Alarm systems - Intrusion and hold-up systems - Part 7: Application guidelines

These application guidelines include guidance on the design, planning, operation, installation, commissioning and maintenance of I&HAS installed in buildings. Requirements for I&HAS are specified in EN 50131-1:2006.
The recommendations of this Technical Specification (TS) also apply to IAS and HAS when these systems are installed independently. When an I&HAS does not include functions relating to the detection of intruders, the requirements relating to intrusion detection do not apply.
When an I&HAS does not include functions relating to hold-up, the requirements relating to hold-up do not apply.
NOTE Unless otherwise stated the abbreviation I&HAS is intended to also mean IAS and HAS.
These application guidelines are intended to assist those responsible for establishing an I&HAS to ascertain the appropriate design of I&HAS both in terms of the extent of the supervision required and in determining the grade of system performance necessary to provide the degree of supervision considered appropriate.
These application guidelines are also intended to assist those responsible for selecting equipment appropriate to both the level of performance required and the environmental conditions in which the equipment will be required to operate.
These application guidelines are relevant to all classes and grades of I&HAS of any size and complexity. These application guidelines should be read in conjunction with EN 50131-1:2006.
NOTE It has been assumed in the drafting of these application guidelines that the execution of its provisions will be entrusted to appropriately qualified and experienced persons. However the guidance is also appropriate to other persons who may be required to purchase or use an I&HAS.

Alarmanlagen - Einbruch- und Überfallmeldeanlagen - Teil 7: Anwendungsregeln

Systèmes d'alarme - Systèmes d'alarme contre l'intrusion et les hold-up - Partie 7: Guide d'application

Alarmni sistemi - Sistemi za javljanje vloma - 7. del: Navodila za uporabo

Ta navodila za uporabo zajemajo napotke za zasnovo, načrtovanje, obratovanje, namestitev, usposobitev za zagon in vzdrževanje sistemov za sporočanje o vlomu in ropu, nameščenih v stavbah. Zahteve za sisteme za sporočanje o vlomu in ropu (I&HAS) so opredeljene v EN 50131-1:2006.
Priporočila te tehnične specifikacije (TS) se uporabljajo tudi za sisteme za sporočanje o vlomu in ropu (IAS in HAS), kadar so ti sistemi nameščeni ločeno. Kadar sistem za javljanje vloma ne zajema funkcij, ki se nanašajo na zaznavanje vsiljivcev, se zahteve, ki se nanašajo na zaznavanje vdora, ne uporabljajo.
Kadar sistem za sporočanje o vlomu in ropu ne zajema funkcij, ki se nanašajo na rop, se zahteve, ki se nanašajo na rop, ne uporabljajo.
OPOMBA: Razen kadar je drugače navedeno, okrajšava I&HAS pomeni tudi IAS in HAS.
Ta navodila za uporabo so opora odgovornim za vzpostavitev sistema za sporočanje o vlomu, za ugotovitev primerne zasnove sistema za sporočanje o vlomu glede obsega potrebnega nadzora in določitve stopnje zmogljivosti sistema, potrebne za zagotavljanje stopnje nadzora, ki velja za primerno.
Ta navodila za uporabo so tudi opora odgovornim pri izbiri opreme, primerne za stopnjo potrebne zmogljivosti in za okoljske razmere, v katerih bo oprema morala delovati.
Ta navodila za uporabo se nanašajo na vse razrede in kategorije sistemov za sporočanje o vlomu katere koli velikosti in zahtevnosti. Ta navodila za uporabo je treba brati skupaj z EN 50131-1:2006.
OPOMBA: Pri snovanju teh navodil za uporabo smo sklepali, da bo izvajanje določil zaupano primerno usposobljenim in izkušenim osebam. Navodilo je primerno tudi za druge osebe, ki bodo morda morale kupiti ali uporabljati sistem za sporočanje o vlomu.

General Information

Status
Published
Publication Date
07-Apr-2011
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
30-Mar-2011
Due Date
04-Jun-2011
Completion Date
08-Apr-2011

Relations

Buy Standard

Technical specification
TS CLC/TS 50131-7:2011
English language
54 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST-TS CLC/TS 50131-7:2011
01-maj-2011
1DGRPHãþD
SIST-TS CLC/TS 50131-7:2009
Alarmni sistemi - Sistemi za javljanje vloma - 7. del: Navodila za uporabo
Alarm systems - Intrusion and hold-up systems - Part 7: Application guidelines
Alarmanlagen - Einbruch- und Überfallmeldeanlagen - Teil 7: Anwendungsregeln
Systèmes d'alarme - Systèmes d'alarme contre l'intrusion et les hold-up - Partie 7: Guide
d'application
Ta slovenski standard je istoveten z: CLC/TS 50131-7:2010
ICS:
13.310 Varstvo pred kriminalom Protection against crime
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST-TS CLC/TS 50131-7:2011 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST-TS CLC/TS 50131-7:2011

---------------------- Page: 2 ----------------------

SIST-TS CLC/TS 50131-7:2011

TECHNICAL SPECIFICATION
CLC/TS 50131-7

SPÉCIFICATION TECHNIQUE
July 2010
TECHNISCHE SPEZIFIKATION

ICS 13.310 Supersedes CLC/TS 50131-7:2008


English version


Alarm systems -
Intrusion and hold-up systems -
Part 7: Application guidelines



Systèmes d'alarme -  Alarmanlagen -
Systèmes d'alarme contre l'intrusion Einbruch- und Überfallmeldeanlagen -
et les hold-up - Teil 7: Anwendungsregeln
Partie 7: Guide d'application






This Technical Specification was approved by CENELEC on 2010-06-25.

CENELEC members are required to announce the existence of this TS in the same way as for an EN and to
make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting
national standards in force.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.



CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels


© 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. CLC/TS 50131-7:2010 E

---------------------- Page: 3 ----------------------

SIST-TS CLC/TS 50131-7:2011
CLC/TS 50131-7:2010 – 2 –
Foreword
This Technical Specification was prepared by the Technical Committee CENELEC TC 79, Alarm
systems. It was circulated for vote in accordance with the Internal Regulations, Part 2,
Subclause 11.3.3.3 and was approved by CENELEC as CLC/TS 50131-7 on 2010-06-25
This document supersedes CLC/TS 50131-7:2008.
Compared to the previous edition the changes are the following:
• 3.1.46: note deleted;
• 10.2: “the test signals replaced with “these signals” in the last paragraph;
nd
• 10.4: “hold-up triggering devices” replaced with “hold-up devices” in the 2 paragraph;
• Annex B, B.6: “Psychological problems of persons after robbery” deleted;
• Annex D, D.13: “avoid” replaced with “minimize”.
The following date was fixed:
– latest date by which the existence of the CLC/TS
has to be announced at national level (doa) 2011-01-01
The EN/TS 50131 series consists of the following parts, under the general title Alarm systems –
Intrusion and hold-up systems:
Part 1 System requirements
Part 2-2 Intrusion detectors – Passive infrared detectors
Part 2-3 Requirements for microwave detectors
Part 2-4 Requirements for combined passive infrared and microwave detectors
Part 2-5 Requirements for combined passive infrared and ultrasonic detectors
Part 2-6 Opening contacts (magnetic)
Part 2-7-1 Intrusion detectors – Glass break detectors (acoustics)
Part 2-7-2 Intrusion detectors – Glass break detectors (passive)
Part 2-7-3 Intrusion detectors – Glass break detectors (active)
1)
Part 2-8 Intrusion detectors – Vibration detectors
1)
Part 2-9 Intrusion detectors – Active infrared detectors
Part 3 Control and indicating equipment
Part 4 Warning devices
1)
Part 5-1 Requirements for wired interconnection for I&HAS equipments located in
supervised premises
Part 5-3 Requirements for interconnections equipment using radio frequency techniques
Part 6 Power supplies
Part 7 Application guidelines
Part 8 Security fog device/systems
1)
Part 9 Alarm verification – Methods and principles
———————
1)
At draft stage.

---------------------- Page: 4 ----------------------

SIST-TS CLC/TS 50131-7:2011
– 3 – CLC/TS 50131-7:2010
Contents
Introduction . 5
1 Scope . 7
2 Normative references . 7
3 Terms, definitions and abbreviations . 7
3.1 Terms and definitions . 7
3.2 Abbreviations . 12
4 Security grade of I&HAS . 12
4.1 Security grading . 12
5 Environmental classification . 13
5.1 Environmental Class I – Indoor . 13
5.2 Environmental Class II – Indoor – General . 13
5.3 Environmental Class III – Outdoor – Sheltered or indoor extreme conditions . 13
5.4 Environmental Class IV – Outdoor – General. 13
6 General . 14
6.1 Other components . 14
6.2 Electrical safety . 14
6.3 Unwanted alarms . 14
6.4 Responsibility . 14
6.5 Qualifications . 14
6.6 Competence . 14
6.7 Tools . 14
6.8 Confidentiality . 14
6.9 Consultation . 14
6.10 Compatibility . 15
7 System design . 15
7.1 Location survey – Risk . 15
7.2 Location survey – Other influences . 16
7.3 System design proposal . 16
8 Installation planning . 21
8.1 General . 21
9 S yst em i nst a ll ati on . 22
9.1 Installation process . 22
10 Inspection, functional testing and commissioning . 22
10.1 Inspection . 22
10.2 Functional testing . 22
10.3 Commissioning . 22
10.4 Handover . 22
10.5 Test period . 23
10.6 Acceptance . 23
10.7 As-fitted document . 23
10.8 Certificate of conformance . 23
11 Documentation and records . 24
11.1 Documentation . 24
11.2 Records . 24
12 Operation of I&HAS . 25

---------------------- Page: 5 ----------------------

SIST-TS CLC/TS 50131-7:2011
CLC/TS 50131-7:2010 – 4 –
13 Maintenance and repair of I&HAS . 25
13.1 General . 25
13.2 Inspection and servicing . 25
13.3 Repair . 26
Annex A (normative) Special national conditions . 27
Annex B (informative) System design – Location survey – Contents . 28
Annex C (informative) Systems design – Location survey – Building . 29
Annex D (informative) Location survey – Influences affecting I&HAS originating
within the supervised premises . 31
Annex E (informative) Location survey – Influences affecting I&HAS originating
outside the supervised premises . 34
Annex F (informative) Levels of supervision . 36
Annex G (normative) Information to be included in the system design proposal . 37
Annex H (informative) Technical survey . 39
Annex I (informative) System record (log book) . 51
Annex J (informative) Maintenance . 52
Annex K (informative) Flow chart . 53
Bib lio gr ap h y . 54

Table
Table F.1 – Levels of supervision. 36
Figure
Figure K.1 – Flow chart . 53

---------------------- Page: 6 ----------------------

SIST-TS CLC/TS 50131-7:2011
– 5 – CLC/TS 50131-7:2010
Introduction
These application guidelines are intended to provide advice relating to the design, installation,
operation and maintenance of Intruder and Hold-up Alarm Systems (I&HAS). The purpose of this
document is to ensure, as far as is practical, that I&HAS provide the required performance with a
minimum of unwanted alarms.
These application guidelines are set out in the logical order in which an I&HAS would normally be
designed and installed. Each procedure is set out separately in the guideline but it is accepted that, in
practice, some of the procedures may be carried out simultaneously. Annex K describes in the form of
a flowchart the main processes and documentation included in this application guideline.
Those responsible for the design, installation planning, system installation, commissioning, operation
and maintenance of I&HAS should be conversant with other European Standards relating to I&HAS,
particularly those relating to system performance, control and indicating equipment, detectors, warning
devices, power supplies and alarm transmission systems.
These application guidelines are set out in seven main clauses; a brief explanation of each section is
shown below.
i) Clause 7 – System design
This clause is intended to assist those responsible for designing I&HAS to design I&HAS suitable
for the premises to be supervised in relation to the perceived risk(s). The design of I&HAS will
depend on many factors all of which will influence more or less the design of I&HAS.
Consideration of these factors will result in a system design proposal for an I&HAS with the
appropriate extent, security grade and environmental class.
ii) Clause 8 – Installation planning
This clause is intended to help those responsible for installing I&HAS by highlighting issues which
should be considered prior to commencing the installation of the I&HAS.
iii) Clause 9 – System installation
In this clause, guidance is given with regard to issues arising during the installation of I&HAS.
This clause is intended to ensure I&HAS is correctly installed as specified at the design stage.
iv) Clause 10 – Inspection, functional testing and commissioning
In this clause, guidance is given on issues arising after I&HAS has been installed. The clause is
intended to ensure I&HAS has been installed as specified and also provides the level of
performance intended at the design stage. Guidance is also provided with regard to the proper
commissioning and handing over of the system to the user and to the documents, records and
operating instructions which should be provided.
v) Clause 11 – Documentation and records
This clause describes the documentation which should be provided to the client on completion of
I&HAS. The documents are intended to provide a history of modifications to I&HAS, based on the
as-fitted document, prepared when I&HAS installation was completed.
The records are intended to chronicle any corrective action carried out following unwanted alarm
conditions and details of any repairs or modifications to I&HAS. The record should also include
details of temporary fault conditions.

---------------------- Page: 7 ----------------------

SIST-TS CLC/TS 50131-7:2011
CLC/TS 50131-7:2010 – 6 –
vi) Clause 12 – Operation of I&HAS
This clause describes the responsibility of the client or user of I&HAS to properly maintain I&HAS
and to ensure it is operated correctly.
vii) Clause 13 – Maintenance and repair of I&HAS
This clause describes how I&HAS should be maintained and repaired to ensure I&HAS continues
to provide the level of performance intended at the design stage.

---------------------- Page: 8 ----------------------

SIST-TS CLC/TS 50131-7:2011
– 7 – CLC/TS 50131-7:2010
1 Scope
These application guidelines include guidance on the design, planning, operation, installation,
commissioning and maintenance of I&HAS installed in buildings. Requirements for I&HAS are
specified in EN 50131-1:2006.
The recommendations of this Technical Specification (TS) also apply to IAS and HAS when these
systems are installed independently.
When an I&HAS does not include functions relating to the detection of intruders, the requirements
relating to intrusion detection do not apply.
When an I&HAS does not include functions relating to hold-up, the requirements relating to hold-up do
not apply.
NOTE Unless otherwise stated the abbreviation I&HAS is intended to also mean IAS and HAS.
These application guidelines are intended to assist those responsible for establishing an I&HAS to
ascertain the appropriate design of I&HAS both in terms of the extent of the supervision required and
in determining the grade of system performance necessary to provide the degree of supervision
considered appropriate.
These application guidelines are also intended to assist those responsible for selecting equipment
appropriate to both the level of performance required and the environmental conditions in which the
equipment will be required to operate.
These application guidelines are relevant to all classes and grades of I&HAS of any size and
complexity. These application guidelines should be read in conjunction with EN 50131-1:2006.
NOTE It has been assumed in the drafting of these application guidelines that the execution of its provisions will be entrusted
to appropriately qualified and experienced persons. However the guidance is also appropriate to other persons who may be
required to purchase or use an I&HAS.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 50131-1:2006, Alarm systems – Intrusion and hold-up systems – Part 1: System requirements
EN 61082-1:2006, Preparation of documents used in electrotechnology – Part 1: Rules
(IEC 61082-1:2006)
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1.1
alarm
warning of the presence of a hazard to life, property or the environment
3.1.2
alarm receiving centre
continuously manned centre to which information concerning the status of one or more I&HAS is
reported

---------------------- Page: 9 ----------------------

SIST-TS CLC/TS 50131-7:2011
CLC/TS 50131-7:2010 – 8 –
3.1.3
alarm company
organization which provides services for I&HAS
3.1.4
alarm condition
condition of an I&HAS, or part thereof, which results from the response of the system to the presence
of a hazard
3.1.5
alarm system
electrical installation which responds to the manual or automatic detection of the presence of a hazard
3.1.6
alarm transmission system
equipment and network used to transfer information concerned with the state of one or more I&HAS to
one or more alarm receiving centre
NOTE Alarm transmission systems exclude local direct connections, i.e. interconnections between parts of an I&HAS which do
not require an interface to transform I&HAS information into a form suitable for transmission.
3.1.7
ancillary control equipment
equipment used for supplementary control purposes
3.1.8
as-fitted document
document in which details of I&HAS as actually installed are recorded
3.1.9
control and indicating equipment
equipment for receiving, processing, controlling, indicating and initiating, the onward transmission of
information
3.1.10
commissioning
putting an I&HAS into operational mode
3.1.11
client
individual or corporate body responsible for acquiring the I&HAS
3.1.12
detector
device designed to generate an intruder alarm signal or message in response to the sensing of an
abnormal condition indicating the presence of a hazard
3.1.13
documentation
paperwork (or other media) prepared during the design, installation, commissioning and handover of
I&HAS recording details of the I&HAS
3.1.14
entry/exit route
route by which authorized entry or exit to the supervised area or part thereof may be achieved
3.1.15
equipment schedule
list of equipment to be installed or actually installed

---------------------- Page: 10 ----------------------

SIST-TS CLC/TS 50131-7:2011
– 9 – CLC/TS 50131-7:2010
3.1.16
fault condition
condition of an alarm system which prevents an I&HAS or parts thereof from functioning normally
3.1.17
entry/exit point
point at which the user enters or leaves the supervised premises
EXAMPLE Entrance door to supervised premises
3.1.18
hold-up alarm system
alarm system providing the means for a user to deliberately generate a hold-up alarm condition
3.1.19
hold-up device
device which when triggered causes a hold-up alarm signal or message to be generated
3.1.20
hold-up alarm condition
condition of an alarm system, or part thereof, which results from the response of an I&HAS to the
triggering of a hold-up device
3.1.21
inhibit
status of a part of an I&HAS in which an alarm condition cannot be notified, such status remaining until
I&HAS or part thereof is unset
3.1.22
installation company
company responsible for installing the I&HAS
3.1.23
installation plan
document describing the methodology to be followed during the installation of the I&HAS
3.1.24
installer
individual or individuals responsible for carrying out the installation process
3.1.25
intruder alarm system
alarm system to detect and indicate the presence, entry or attempted entry of an intruder into
supervised premises
3.1.26
interconnection
means by which messages and/or signals are transmitted between I&HAS components
3.1.27
isolation
status of a part of an alarm system in which an alarm condition cannot be notified, such status
remaining until deliberately cancelled
3.1.28
non-specific wired interconnection
interconnection conveying information pertaining to two or more applications
3.1.29
normal condition
state of an I&HAS system where no conditions exist which would prevent the setting of the I&HAS

---------------------- Page: 11 ----------------------

SIST-TS CLC/TS 50131-7:2011
CLC/TS 50131-7:2010 – 10 –
3.1.30
notification
passing of an alarm, tamper or fault condition to warning devices and/or alarm transmission systems
3.1.31
operational mode
state of an alarm system when it is complete, commissioned and ready for use
3.1.32
part set
status of an I&HAS in which an intruder alarm condition can be notified but part of I&HAS is unset
3.1.33
power supply
that part of an alarm system which provides power for I&HAS or any part thereof
3.1.34
response authority
designated authority with responsibility for attending the supervised premises following an alarm and
taking the appropriate action
3.1.35
set
status of an I&HAS or part thereof in which an alarm condition can be notified
3.1.36
specific wired interconnection
interconnection conveying information pertaining to one application
3.1.37
specifier
individual or corporate body responsible for stipulating the requirements I&HAS will be required to
meet
3.1.38
subsystem
that part of an I&HAS located in a clearly defined part of the supervised premises capable of
independent operation
3.1.39
supervised premises
part of a building and/or area in which an intrusion, attempted intrusion, or the triggering of a hold-up
device may be detected by an I&HAS
3.1.40
supervised premises transceiver
equipment at the supervised premises, including the interface to the alarm system and the interface to
the alarm transmission network
3.1.41
system components
individual items of equipment which constitute an I&HAS when configured together
3.1.42
system record
history of maintenance, faults, repair or modifications to the IAS
EXAMPLE A log book

---------------------- Page: 12 ----------------------

SIST-TS CLC/TS 50131-7:2011
– 11 – CLC/TS 50131-7:2010
3.1.43
tamper
deliberate interference with an I&HAS or part thereof
3.1.44
tamper alarm
alarm generated by tamper detection
3.1.45
tamper condition
condition of an I&HAS in which tampering has been detected
3.1.46
tamper protection
methods or means used to protect an I&HAS or part thereof against deliberate interference.
3.1.47
technical survey
inspection of the premises to be supervised, carried out after the proposal has been accepted, to
verify the selection, location and siting of system components and to consider the selection of
components in relation to the environmental conditions to which the system components will be
exposed
3.1.48
unset
status of an I&HAS or part thereof in which an alarm condition cannot be notified
3.1.49
user
person authorized to operate an I&HAS
3.1.50
unknown alarm
alarm for which the cause cannot be positively identified
3.1.51
unwanted alarm
alarm conditions not generated by an intrusion or attempted intrusion into the supervised premises
3.1.52
warning device
device that gives an audible alarm in response to a notification
NOTE A warning device may also provide alert indications providing such indications are easily distinguishable from an alarm.
3.1.53
wire-free interconnection
interconnection conveying information between I&HAS components without physical media
3.1.54
zone
assessed area of a supervised premises where an intrusion, attempted intrusion, or the triggering of a
hold-up device may be detected by an I&HAS

---------------------- Page: 13 ----------------------

SIST-TS CLC/TS 50131-7:2011
CLC/TS 50131-7:2010 – 12 –
3.2 Abbreviations
For the purposes of this document, the following abbreviations apply.
ACE Ancillary Control Equipment
APS Alternative Power Source
ARC Alarm Receiving Centre
ATS Alarm Transmission System
CIE Control and Indicating Equipment
HAS Hold-up Alarm System(s)
I&HAS Intrusion and Hold-up Alarm System(s)
IAS Intruder Alarm System(s)
PIR Passive Infra-Red
PS Power Supply
SPT Supervised Premises Transceiver
WD Warning Device
4 Security grade of I&HAS
The security grade of I&HAS will depend upon the performance required as determined during the risk
assessment and location survey.
An I&HAS may include I&HAS components of differing grades when divided into clearly defined
sub-systems. When I&HAS is divided into sub-systems, each sub-system may be of a different grade.
The grade of a sub-system shall be that of the lowest graded component within it.
Components shared by more than one sub-system should have a grade equal to that of the highest
sub-system grade, e.g. control and indicating equipment, alarm transmission system, warning devices
and power supplies.
4.1 Security grading
EN 50131-1:2006 describes four security grades which should be considered when selecting
equipment. These are as follows.
4.1.1 Grade 1 – Low risk
An intruder or robber is expected to have little knowledge of I&HAS and be restricted to a limited range
of easily available tools.
4.1.2 Grade 2 – Low to medium risk
An intruder or robber is expected to have a limited knowledge of I&HAS and the use of a general
range of tools and portable instruments (e.g. a multi-meter).
4.1.3 Grade 3 – Medium to high risk
An intruder or robber is expected to be conversant with I&HAS and have a comprehensive range of
tools and portable electronic equipment.

---------------------- Page: 14 ----------------------

SIST-TS CLC/TS 50131-7:2011
– 13 – CLC/TS 50131-7:2010
4.1.4 Grade 4 – High risk
To be used when security takes precedence over all other factors. An intruder or robber is expected to
have the ability or resource to plan an intrusion or robbery in detail and have a full range of equipment,
including means of substitution of components in an I&HAS.
NOTE In all grades the term “intruder” is intended to embrace other types of threat (e.g. robbery or the threat of physical
violence, which might influence the design of an I&HAS).
5 Environmental classification
The environmental class of each system component should be determined by the environmental
conditions in which the component is expected to operate.
NOTE 1 Classes I, II, III and IV are progressively more severe and therefore Class IV components may, for example, be used
in Class III I&HAS.
NOTE 2 Annex A includes special national conditions for specified countries.
EN 50131-1:2006 defines 4 environmental classes as shown below.
5.1 Environmental Class I – Indoor
Environmental influences normally experienced indoors when the temperature is well maintained (e.g.
in a residential or commercial property).
NOTE Temperatures may be expected to vary between +5 °C and +40 °C.
5.2 Environmental Class II – Indoor – General
Environmental influences normally experienced indoors when the temperature is not well maintained
(e.g. in corridors, halls or staircases and where condensation can occur on windows and in unheated
storage area
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.