Fire resistance tests for non-loadbearing elements - Part 1: Walls

This Part of EN 1364 specifies a method for determining the fire resistance of non-loadbearing walls.
This Standard is used in conjunction with EN 1363-1.
It is applicable to internal non-loadbearing walls with and without glazing, non-loadbearing walls consisting almost wholly of glazing, (glazed non-loadbearing walls) and other non-loadbearing internal and external non-loadbearing walls with and without glazing.

Feuerwiderstandsprüfungen für nichttragende Bauteile - Teil 1: Wände

Dieser Teil von EN 1364 legt ein Verfahren zur Bestimmung der Feuerwiderstandsdauer von nichttragenden
Wänden fest.
Diese Norm gilt in Verbindung mit EN 1363-1.
Sie gilt für nichttragende Innenwände mit und ohne Verglasung, nahezu vollständig aus Verglasung
bestehende nichttragende Wände (nichttragende Glaswände) sowie sonstige nichttragende Innen- und
Außenwände mit und ohne Verglasung.
Die Feuerwiderstandsdauer von nichttragenden Außenwänden kann durch Beflammung von innen oder von
außen bestimmt werden. Im letzteren Fall wird die in EN 1363-2 aufgeführte Außenbrandkurve angewendet.
Die Norm gilt nicht für:
i) Vorhangfassaden (nichttragende Außenwände, die vor Decken abgehängt werden), sofern dies
nicht ausdrücklich nach EN 1364-3, die Einzelheiten zur anzuwendenden Vorgehensweise
enthält, zulässig ist;
ii) nichttragende Wände mit Türen, die nach EN 1634-1 zu prüfen sind.
Besondere Anforderungen an die Prüfung von Verglasungen sind in Anhang A aufgeführt.

Essais de résistance au feu des éléments non porteurs - Partie 1: Murs

La présente partie de l’EN 1364 spécifie une méthode pour déterminer la résistance au feu des murs non porteurs.
La présente norme est utilisée conjointement avec l’EN 1363-1.
Elle est applicable aux murs intérieurs non porteurs, avec et sans vitrage, aux murs non porteurs constitués presque entièrement de vitrage (murs non porteurs vitrés) et aux autres murs intérieurs et extérieurs non porteurs, avec ou sans vitrage.
La résistance au feu des murs extérieurs non porteurs peut être déterminée dans des conditions d’exposition à l’intérieur ou à l’extérieur. Dans ce dernier cas, on utilise la courbe d’exposition au feu extérieur donnée dans l’EN 1363-2.
Elle ne s’applique pas :
i)   aux façades rideaux (murs extérieurs non porteurs suspendus devant la dalle de plancher), sauf si cela est explicitement autorisé par l’EN 1364-3, qui doit contenir des détails sur la méthodologie à suivre ;
ii)   aux murs non porteurs comportant des blocs-portes qui doivent être soumis à l’essai conformément à l’EN 1634-1.
Les prescriptions spécifiques se rapportant aux essais effectués sur les vitrages sont données dans l’Annexe A.

Preskusi požarne odpornosti nenosilnih elementov - 1. del: Stene

General Information

Status
Not Published
Public Enquiry End Date
30-Jan-2012
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
14-Feb-2014
Due Date
19-Feb-2014
Completion Date
14-Feb-2014

Relations

Buy Standard

Draft
prEN 1364-1:2012
English language
44 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 1364-1:2012
01-januar-2012
Preskusi požarne odpornosti nenosilnih elementov - 1. del: Stene
Fire resistance tests for non-loadbearing elements - Part 1: Walls
Feuerwiderstandsprüfungen für nichttragende Bauteile - Teil 1: Wände
Essais de résistance au feu des éléments non porteurs - Partie 1: Murs
Ta slovenski standard je istoveten z: prEN 1364-1 rev
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.10 Stene. Predelne stene. Walls. Partitions. Facades
Fasade
oSIST prEN 1364-1:2012 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 1364-1:2012

---------------------- Page: 2 ----------------------
oSIST prEN 1364-1:2012


EUROPEAN STANDARD
DRAFT
prEN 1364-1 rev
NORME EUROPÉENNE

EUROPÄISCHE NORM

October 2011
ICS 13.220.50; 91.060.10 Will supersede EN 1364-1:1999
English Version
Fire resistance tests for non-loadbearing elements - Part 1:
Walls
Essais de résistance au feu des éléments non porteurs - Feuerwiderstandsprüfungen für nichttragende Bauteile -
Partie 1: Murs Teil 1: Wände
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2011 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1364-1 rev:2011: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
Contents Page
Foreword .4
Introduction .5
1 Scope .6
2 Normative references .6
3 Definitions .6
4 Test equipment .8
5 Test conditions .8
6 Test specimen .8
6.1 Size .8
6.2 Number .8
6.3 Design .9
6.3.1 General .9
6.3.2 Restraint . 10
6.4 Construction . 10
6.5 Verification . 10
7 Installation of test specimen . 10
7.1 General . 10
7.2 Standard supporting construction. 10
7.3 Non-standard supporting construction . 11
8 Conditioning . 11
9 Application of instrumentation . 11
9.1 Thermocouples . 11
9.1.1 Furnace thermocouples (plate thermometers) . 11
9.1.2 Unexposed face thermocouples . 11
9.2 Pressure . 12
9.3 Deflection . 12
9.4 Radiation . 12
9.5 Impact . 12
10 Test procedure . 12
11 Performance criteria . 13
12 Test report . 13
13 Field of direct application of test results . 13
13.1 General . 13
13.2 Extension of width . 13
13.3 Extension of height. 14
13.4 Supporting constructions . 14
13.4.1 Standard supporting constructions. 14
Annex A - (normative) Specific requirements for testing glazed elements or non loadbearing walls
incorporating glazing . 15
A.1 General . 15
A.2 Test specimen design . 15
A.3 Test specimen instrumentation . 16
A.3.1 General . 16
A.3.2 Average temperature rise . 16
2

---------------------- Page: 4 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
A.3.3 Maximum temperature rise . 16
A.3.4 Radiation measurement . 17
A.3.5 Deflection measurement . 17
A.4 Performance criteria . 17
A.4.1 Integrity. 17
A.4.2 Insulation . 17
A.5 Field of direct application of test results . 18
A.5.1 General . 18
A.5.2 Field of direct application rules not requiring overrun time . 18
A.5.3 Field of direct application rules requiring overrun time . 20
Annex B (normative) Specific requirements for testing non loadbearing external and internal
walls designed to span horizontally between two independently proven fire resisting
vertical structural elements . 23
B.1 General . 23
B.2 Test specimen . 23
B.2.1 Size . 23
B.2.2 Number . 23
B.2.3 Design . 23
B.2.4 Boundary and Restraint conditions . 23
B.3 Test specimen instrumentation . 24
B.4 Test procedure . 24
B.5 Performance criteria . 24
B.6 Field of direct application of test results . 24
B.6.1 General . 24
B.6.2 Supporting constructions. 25
B.6.3 Extension of width . 25
B.6.4 Extension of height . 25

3

---------------------- Page: 5 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
Foreword
This document (prEN 1364-1:2011) has been prepared by Technical Committee CEN/TC 127 “Fire safety in
buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 1364-1:1999.
EN 1364 ‘Fire resistance tests for non-loadbearing elements’ consists of the following
Part 1: Walls
Part 2: Ceilings
Part 3: Curtain walls - full configuration
Part 4: Curtain walls - part configuration
4

---------------------- Page: 6 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
Introduction
The purpose of this test is to measure the ability of a representative specimen of a non-loadbearing wall to
resist the spread of fire from one side to another.
It is applicable to non-loadbearing walls, with and without glazing, non-loadbearing walls consisting almost
wholly of glazing and other non-loadbearing internal and external non-loadbearing walls.
It is not applicable to curtain walls (external non-loadbearing walls suspended in front of the floor slab) which
are dealt with specifically in EN 1364-3.
For external fire exposure to a non-loadbearing external wall, the external fire exposure curve given in EN
1363-2 is used.

Caution
The attention of all persons concerned with managing and carrying out this fire resistance test is drawn to the
fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful smoke and
gases may be evolved during the test. Mechanical and operational hazards may also arise during the
construction of the test elements or structures, their testing and disposal of test residues.
An assessment of all potential hazards and risks to health shall be made and safety precautions shall be
identified and provided. Written safety instructions shall be issued. Appropriate training shall be given to
relevant personnel. Laboratory personnel shall ensure that they follow written safety instructions at all times.
5

---------------------- Page: 7 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
1 Scope
This Part of EN 1364 specifies a method for determining the fire resistance of non-loadbearing walls.
This Standard is used in conjunction with EN 1363-1.
It is applicable to internal non-loadbearing walls with and without glazing, non-loadbearing walls consisting
almost wholly of glazing, (glazed non-loadbearing walls) and other non-loadbearing internal and external non-
loadbearing walls with and without glazing.
The fire resistance of external non-loadbearing walls can be determined under internal or external exposure
conditions. In the latter case the external fire exposure curve given in EN 1363-2 is used.
It is not applicable to:
i) curtain walls (external non-loadbearing walls suspended in front of the floor slab), unless explicitly
permitted under EN 1364-3 which shall contain details of the methodology to be used.
ii) non-loadbearing walls containing door assemblies which shall be tested to EN 1634-1.
Specific requirements relating to the testing of glazing are given in annex A.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 1363-1 Fire resistance tests Part 1: General requirements
EN 1363-2 Fire resistance tests Part 2: Alternative and additional procedures
EN 1364-3 Fire resistance tests for non-loadbearing elements - Part 3: Curtain walls - full configuration
EN 1634-1 Fire resistance tests for door and shutter assemblies - Part 1: Fire doors and shutters
EN ISO 13943 Fire safety - Vocabulary (ISO/DIS 13943:2008)
3 Definitions
For the purposes of this Part of EN 1364, the definitions given in EN 1363-1 and EN ISO 13943, together with
the following, apply:
3.1 non-loadbearing wall

A wall designed not to be subject to any load other than its self-weight.
3.2 internal non-loadbearing wall
A wall, with or without glazing, which provides fire separation. It may be exposed separately to a fire from
either side.

6

---------------------- Page: 8 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
3.3 external non-loadbearing wall
A wall forming the external envelope of a building which may be exposed separately to an internal or an
external fire.
3.4 insulated non-loadbearing wall
A wall, with or without glazing, which satisfies both the integrity and insulation criteria for the anticipated fire
resistance period.
3.5 uninsulated non-loadbearing wall
A wall which satisfies the integrity and, where required, the radiation criteria for the anticipated fire resistance
period, but which is not intended to provide insulation. Such a non-loadbearing wall may consist entirely of
uninsulated fire resistant glazing.
3.6 fire resistant glazing
A glazing system consisting of one or more transparent or translucent panes with a suitable method of
mounting, with e.g frames, seals, fixing materials etc, capable of satisfying the appropriate fire resistance
criteria.
3.7 insulated glazing
Fire resistant glazing which satisfies both the integrity and insulation criteria for the anticipated fire resistance
period.
3.8 uninsulated glazing
Fire resistant glazing which satisfies the integrity and, where required, the radiation criteria for the anticipated
fire resistance period but which is not intended to provide insulation.
3.9 glazed elements
Building elements with one or more (light transmissive) panes, that are built in a frame with fixings and seals.
3.10 pane
A single piece of monolithic or laminated glass, or an insulated glass unit (IGU).
3.11 glazing system
Glass and glazing materials used in the fire test to glaze the glass into its framing system, e.g. glazing strips,
beads and bead fixings, setting blocks, gaskets, sealant (see Figure 16).
3.12 butt-joint(ed) glazing
A glazing configuration where adjoining panes are connected without the use of framing profiles at the glass to
glass joint.
3.13 framing system
Frame profiles and fixings to the supporting structure (e.g. wall) (see Figure 16).
3.14 aspect ratio
The ratio of the height of a pane to its width.
7

---------------------- Page: 9 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
3.15 mullion
A vertical framing member separating and supporting two adjacent panes of glass or panels.
3.16 transom
A horizontal framing member separating and supporting two adjacent panes of glass or panels.
3.17 standard supporting construction
A form of construction used to close off the furnace and to support the non-loadbearing wall being evaluated
and which has known resistance to thermal distortion.
3.18 plinth
A form of standard supporting construction that reduces the height of the opening by raising the support base
to accommodate the test specimen.
3.19 overrun time
Period of fire resistance in minutes beyond the intended classification period achieved in the test.

4 Test equipment
In addition to the test equipment specified in EN 1363-1, and if applicable EN 1363-2, the following is required:
A test frame shall be provided, the rigidity of which shall be evaluated by applying an expansion force within
the frame at mid-way between two opposite members of the frame, and measuring the increase in the internal
dimensions at these positions. This evaluation shall be conducted in both directions of the frame and the
increase of the internal dimension shall be measured.
The increase in the internal dimensions of the test frame shall not exceed 5 mm with an applied force of
25 kN. In case of testing with a free edge, this requirement does not apply for the horizontal dimension.
5 Test conditions
The heating and pressure conditions and the furnace atmosphere shall conform to those given in EN 1363-1
or if applicable, EN 1363-2.
6 Test specimen
6.1 Size
If, in practice, the height or width of the construction is 3m or smaller, then that dimension of the test specimen
shall be tested at full size. If any dimension of the construction is greater than 3m, then that dimension shall
be tested at not less than 3m.
6.2 Number
The number of test specimens shall be as given in EN 1363-1. However, where information is required under
different exposure conditions or where the construction is to be evaluated with and without glazing, additional
tests shall be undertaken for each situation using separate test specimens.
8

---------------------- Page: 10 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
6.3 Design
6.3.1 General
The test specimen shall be either:
a) fully representative of the construction intended for use in practice, including any surface
finishes and fittings which are essential and may influence its behaviour in the test,
or,
b) be designed to obtain the widest applicability of the test result to other similar constructions.
The design features which influence fire performance that should be included to give the widest application
can be derived from the field of direct application, clause 13.
Guidance on testing glazed elements or non-loadbearing walls incorporating glazing is given in annex A.
Guidance on testing non-loadbearing external and internal walls designed to span horizontally between two
independently proven fire resisting vertical structural elements is given in annex B.
6.3.1.1 Vertical joints
The test specimen shall contain as many full width boards as possible. Where the test specimen can
incorporate at least two full width boards, the free edge shall be adjacent to a full sized board on the exposed
face. (see figure 1, case A) When it is not possible to incorporate two full sized boards into the test specimen,
the single full sized board shall be located in the centre of the specimen, with smaller boards of equal width on
each side. The smaller boards shall not be less than 500 mm wide. (see figure 1, case B) Where the smaller
boards would be less than 500 mm wide, only one shall be used next to the free edge of the specimen. (see
figure 1, case C).
Note: The test specimen should be designed to obtain the widest applicability of the test result when
considered in conjunction with the direct and extended field of application rules. Some design features
which influence fire performance that should be included can be derived from the field of direct
application, clause 13.
The test specimen shall only contain a mixture of different designs providing this is representative of end use
applications.
If the element incorporates vertical joints in practice, then the test specimen shall incorporate a vertical joint.
This joint shall be located between 350mm and 650mm in from the free edge and shall be on the outer layer
of the unexposed face.(see figure 1, case D). If joints may not be staggered, figure 1, case A prevails.
6.3.1.2 Horizontal joints
If the element incorporates horizontal joints in practice, then the test specimen shall incorporate a horizontal
joint. This joint shall be located between 350mm and 650mm in from the top edge and shall be on the outer
layer on the unexposed face.
Note: Test specimens can incorporate both horizontal and vertical joints in the same test. If large dimension
boards e.g. 3m high are used in practice, then this will necessitate two tests for a 3m x 3m furnace: one
test to evaluate the effect of joints and another to evaluate the full height board. An alternative is to use
a 4m high (or more) furnace in which both the full height board together with the joints at the specified
locations can be incorporated in one test.
9

---------------------- Page: 11 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
6.3.2 Restraint
When, in practice the test specimen is not larger than the front opening of the furnace, then the edges of the
test specimen shall be restrained as in practice. Where, in practice the width of the construction is larger than
the front opening of the furnace, one vertical edge shall be left unrestrained and there shall be a gap of 25mm
to 50mm between the free edge of the test specimen and the test frame. This gap shall be packed with a
resilient non-combustible material, e.g. mineral fibre, to provide a seal without restricting freedom of
movement. The remaining edges shall be restrained as in practice.
Any construction including any sealing of the free edge shall respect the following principles:
a) prevent as far as possible the leakage of hot gases from the furnace into the test specimen;
b) prevent as far as possible the leakage of gasses out of the test specimen;
c) have as minimal effect as possible on the deformations of the test specimen;
d) have as minimal effect as possible on the insulation rating of the test specimen.
6.4 Construction
The test specimen shall be constructed as described in EN 1363-1.
6.5 Verification
Verification of the test specimen shall be carried out as described in EN 1363-1.
7 Installation of test specimen
7.1 General
The test specimen shall be installed in the test frame and, if used, the supporting construction, as in practice.
The whole area of the test construction shall be exposed to the heating conditions.
7.2 Standard supporting construction
If the size of the test specimen is smaller than the opening in the test frame then it shall be installed in the test
frame using one of the following approaches:
a) Where the height of the test specimen is smaller than the height of the test frame opening,
then a plinth shall be provided to reduce the opening to the required height. The plinth shall
possess sufficient stability for the test specimen and shall be selected from one of the rigid
standard supporting constructions in EN 1363-1.
b) Where the width of the test specimen is smaller, a standard supporting construction shall be
provided on the vertical sides of the opening selected from either the rigid or flexible standard
supporting constructions given in EN 1363-1.
10

---------------------- Page: 12 ----------------------
oSIST prEN 1364-1:2012
prEN 1364-1:2011 (E)
7.3 Non-standard supporting construction
If the test specimen is mounted in a supporting construction not given in EN 1363-1, then the result will only
be valid for non-loadbearing walls mounted in the construction as tested.
8 Conditioning
The test construction shall be conditioned in accordance with EN 1363-1.
9 Application of instrumentation
9.1  Thermocouples
9.1.1 Furnace thermocouples (plate thermometers)
Plate thermometers shall be provided in accordance with EN 1363-1. There shall be at least one for every 1,5
2
m of the area of the plane parallel to the exposed surface area of the test construction. The plate
thermometers shall be oriented so that side ‘A’ faces the back wall of the furnace.
9.1.2 Unexposed face thermocouples
9.1.2.1 General
For uninsulated non-loadbearing walls, glazed or unglazed, the temperature of the unexposed face is not
required to be measured and no thermocouples are therefore required to be attached.
For walls with an anticipated insulation performance, thermocouples of the type specified in EN 1363-1 shall
be attached to the unexposed face for the purpose of obtaining the average and the maximum surface
temperatures. Examples of location of unexposed face thermocouples are given in figures 2 to 15.
General rules for the attachment and exclusion of thermocouples given in EN 1363-1 shall apply.
Unexposed surface thermocouples may be placed on the test specimen at any angle and do not need to be
p
...