Low-voltage switchgear and controlgear -- Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters

EN following parallel vote

Niederspannungsschaltgeräte -- Teil 4-1: Schütze und Motorstarter - Elektromechanische Schütze und Motorstarter

Appareillage à basse tension -- Partie 4-1: Contacteurs et démarreurs de moteurs - Contacteurs et démarreurs électromécaniques

Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters

General Information

Status
Withdrawn
Publication Date
31-Jan-2003
Withdrawal Date
23-Nov-2014
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
20-Nov-2014
Due Date
13-Dec-2014
Completion Date
24-Nov-2014

Relations

Buy Standard

Amendment
EN 60947-4-1:2002/A1:2003
English language
23 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI SIST EN 60947-4-
1:2002/A1:2003

STANDARD
februar 2003
Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters -
Electromechanical contactors and motor-starters
ICS 5HIHUHQþQDãWHYLOND
29.130.20
SIST EN 60947-4-1:2002/A1:2003(en)
! "#$%!&!%’()*#+’

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD EN 60947-4-1/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM December 2002

ICS 29.120.99; 29.130.20


English version


Low-voltage switchgear and controlgear
Part 4-1: Contactors and motor-starters -
Electromechanical contactors and motor-starters
(IEC 60947-4-1:2000/A1:2002)


Appareillage à basse tension Niederspannungsschaltgeräte
Partie 4-1: Contacteurs et démarreurs Teil 4-1: Schütze und Motorstarter -
de moteurs - Elektromechanische Schütze
Contacteurs et démarreurs und Motorstarter
électromécaniques (IEC 60947-4-1:2000/A1:2002)
(CEI 60947-4-1:2000/A1:2002)






This amendment A1 modifies the European Standard EN 60947-4-1:2001; it was approved by CENELEC
on 2002-10-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this amendment the status of a national standard without any
alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2002 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 60947-4-1:2001/A1:2002 E

---------------------- Page: 2 ----------------------

EN 60947-4-1:2001/A1:2002 - 2 -
Foreword
The text of document 17B/1210/FDIS, future amendment 1 to IEC 60947-4-1:2000, prepared by
SC 17B, Low-voltage switchgear and controlgear, of IEC TC 17, Switchgear and controlgear, was
submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as amendment A1 to
EN 60947-4-1:2001 on 2002-10-01.
The following dates were fixed:
– latest date by which the amendment has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2003-07-01
– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2005-10-01
Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annexes F and ZA are normative and annex E is informative.
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of amendment 1:2002 to the International Standard IEC 60947-4-1:2000 was approved by
CENELEC as an amendment to the European Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated:

IEC 60664-1 NOTE Harmonized as HD 625.1 S1:1996 (modified).
__________

---------------------- Page: 3 ----------------------

- 3 - EN 60947-4-1:2001/A1:2002
Replace annex ZA of EN 60947-4-1:2001 by the following:
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies (including
amendments).
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
Publication Year Title EN/HD Year
IEC 60034-1 (mod) 1996 Rotating electrical machines EN 60034-1 1998
 Part 1: Rating and performance + corr. February 2000
A1 1997 A1 1998
A2 1999 A2 1999
A11 2002

IEC 60034-11 1978 Part 11: Built-in thermal protection - -
Chapter 1: Rules for protection of
rotating electrical machines

IEC 60050-441 1984 International Electrotechnical - -
Vocabulary (IEV)
Chapter 441: Switchgear, controlgear
and fuses

IEC 60076-1 (mod) 1993 Power transformers EN 60076-1 1997
 Part 1: General A11 1997
A1 1999 A1 2000
A12 2002

IEC 60085 1984 Thermal evaluation and classification of HD 566 S1 1990
electrical insulation

IEC 60112 1979 Method for determining the comparative HD 214 S2 1980
and the proof tracking indices of solid
insulating materials under moist
conditions

IEC 60255-8 (mod) 1990 Electrical relays EN 60255-8 1998
Part 8: Thermal electrical relays

IEC 60269-1 1998 Low-voltage fuses EN 60269-1 1998
Part 1: General requirements

IEC 60269-2 1986 Part 2: Supplementary requirements for EN 60269-2 1995
A1 1995 fuses for use by authorized persons A1 1998
A2 2001 (fuses mainly for industrial application) A2 2002

---------------------- Page: 4 ----------------------

EN 60947-4-1:2001/A1:2002 - 4 -
Publication Year Title EN/HD Year
IEC 60269-2-1 (mod) 1998 Part 2-1: Supplementary requirements
+ A1 1999 for fuses for use by authorized persons HD 630.2.1 S5 2002
A2 2002 (fuses mainly for industrial application) - -
Sections I to V: Examples of types of
standardized fuses

IEC 60410 1973 Sampling plans and procedures for - -
inspection by attributes

IEC 60947-1 (mod) 1999 Low-voltage switchgear and controlgear EN 60947-1 1999
 Part 1: General rules + corr. October 1999
A1 2000 A1 2000
A2 2001 A2 2001

IEC 60947-2 1995 Part 2: Circuit-breakers EN 60947-2 1996
  + corr. June 1997
A1 1997 A1 1997
A2 2001 A2 2001

IEC 60947-3 1999 Part 3: Switches, disconnectors, switch- EN 60947-3 1999
A1 2001 disconnectors and fuse-combination A1 2001
units

IEC 60947-5-1 1997 Part 5-1: Control circuit devices and EN 60947-5-1 1997
A1 1999 switching elements - Electromechanical A1 1999
 control circuit devices A12 1999
A2 1999 A2 2000

IEC 61000-4-2 1995 Electromagnetic compatibility (EMC) EN 61000-4-2 1995
A1 1998 Part 4-2: Testing and measurement A1 1998
A2 2000 techniques - Electrostatic discharge A2 2001
immunity test

IEC 61000-4-3 (mod) 1995 Part 4-3: Testing and measurement EN 61000-4-3 1996
A1 1998 techniques - Radiated, radio-frequency, A1 1998
A2 2000 electromagnetic field immunity test A2 2001

IEC 61000-4-4 1995 Part 4-4: Testing and measurement EN 61000-4-4 1995
A1 2000 techniques - Electrical fast A1 2001
A2 2001 transient/burst immunity test A2 2001

IEC 61000-4-5 1995 Part 4-5: Testing and measurement EN 61000-4-5 1995
A1 2000 techniques - Surge immunity test A1 2001

IEC 61095 1992 Electromechanical contactors for EN 61095 1993
 household and similar purposes + corr. March 1993
A1 2000 A1 2000
+ corr. April 2001

IEC 61810-1 1998 Electromechanical non-specified time EN 61810-1 1998
all-or-nothing relays
Part 1: General requirements

CISPR 11 (mod) 1997 Industrial, scientific and medical (ISM) EN 55011 1998
A1 1999 radio-frequency equipment - Radio A1 1999
disturbance characteristics - Limits and
methods of measurement

---------------------- Page: 5 ----------------------

NORME CEI
INTERNATIONALE IEC
60947-4-1
INTERNATIONAL
2000
STANDARD
AMENDEMENT 1
AMENDMENT 1
2002-09
Amendement 1
Appareillage à basse tension
Partie 4-1:
Contacteurs et démarreurs de moteurs –
Contacteurs et démarreurs électromécaniques
Amendment 1
Low-voltage switchgear and controlgear –
Part 4-1:
Contactors and motor-starters –
Electromechanical contactors and
motor-starters
 IEC 2002 Droits de reproduction réservés  Copyright - all rights reserved
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch  Web: www.iec.ch
CODE PRIX
R
Commission Electrotechnique Internationale
PRICE CODE
International Electrotechnical Commission
Международная Электротехническая Комиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

---------------------- Page: 6 ----------------------

60947-4-1 Amend. 1  IEC:2002 – 3 –
FOREWORD
This amendment has been prepared by subcommittee 17B: Low-voltage switchgear and
controlgear, of IEC technical committee 17: Switchgear and controlgear.
The text of this amendment is based on the following documents:
FDIS Report on voting
17B/1210/FDIS 17B/1237/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until 2005. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
___________
Page 3
CONTENTS
Modify, on page 5, the title of annex C to read:
Annex C Void
Add, on page 5, the titles of the new annexes E and F and the new Bibliography:
Annex E (informative) Examples of control circuit configurations
Annex F (normative) Requirements for auxiliary contact linked with power contact (mirror
contact)
Bibliography
Delete, on page 7, the reference to table 11.

---------------------- Page: 7 ----------------------

60947-4-1 Amend. 1  IEC:2002 – 5 –
Page 11
Replace both fourth and fifth paragraphs by the following:
Annexes A, B and F form an integral part of this standard.
Annexes D and E are for information only.
Page 13
1.1 AC and d.c. contactors
Add, at the end of this subclause, the following new paragraph:
Contactors or starters with an electronically controlled electromagnet are also covered by this
standard.
Page 19
2 Normative references
Add, after IEC 60034-1:1996, the following references:
Amendment 1 (1997)
Amendment 2 (1999)
Add, after IEC 60076-1:1993, the following reference:
Amendment 1 (1999)
Add, after IEC 60269-2:1986, the following references:
Amendment 1 (1995)
Amendment 2 (2001)
Add, after IEC 60269-2-1:1998, the following references:
Amendment 1 (1999)
Amendment 2 (2002)
Add, after IEC 60947-1:1999, the following references:
Amendment 1 (2000)
Amendment 2 (2001)
Add, after IEC 60947-2:1995, the following references:
Amendment 1 (1997)
Amendment 2 (2001)

---------------------- Page: 8 ----------------------

60947-4-1 Amend. 1  IEC:2002 – 7 –
Add, after IEC 60947-3:1999, the following reference:
Amendment 1 (2001)
Add, after IEC 60947-5-1:1997, the following references:
Amendment 1 (1999)
Amendment 2 (1999)
Add, after IEC 61000-4-2:1995, the following references:
Amendment 1 (1998)
Amendment 2 (2000)
Add, after IEC 61000-4-3:1995, the following references:
Amendment 1 (1998)
Amendment 2 (2000)
Add, after IEC 61000-4-4:1995, the following references:
Amendment 1 (2000)
Amendment 2 (2001)
Add, after IEC 61000-4-5:1995, the following reference:
Amendment 1 (2000)
Add, after IEC 61095:1992, the following reference:
Amendment 1 (2000)
Add, after CISPR 11:1997, the following reference:
Amendment 1 (1999)
Page 23
3.1.2
electromagnetic contactor
Add, after the definition, the following note:
NOTE The electromagnet may be electronically controlled (see 3.1.8).

---------------------- Page: 9 ----------------------

60947-4-1 Amend. 1  IEC:2002 – 9 –
Add, after 3.1.7, the following new definition 3.1.8:
3.1.8
electronically controlled coil for electromagnet
coil controlled by a circuit with active electronic elements
Page 51
5.5 Control circuits
Replace the existing text by the following:
Subclause 4.5 of IEC 60947-1 applies; moreover, for an electronically controlled electro-
magnet, 4.5.1 of IEC 60947-1 applies with the following addition.
The electronic part may form an integral part or a separate part provided it is an intrinsic
function of the device. In both cases, the device shall be tested with this electronic part
mounted as in normal use.
The characteristics of electronic control circuits are as follows:
− type of current;
− power consumption;
− rated frequency (or d.c.);
− rated control circuit voltage, U (nature: a.c./d.c.);
c
− rated control supply voltage, U (nature: a.c./d.c.);
s
− nature of external control circuit devices (contacts, sensors, optocouplers, electronic
active components, etc).
Annex E gives examples and illustrations of different circuit configurations.
NOTE A distinction is made between the control circuit voltage U , which is the controlling input signal, and the
c
control supply voltage U , which is the voltage applied to energize the power supply terminals of the control circuit
s
equipment and may be different from U due to the presence of built-in transformers, rectifiers, resistors, electronic
c
circuitry, etc.
Page 57
5.8 Co-ordination with short-circuit protective devices
Replace the existing text by the following:
The co-ordination of contactors and starters is characterized by the type, ratings and
characteristics of the short-circuit protective devices (SCPD) that provide protection of the
contactor and starter against short-circuit currents. Requirements are given in 8.2.5.1 and
8.2.5.2 of this standard, and in 4.8 of IEC 60947-1.

---------------------- Page: 10 ----------------------

60947-4-1 Amend. 1  IEC:2002 – 11 –
Page 61
6.1.2 Characteristics, basic rated values and utilization
Replace the existing item j) by the following new item j):
j) rated impulse withstand voltage (see 5.3.1.3);
Replace, on page 63, the existing item y) by the following new item y):
y) environment A or B: see 7.3.1 of IEC 60947-1;
Page 63
6.2 Marking
Add, after the third paragraph, the following new paragraph:
In the case of electronically controlled electromagnets, information other than that given in o)
and p) of 6.1.2 may also be necessary; see also 5.5 and annex E.
Page 65
8.1.3 Clearances and creepage distances
Replace the existing text by the following:
Subclause 7.1.3 of IEC 60947-1 applies.
8.1.6 Additional safety requirements for equipment with isolating function
Replace the existing text by the following:
Subclause 7.1.6 of IEC 60947-1 applies with the addition of the following paragraphs to
subclause 7.1.6.1 of that standard.
Devices provided with positions like trip position or stand-by position which are not the
indicated open position shall be clearly marked.
An actuator having only one position of rest shall not be considered as appropriate to indicate
the position of the main contact.

---------------------- Page: 11 ----------------------

60947-4-1 Amend. 1  IEC:2002 – 13 –
Page 69
8.2.1.2 Limits of operation of contactors and power-operated starters
Replace the existing text of this subclause as follows:
8.2.1.2.1 Electromagnetic contactors and starters
Electromagnetic contactors, whether used separately or in starters, shall close satisfactorily at
any value between 85 % and 110 % of their rated control supply voltage U . Where a range is
s
declared, 85 % shall apply to the lower value and 110 % to the higher.
The limits between which contactors shall drop out and open fully are 75 % to 20 % for a.c.
and 75 % to 10 % for d.c. of their rated control supply voltage U . Where a range is declared,
s
20 % or 10 %, as the case may be, shall apply to the higher value and 75 % to the lower.
Limits for closing are applicable after the coils have reached a stable temperature
corresponding to indefinite application of 100 % U in an ambient temperature equivalent to
s
the ambient temperature declared by the manufacturer but not less than +40 °C.
Limits for drop-out are applicable with the coil circuit resistance at −5 °C. This can be verified
by calculation using values obtained at normal ambient air temperature.
The limits apply to d.c. and a.c. at declared frequency.
8.2.1.2.2 Contactors and starters with electronically controlled electromagnet
Subclause 8.2.1.2.1 applies with the following modification.
Replace the second paragraph as follows:
The limits between which contactors with an electronically controlled electromagnet shall drop
out and open fully are
− for d.c.: 75 % to 10 % of their rated control supply voltage U
s,
− for a.c.: 75 % to 20 % of their rated control supply voltage U ,
s
− for a.c.: 75 % to 10 % of their rated control supply voltage U if specified by the
s
manufacturer,
− for a.c., where a range is declared with limits between 75 % to 10 % of their rated control
supply voltage U , the contactor shall, in addition, be submitted to the capacitive drop out
s
test of 8.2.1.2.4.
Where a range is declared, 20 % or 10 % as the case may be, shall apply to the higher value
of the range and 75 % to the lower value of the range.