Fixed firefighting systems - Condensed aerosol extinguishing systems - Part 2: Design, installation and maintenance

This document specifies requirements and describes the methods for the design, installation, testing, maintenance and safety of condensed aerosol extinguishing systems and the characteristics of the extinguishant media and types of fire for which it is a suitable extinguishing medium.
This document also covers the use of condensed aerosol extinguishing systems for total flooding applications in normally unoccupied and unoccupiable areas, primarily related to buildings, plant and other specific applications, utilising electrically non-conducting aerosol fire extinguishants and for which there are sufficient data available to enable validation of performance characteristics by an appropriate independent authority.
This  document is not applicable to explosion suppression applications.
This document is not intended to indicate approval of the extinguishants listed herein by the appropriate authorities, as other extinguishants may be equally acceptable.
This document is applicable to the extinguishants which fulfil prEN152761 (WI 00191148).

Ortsfeste Brandbekämpfungsanlagen - Löschanlagen für kondensierte Aerosole - Teil 2: Planung, Installation und Wartung

Dieses Dokument legt Anforderungen fest und beschreibt die Verfahren für die Planung, Installation, Prüfung,
Instandhaltung und Sicherheit von Aerosol-Löschanlagen sowie die Kenndaten der Löschmittel und deren
Eignung für die verschiedenen Brände.
Dieses Dokument beschreibt ebenfalls den Einsatz von Löschanlagen für kondensierte Aerosole als
Raumschutzanlagen in gewöhnlich unbesetzten und nicht begehbaren Räumen, hauptsächlich hinsichtlich
Gebäuden, Anlagen und weiteren besonderen Anwendungen, bei denen elektrisch nicht leitende Aerosol-Löschmittel
eingesetzt werden, über die gegenwärtig ausreichend viele Angaben verfügbar sind, so dass ihre
Kenndaten durch eine zuständige, unabhängige Institution bestätigt werden können.
Diese Europäische Norm gilt nicht für die Explosionsunterdrückung.
Dieses Dokument stellt keine Auflistung der von zuständigen Stellen zugelassenen Löschmittel dar, weitere,
hier nicht aufgeführte Löschmittel können ebenfalls akzeptabel sein.

Installations de lutte contre l'incendie - Systemes d'extinction a aérosol - Partie 2 : Calcul, installation et maintenance

Le présent document spécifie les exigences et décrit les méthodes de conception, d?installation, d?essai, de
maintenance et sécurité des systemes d'extinction a aérosol de condensation et les caractéristiques des
agents d'extinction, et les types de feux pour lesquels il existe un agent d'extinction approprié.
Le présent document couvre également l'utilisation des systemes d'extinction a aérosol de condensation pour
des applications de noyage total dans des zones habituellement inoccupées et non occupables,
principalement liées aux bâtiments, usines et d'autres applications spécifiques, utilisant des agents
extincteurs en aérosol électriquement non conducteurs et pour lesquels des données suffisantes sont
disponibles afin de permettre la validation des caractéristiques de performance par une autorité indépendante
appropriée.
Le présent document n'est pas applicable aux applications de suppression d'explosion.
Le présent document n'est pas destinée a indiquer l'approbation des agents extincteurs énumérés ici, par les
autorités compétentes, car d'autres agents extincteurs peuvent etre également acceptables.
Le présent document s'applique aux agents extincteurs qui satisfont a la prEN 15276-1.

Vgrajeni gasilni sistemi - Sistemi za gašenje s kondenziranim aerosolom - 2. del: Načrtovanje, vgradnja in vzdrževanje

General Information

Status
Withdrawn
Publication Date
24-Feb-2009
Withdrawal Date
10-Apr-2019
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
11-Apr-2019
Due Date
04-May-2019
Completion Date
11-Apr-2019

Relations

Buy Standard

Technical report
TP CEN/TR 15276-2:2009
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST-TP CEN/TR 15276-2:2009
01-april-2009
9JUDMHQLJDVLOQLVLVWHPL6LVWHPL]DJDãHQMHVNRQGHQ]LUDQLPDHURVRORPGHO
1DþUWRYDQMHYJUDGQMDLQY]GUåHYDQMH
Fixed firefighting systems - Condensed aerosol extinguishing systems - Part 2: Design,
installation and maintenance
Ortsfeste Brandbekämpfungsanlagen - Löschanlagen für kondensierte Aerosole - Teil 2:
Planung, Installation und Wartung
Installations de lutte contre l'incendie - Systemes d'extinction a aérosol - Partie 2 :
Calcul, installation et maintenance
Ta slovenski standard je istoveten z: CEN/TR 15276-2:2009
ICS:
13.220.10 Gašenje požara Fire-fighting
SIST-TP CEN/TR 15276-2:2009 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST-TP CEN/TR 15276-2:2009

---------------------- Page: 2 ----------------------

SIST-TP CEN/TR 15276-2:2009
TECHNICAL REPORT
CEN/TR 15276-2
RAPPORT TECHNIQUE
TECHNISCHER BERICHT
January 2009
ICS 13.220.20

English Version
Fixed firefighting systems - Condensed aerosol extinguishing
systems - Part 2: Design, installation and maintenance
Installations fixes de lutte contre l'incendie - Systèmes Ortsfeste Brandbekämpfungsanlagen - Löschanlagen für
d'extinction à aérosol - Partie 2 : Calcul, installation et kondensierte Aerosole - Teil 2: Planung, Installation und
maintenance Instandhaltung
This Technical Report was approved by CEN on 9 September 2008. It has been drawn up by the Technical Committee CEN/TC 191.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TR 15276-2:2009: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
Contents Page
Foreword .4
Introduction .5
1 Scope .6
2 Normative references .6
3 Terms and definitions .7
4 Use and limitations . 10
4.1 General . 10
4.2 Extinguishants . 11
4.2.1 General . 11
4.2.2 Extinguishing mechanism . 11
4.3 Potentially explosive atmosphere . 11
4.4 Temperature limitations . 11
5 Safety . 12
5.1 Hazard to personnel . 12
5.2 Safety precautions . 12
5.2.1 General . 12
5.2.2 Normally unoccupied areas . 13
5.2.3 Unoccupiable areas . 14
5.2.4 Installer’s responsibility . 14
5.2.5 User’s responsibility . 15
5.3 Electrical hazards . 15
5.3.1 General . 15
5.3.2 Electrical earthing . 15
5.3.3 Electrostatic discharge . 15
6 System design . 15
6.1 General . 15
6.2 Specifications, plans and approvals. 16
6.3 Enclosures . 16
6.3.1 Protected enclosure . 16
6.3.2 Openings . 16
6.3.3 Unclosable openings . 16
6.3.4 Ventilation and services . 16
6.3.5 Venting requirements . 16
6.4 Design factor requirements . 17
6.5 Design factor adjustment . 18
6.5.1 Effects of altitude . 18
6.5.2 Effects of temperature . 18
6.5.3 Effects of ventilation . 19
6.5.4 Compensation for Leakage through enclosure openings . 19
6.6 Design quantity . 19
6.7 Unit size and quantity of aerosol generators . 19
6.7.1 Aerosol generator size selection . 19
6.7.2 Quantity of aerosol generator . 20
6.8 Duration of protection . 21
6.9 System discharge . 21
6.9.1 Discharge time . 21
6.9.2 Extended discharge . 21
6.10 Plans . 21
2

---------------------- Page: 4 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
7 System installation . 22
7.1 General . 22
7.2 Aerosol generator arrangement . 22
7.3 Operating conditions . 23
7.4 Installation recommendations . 23
7.5 System operation . 23
7.5.1 General . 23
7.5.2 Automatic operation . 23
7.5.3 Manual operation . 23
7.5.4 System isolate switch (lock off device) . 23
8 Detection, alarm and control systems . 24
8.1 General . 24
8.2 Automatic detection . 24
8.3 Operating devices . 24
8.3.1 General . 24
8.3.2 Automatic operation . 24
8.3.3 Manual operation . 25
8.4 Control equipment . 25
8.4.1 Electric control equipment . 25
8.4.2 Pneumatic control equipment . 25
8.4.3 Operating alarms and indicators . 25
8.4.4 Time delay device . 26
8.4.5 Control and indicating equipment . 26
9 Commissioning and acceptance . 26
9.1 General . 26
9.2 Tests . 27
9.2.1 General . 27
9.2.2 Enclosure check . 27
9.2.3 Review of mechanical components . 27
9.2.4 Review of enclosure integrity . 27
9.2.5 Review of electrical components . 28
9.2.6 Preliminary functional tests . 28
9.2.7 System functional operational test . 29
9.2.8 Remote monitoring operations (if applicable) . 29
9.2.9 Control panel primary power source . 29
9.3 Completion of functional tests . 29
9.4 Completion certificate and documentation . 29
10 Inspection . 30
10.1 General . 30
10.2 Inspection . 30
10.2.1 General . 30
10.2.2 Enclosures . 30
11 Maintenance . 31
11.1 General . 31
11.2 User's programme of inspection . 31
11.3 Service schedule . 31
12 Training. 31
Annex A (normative) Working documents . 32
A.1 General . 32
A.2 Working documents . 32
Bibliography . 33

3

---------------------- Page: 5 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
Foreword
This document (CEN/TR 15276-2:2009) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
This document has the general title Fixed firefighting systems — Condensed aerosol extinguishing systems
and will consist of the following parts:
 Part 1: Requirements and test methods for components;
 Part 2: Design, installation and maintenance.
4

---------------------- Page: 6 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)

Introduction
It has been assumed in the preparation of this document that the execution of its provisions is entrusted to
appropriately qualified and experienced people in the specification, design, installation, testing, approval,
inspection, operation and maintenance of systems and equipment, for whose guidance it has been prepared,
and who can be expected to exercise a duty of care to avoid unnecessary release of extinguishant.
Product certification: Users of this document are advised to consider the desirability of independent
certification of product conformity with this document based on testing and continuing surveillance, which may
be coupled with assessment of manufacturer quality systems against EN ISO 9001.
Fire-fighting systems covered in this document are designed to provide a supply of fixed condensed aerosol
extinguishing medium to extinguish fire.
The requirements of this document are made in the light of the best technical data known to the working group
at the time of writing but, since a wide field is covered, it has been impracticable to consider every possible
factor or circumstance that might affect implementation of the requirements.
It is important that the fire protection of a building or plant be considered as a whole. Aerosol extinguishant
systems form only a part of the available facilities, but it should not be assumed that their adoption necessarily
removes the need to consider supplementary measures, such as the provision of portable fire extinguishers or
other mobile appliances for first aid or emergency use, or to deal with special hazards.
Small scale fire tests, comparable with the test methods mentioned in this standard, indicate that aerosol
extinguishants can be recognized as effective media for the extinction of certain Class A fires (solid surface
burning fires) and Class B and Class C fires according to EN 2, but it should not be forgotten, in the planning
of comprehensive schemes, that there may be hazards for which these mediums are not suitable, or that in
certain circumstances or situations there may be dangers in their use requiring special precautions.
Advice on these matters can be obtained from the appropriate manufacturer of the aerosol generators or the
extinguishing system. Information may also be sought from the appropriate fire authority, the health and safety
authorities and insurers. In addition, reference should be made as necessary to other national standards and
statutory regulations.
It is essential that fire-fighting equipment, the enclosure and the protected occupancy is carefully maintained
and managed to ensure instant readiness when required and effectiveness of the protection. Routine
maintenance is liable to be overlooked or given insufficient attention by the owner of the system. It is,
however, neglected at peril to the lives of occupants of the premises and at the risk of crippling financial loss.
The importance of maintenance cannot be too highly emphasised.
Condensed aerosol may contain traces of toxic substances like those produced by a fire, and will obscure
vision like smoke from fire. This standard requires, as a precaution, that the room is evacuated and sealed off
whenever a generator is activated - much like recommended response to fires. Precautions include
evacuation of the proximity area, criteria for re-entering and other safeguards as stated in paragraph 5.
5

---------------------- Page: 7 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)

1 Scope
This document specifies requirements and describes the methods for the design, installation, testing,
maintenance and safety of condensed aerosol extinguishing systems and the characteristics of the
extinguishant media and types of fire for which it is a suitable extinguishing medium.
This document also covers the use of condensed aerosol extinguishing systems for total flooding applications
in normally unoccupied and unoccupiable areas, primarily related to buildings, plant and other specific
applications, utilising electrically non-conducting aerosol fire extinguishants and for which there are sufficient
data available to enable validation of performance characteristics by an appropriate independent authority.
This document is intended as a standard covering solely condensed aerosol.
This document is not applicable to explosion suppression applications.
This document is not intended to indicate approval of the extinguishants listed herein by the appropriate
authorities, as other extinguishants may be equally acceptable.
This document is applicable to the extinguishants which fulfil CEN/TR 15276-1.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54 (all parts), Fire detection and fire alarm systems
EN 12094-1, Fixed firefighting systems — Components for gas extinguishing systems — Part 1:
Requirements and test methods for electrical automatic control and delay devices
CEN/TR 15276-1:2009, Fixed firefighting systems — Condensed aerosol extinguishing systems — Part 1:
Requirements and test methods for components
EN 50110, Operation of electrical installations

6

---------------------- Page: 8 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in CEN/TR 15276-1:2009 and the following
apply.
3.1
actuating mechanism
automatic or manual activation leading to the physical discharge of extinguishant
3.2
approved
acceptable to a relevant authority
3.3
authority
organisation, office or individual responsible for approving equipment, installations or procedures in
determining acceptability
NOTE The authority may base acceptance on conformity to the appropriate standards.
3.4
automatic
performing a function without the necessity of intentional intervention
3.5
automatic/manual switch
means of converting the system from automatic to manual actuation
NOTE This may be in the form of a manual switch on the control panel or other units, or a personnel door interlock. In
all cases, this changes the actuation mode of the system from automatic and manual to manual only or vice versa.
3.6
clearance

3.6.1
electrical clearance
unobstructed air distance between extinguishing system equipment and unenclosed or uninsulated live
electrical components not at ground potential
3.6.2
thermal clearance
air distance between a condensed aerosol generator and any structure or components sensitive to the
temperature developed by the generator
3.7
competent person
designated person, suitably trained, qualified by knowledge and practical experience and with the necessary
instructions to enable the required tests and examinations to be carried out
3.8
condensed aerosol
extinguishing medium consisting of finely divided solid particles and gaseous matter, these being generated
by a combustion process of a solid aerosol-forming compound
3.9
condensed aerosol generator
non-pressurised device which, when activated, generates an aerosol
7

---------------------- Page: 9 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
NOTE It includes the mounting brackets.
3.10
control device
device which is able to control the sequence of events leading to the activation
3.11
coolant
heat absorbing medium or process
3.12
3
design application density (g/m )
extinguishing factor multiplied by the safety factor, required for system design purposes
NOTE 1 The design factor is expressed in grams per cubic metre.
NOTE 2 Extinguishing factor and design factor have been introduced as an alternative to extinguishing concentration
and design concentration respectively as concentration of the actual aerosol cannot be measured or even assessed in
some cases (the discharged medium, apart from the condensed aerosol, may contain products of the thermal
decomposition of a chemical coolant).
3.13
design quantity
mass of solid aerosol-forming composition necessary to achieve the design factor (density) in the maximum
protected volume of a specific risk
NOTE The design quantity is expressed in grams.
3.14
discharge time
time from the generator activation to the end of its discharge
3.15
extinguishing application density
the minimum mass of a specific aerosol-forming compound per cubic meter of enclosure volume required to
extinguish fire involving a specific fuel under defined experimental conditions, using a specific aerosol
generator type and size, excluding any safety factor.
NOTE The extinguishing factor is expressed in grams per cubic metre.
3.16
family
group of generators with same solid compound, same kind of cooling device, same kind of discharge outlet,
same ignition device, same layout and same internal/external architecture
3.17
holding time
period of time during which the extinguishant is required to maintain at least the extinguishing application
density throughout the protected area/volume.
3.18
hot work
grinding, welding, thermal or oxygen cutting or heating and other related heat-producing or spark-producing
operations
3.19
ignition device
device which is able to ignite the solid aerosol-forming compound
8

---------------------- Page: 10 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
3.20
inspection
visual check to give a reasonable assurance that the extinguishing system is ready to operations
3.21
listing authority
recognized fire protection testing and approval body (notified laboratory)
3.22
location drawing
plan of the risk clearly indicating the as-installed location of all aerosol generators, controls and maintenance
isolate switch (lock off devices)
3.23
lock-off device
manual shut-off device that prevents the electrical actuation of aerosol generators
NOTE The device operation provides an indication of system isolation.
3.24
lowest observed adverse effect level
LOAEL
lowest agent factor at which an adverse toxicological or physiological effect has been observed
3.25
maintenance
thorough check to give maximum assurance that the extinguishing system will operate as intended
NOTE It includes a thorough examination and any necessary repair or replacement of system components.
3.26
manual
requiring intentional intervention to accomplish a function
3.27
manufacturer
legal person that is responsible for the design, manufacturing, packaging and quality insurance of a device
before it is placed on the market
3.28
monitoring
supervision of the operating integrity of an electrical, mechanical, pneumatic or hydraulic control feature of a
system
3.29
no observed adverse effect level
NOAEL
highest agent factor at which no adverse toxicological or physiological effect has been observed
3.30
normally unoccupied area
area that is not occupied by persons under normal circumstances but may be entered occasionally for brief
periods
3.31
protected volume
volume enclosed by the building elements around the protected enclosure, minus the volume of any
permanent impermeable building element within the enclosure
9

---------------------- Page: 11 ----------------------

SIST-TP CEN/TR 15276-2:2009
CEN/TR 15276-2:2009 (E)
3.32
release
physical discharge or emission of an aerosol as a consequence of the generator actuation
3.33
safety factor
multiplier
...