.3.6 Standard values of rated impulse withstand voltage (U )
imp
Replace Table 3 by the following new Table 3:
Table 3 – Rated impulse withstand voltage as a function
of the nominal voltage of the installation
Nominal voltage of the installation
Rated impulse withstand voltage
Single-phase system with mid-
U
Three-phase systems
imp
point earthed
kV
V
V
a b
2,5 120/240
a c
4 230/400 120/240, 240
NOTE 1 For test voltages to check the insulation, see Table 14.
NOTE 2 For test voltages to check the isolation distance across open contacts, see Table 15.
a
The values 3 kV and 5 kV, respectively, are used for verifying the isolating distances across open contacts at
the altitude of 2 000 m (see Table 15).
b
For installation practice in Japan.
c
For installation practice in North American countries.

SIST EN 60898-1:2019/oprA1:2022
IEC 60898-1:2015/AMD1:2019 – 5 –
© IEC 2019
6 Marking and other product information
Add the following new paragraph after NOTE 3:
For rail-mounted circuit-breakers, appropriate rail(s) shall be indicated in the manufacturer's
documentation.
8 Requirements for construction and operation
8.1.3 Clearances and creepage distances (see Annex B)
Replace 8.1.3 by the following new 8.1.3:
8.1.3 Clearances, creepage distances and solid insulation
The minimum required clearances and creepage distances are given in Table 4 which is
based on the circuit-breaker being designed for operating in an environment with pollution
degree 2.
Parts of PCBs connected to live parts and protected against pollution by the use of a type 2
protection according to IEC 60664-3 are exempted from this verification.
The insulating materials are classified into material groups on the basis of their comparative
tracking index (CTI) according to IEC 60664-1.
NOTE 1 The comparative tracking index (CTI) is declared by the manufacturer on the basis of tests carried out on
the insulating material.
NOTE 2 Information on the requirements for design of solid insulation is provided in IEC 60664-1.
For clearances on printed wiring material, footnote 3 in Table F.2 of IEC 60664-1:2007
applies. For creepage distances on printed wiring material, the distances from Table F.4 of
IEC 60664-1:2007 for pollution degree 1 can be applied only if protected with a coating
meeting IEC 60664-3 requirements and tests.

SIST EN 60898-1:2019/oprA1:2022
– 6 – IEC 60898-1:2015/AMD1:2019
© IEC 2019
Table 4 – Minimum clearances and creepage distances
e, f
Minimum clearances Minimum creepage distances
mm mm
h
Group IIIa Group II Group I
d
(175 V ≤ CTI < (400 V ≤ CTI < (600 V ≤ CTI)
d d
400 V) 600 V)
e
Rated voltage Working voltage
V V
U
imp
2,5 kV 4 kV 4 kV
Description/item
120/ 120/ 230/ > 25 120 250 400 > 25 120 250 400 > 25 120 250 400
i i i
240 240 400 ≤ 50 ≤ 50 ≤ 50
120 240 230
1. Between live parts
which are
separated when
2,0 4,0 4,0 1,2 2,0 4,0 4,0 0,9 2,0 4,0 4,0 0,6 2,0 4,0 4,0
the main contacts
are in the open
a, j
position
2. Between live parts
of different 1,5 3,0 3,0 1,2 1,5 3,0 4,0 0,9 1,5 3,0 3,0 0,6 1,5 3,0 3,0
a
polarity
3. Between circuits
supplied from
different sources,
3,0 6,0 8,0 3,0 6,0 8,0 3,0 6,0 8,0 3,0 6,0 8,0
one of which
being PELV or
g
SELV
Rated voltage
V
120/ 230/ 120/ 230/ 120/ 230/
240 400 240 400 240 400
4. Between live parts
and
– accessible
surfaces of
operating
means
– screws or other
means for fixing
1,5 3,0 3,0 1,5 4,0 1,5 3,0 1,5 3,0
covers which
have to be
removed when
mounting the
circuit-breaker
– surface on
which the
circuit-breaker
b
is mounted
– screws or other
means for fixing
the circuit-
breaker
– metal covers or
b
boxes
– other
accessible
c
metal parts
– metal frames
supporting
flush-type
circuit-breakers
SIST EN 60898-1:2019/oprA1:2022
IEC 60898-1:2015/AMD1:2019 – 7 –
© IEC 2019
Care should be taken to provide adequate clearances and creepage distances between live parts of different
polarity of circuit-breake
...