Extended application of results from fire resistance tests - Non-loadbearing walls - Part 6: Curtain walling

EN 15254-6 provides guidance and, where appropriate, defines procedures for variations of certain parameters and factors associated with the design of curtain walls according to EN 13830 which have been tested in accordance with EN 1364-3 and classified according to EN 13501-2 (curtain wall type B according to 3.2), components of curtain walls type A or type B according to 3.1 and 3.2, e.g. spandrel panels, which have been tested in accordance with EN 1364-4, and classified according to EN 13501-2.

Erweiterter Anwendungsbereich der Ergebnisse von Feuerwiderstandsprüfungen - Nichttragende Wände - Teil 6: Vorhangfassaden

Diese Europäische Norm enthält eine Anleitung und definiert gegebenenfalls Verfahren für Änderungen bestimmter Parameter und Faktoren, die die Bemessung von Folgendem betreffen: Vorhangfassaden nach EN 13830, die nach EN 1364 3 geprüft und nach EN 13501 2 klassifiziert wurden (Vorhangfassaden vom Typ B nach 3.2) sowie Bauteile von Vorhangfassaden vom Typ A oder Typ B nach 3.1 und 3.2, z. B. Brüstungsausfachungen, die nach EN 1364 4 geprüft und nach EN 13501 2 klassifiziert wurden.

Application étendue des résultats d'essais de résistance au feu - Murs non porteurs - Partie 6: Façades rideaux

La présente Norme européenne fournit des lignes directrices et, le cas échéant, définit des modes opératoires pour les variations de certains paramètres et facteurs associés à la conception des façades rideaux conformes à l'EN 13830 qui ont été soumises à essai conformément à l'EN 1364-3 et classées conformément à l'EN 13501-2 (façades rideaux de type B conformément à 3.2) et des composants de façades rideaux de type A ou de type B conformément à 3.1 et 3.2, par exemple panneaux d'allège, qui ont été soumis à essai conformément à l'EN 1364-4 et classés conformément à l'EN 13501-2.

Razširjena uporaba rezultatov preskusov požarne odpornosti - Nenosilne stene - 6. del: Obešene fasade

General Information

Status
Published
Public Enquiry End Date
30-Jan-2012
Publication Date
09-Feb-2014
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
30-Jan-2014
Due Date
06-Apr-2014
Completion Date
10-Feb-2014

Buy Standard

Standard
EN 15254-6:2014
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Razširjena uporaba rezultatov preskusov požarne odpornosti - Nenosilne stene - 6. del: Obešene fasadeErweiterter Anwendungsbereich der Ergebnisse von Feuerwiderstandsprüfungen - Nichttragende Wände - Teil 6: VorhangfassadenApplication étendue des résultats d'essais de résistance au feu - Murs non porteurs - Partie 6: Façades rideauxExtended application of results from fire resistance tests - Non-loadbearing walls - Part 6: Curtain walling91.060.10Stene. Predelne stene. FasadeWalls. Partitions. Facades13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 15254-6:2014SIST EN 15254-6:2014en,fr,de01-marec-2014SIST EN 15254-6:2014SLOVENSKI
STANDARD



SIST EN 15254-6:2014



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15254-6
January 2014 ICS 13.220.50; 91.060.10 English Version
Extended application of results from fire resistance tests - Non-loadbearing walls - Part 6: Curtain walling
Application étendue des résultats d'essais de résistance au feu - Murs non porteurs - Partie 6: Murs rideaux
Erweiterter Anwendungsbereich der Ergebnisse von Feuerwiderstandsprüfungen - Nichttragende Wände - Teil 6: Vorhangfassaden This European Standard was approved by CEN on 9 November 2013.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2014 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15254-6:2014 ESIST EN 15254-6:2014



EN 15254-6:2014 (E) 2 Contents Page Foreword .3 1 Scope .4 2 Normative references .4 3 Terms and definitions .4 4 Principles .5 4.1 General principles.5 4.2 Use of test evidence .5 4.3 Analysis of test results .5 5 General rules .5 5.1 Fire resistance classification .5 5.2 Combination of extended application.5 5.3 Overrun time .5 6 Specific rules for curtain walling type B .6 6.1 General .6 6.2 Rules for the complete construction .6 6.3 Framing system .7 6.4 Fire resistant translucent or transparent infill panels .8 7 Specific rules for curtain walling type A .9 7.1 General .9 7.2 Rules for the complete construction .9 7.3 Framing system . 10 7.4 Fire resistant translucent or transparent infill panels . 10 8 Report of the extended application analysis . 10 8.1 Contents of the extended application report . 10 8.2 Review of the extended application report . 11 Annex A (normative)
Radiation calculation . 14 A.1 General . 14 A.2 Rectangular fire resistant translucent or transparent infill panels . 14 A.3 Circular fire resistant translucent or transparent infill panels . 15 A.4 Other shapes of fire resistant translucent or transparent infill panels with EW-classification . 15
SIST EN 15254-6:2014



EN 15254-6:2014 (E) 3 Foreword This document (EN 15254-6:2014) has been prepared by Technical Committee CEN/TC 127 “Fire Safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by July 2014, and conflicting national standards shall be withdrawn at the latest by July 2014. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of 89/106/EEC. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 15254-6:2014



EN 15254-6:2014 (E) 4 1 Scope This European Standard provides guidance and, where appropriate, defines procedures for variations of certain parameters and factors associated with the design of curtain walling according to EN 13830 which have been tested in accordance with EN 1364-3 and classified according to EN 13501-2 (curtain walling type B according to 3.2), components of curtain walling type A or type B according to 3.1 and 3.2, e.g. spandrel panels, which have been tested in accordance with EN 1364-4, and classified according to EN 13501-2. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1, Fire resistance tests - Part 1: General Requirements EN 1363-2, Fire resistance tests - Part 2: Alternative and additional procedures EN 1364-3:2014, Fire resistance tests for non-loadbearing elements — Part 3: Curtain walling — Full configuration (complete assembly) EN 1364-4:2014, Fire resistance tests for non-loadbearing elements — Part 4: Curtain walling — Part configuration EN 13119, Curtain walling - Terminology EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification using data from fire resistance tests, excluding ventilation services EN 13830, Curtain walling - Product standard EN ISO 13943, Fire safety - Vocabulary (ISO 13943) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1, EN 1363-2, EN 1364-3,
EN 1364-4, EN 13119, EN 13830, EN ISO 13943 and the following apply. 3.1 curtain walling Type A for definition see EN 1364-3 3.2 curtain walling Type B for definition see EN 1364-3 3.3 vertically faceted curtain walling curtain walling with a vertical and a sloped part without fixing/bracket at the joint (see Figure 1) SIST EN 15254-6:2014



EN 15254-6:2014 (E) 5 4 Principles 4.1 General principles Extended application is a prediction of the expected fire resistance performance of a fire resistant curtain walling or its components. It may be based either on interpolation between or extrapolation from test data according to EN 1364-3 and/or EN 1364-4. Curtain walling function as integral systems in which the individual components (e.g. frames and fixing of the framing system (anchoring), infill panels, perimeter seals and vertical linear gap seals) are combined in such a way that they are effective in meeting the defined fire resistance criteria. In this document in addition to rules for the complete construction rules are defined for the components of curtain walling which are separately characterised as the framing system, the fixing of the framing system (anchoring), the infill panels and its fixing methods, the perimeter seal and the vertical linear gap seals as well as the supporting construction (floor and walls). 4.2 Use of test evidence The applicant for the extended application shall either be the “owner” (i.e. sponsor) of all test data being submitted for the extension, or have written permission from the owner to use the submitted test evidence. 4.3 Analysis of test results In order to maximise the extended field of application, it is important that the test reports shall record details of any premature integrity and / or insulation failure. Where a series of tests have been conducted, the field of extended application shall be based on the lowest performance achieved from the complete series of tests unless premature failure has been attributed to one or more specific construction parameter variations. Where it has been possible, to identify specific parameter failures, the extended application for all other construction parameter variations can be based on the performance achieved after isolating the premature failure(s). 5 General rules 5.1 Fire resistance classification In the extended application, an increase in the classification time (e.g. from 30 min to 45 min) and changes to the fire resistance classification (e.g. from E to EW to EI) are not permitted. 5.2 Combination of extended application Each extended application shall be the subject of a separate evaluation. Within this application it is allowed to produce a combination of extensions provided these combinations can be substantiated by the supporting test evidence. 5.3 Overrun time For some rules to be applicable an overrun time in the fire test result compared to the envisaged classification time is required. The required overrun time is shown in Table 1. The overrun time is required for the following criteria: — E classification: integrity SIST EN 15254-6:2014



EN 15254-6:2014 (E) 6 — EW classification: integrity and radiation — EI classification: integrity and insulation Table 1 – Overrun time Classification Time Overrun time ≤ 20 min minimum 3 min 30, 45 and 60 min minimum 6 min ≥ 90 min minimum 10 % of the classification time 6 Specific rules for curtain walling type B 6.1 General Minimum one test according to EN 1364-3 is required. The assessment of the extended field of application may be based on additional test results from EN 1364-4 or EN 1364-3. The rules given in 6.2 to 6.4 apply to stick constructions only except where stated otherwise. Rules which result in higher weight of the curtain walling are only applicable if the fixing of the framing system used in practice has been designed for the higher load. The measured temperature at the fixing of the framing system shall be taken into account. 6.2 Rules for the complete construction 6.2.1 Width for curtain walling with classification EW Test results are also valid for curtain walling with classification EW extending over one or more fire separating walls with a higher distance between the fire separating walls than the width of the tested construction if in addition to the criteria given in EN 1364-3 the radiation criterion is fulfilled for the resulting larger area. The radiation criterion shall be assessed using the rules given in A.1. The result of a calculation for a width equalling three times the tested width or minimum 9 m, whatever is larger, is applicable to any larger width. An increase in width is only permitted by replicating the tested construction (especially type and dimensions of infill panels) in the same arrangement as tested. 6.2.2 Span length for curtain walling with classification EW Test results are also valid for curtain walling with classification EW for a higher span length than used in the test if in addition to the criteria given in EN 1364-3 the radiation criterion is fulfilled for the resulting larger area. The radiation criterion shall be assessed using the rules given in A.1. This rule applies also to unitised constructions. 6.2.3 Installation angle (vertical/sloped) Test results cover all installation angles between the maximum and minimum angle used in tests. This rule applies also to unitised constructions. 6.2.4 Vertically faceted curtain walling Test results cover all angles between vertically adjacent infill panels between the maximum and minimum angle used in tests. This rule applies also to unitised constructions. SIST EN 15254-6:2014



EN 15254-6:2014 (E) 7 6.2.5 Horizontally faceted curtain walling For corners and facet angles not covered by the rules given in EN 1364-3 the following rules apply: EI classification: Results from tests of faceted specimens according to EN 1364-3 using the test configurations A and B or alternatively E as illustrated in EN 1364-3:2014, Figure 8 and from minimum one test of a straight specimen cover all angles between horizontally adjacent infill panels at the common mullion from 45° to 315° (see Figure 2) with classification EI (o < i). E, EW classification: Results from tests of faceted specimens according to EN 1364-3 using the test configurations A, B, C and D or alternatively E and F as illustrated in EN 1364-3:2014, Fi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.