Copper and copper alloys - Seamless, round copper tubes for water and gas in sanitary and heating applications

This European Standard specifies the requirements, sampling, test methods and conditions of delivery for seamless round copper tubes. It is applicable to tubes having an outside diameterr from 6 mm up to and including 267 mm for: distributing networks for hot water and cold water; hot water heating systems, including panel heating systems (under-floor, wall, overhead); domestic gas and liquid fuel distribution; waste water sanitation. It is also applicable to seamless round copper tubes intended to be pre-insulated before use for any of the above purposes. In comparison with the first edition of EN 1057:1996, the following significant technical changes were made: harmonization of the standard to the Construction Product Directive (CPD) and to the Pressure Equipment Directive (PED); introduction of two new definitions: "permanently marked" and "durably marked"; updating of the definitions regarding soldering, brazing, fusion welding, braze welding and mean diameter; introduction of five new items in Clause 5 "Ordering information" regarding options on tests and documents; due to the process of harmonization to the CPD, introduction of three new characteristics in Clause 6 "Material characteristics" inherent to copper material which are not to be tested; modification of Table 3 "Standardized dimensions"; simplification of Table 6 "Quantitative and qualitative specification for carbon residues": Suppression of the residual and potential carbon and application of the thresholds to the total carbon; text in Clause 8 "Evaluation of conformity" added due to the process of harmonization to the CPD; for permanent and durable markings, specification of their applicability in 12.1 "Marking"; modification of the table in Annex A, introduction of new diameters and wall thicknesses; due to the process of harmonization to the CPD and PED introduction of Annexes ZA and ZB.

Kupfer und Kupferlegierungen - Nahtlose Rundrohre aus Kupfer für Wasser- und Gasleitungen für Sanitärinstallationen und Heizungsanlagen

Diese Europäische Norm legt die Anforderungen, Probenentnahme, Prüfverfahren und Lieferbedingungen für
nahtlose Rundrohre aus Kupfer fest.
Sie gilt für Rohre mit einem Außendurchmesser von 6 mm bis 267 mm für:
- Kalt- und Warmwasser-Verteilungsnetze;
- Warmwasser-Heizungssysteme, einschließlich Fußboden-, Wand- oder Deckenheizungssysteme;
- Verteilung gasförmiger und flüssiger Hausbrennstoffe;
- Abwasserentsorgung.
Sie gilt auch für nahtlose Rundrohre aus Kupfer, die zum Vorummanteln vor dem Einsatz für alle oben-genannten
Zwecke bestimmt sind.

Cuivre et alliages de cuivre - Tubes ronds sans soudure en cuivre pour l'eau et le gaz dans les applications sanitaires et de chauffage

La présente Norme européenne établit les exigences, le mode d'échantillonnage, les méthodes d'essai et les conditions de livraison applicables aux tubes ronds sans soudure en cuivre.
Elle s'applique aux tubes de diametre extérieur compris entre 6 mm et 267 mm inclus, destinés :
-   a la distribution d'eau chaude et d'eau froide ;
-   au chauffage a eau chaude, y compris les systemes de panneaux chauffants (par le sol, par les murs ou par le plafond) ;
-   a la distribution de gaz domestique et de combustibles liquides ;
-   a l'évacuation des eaux usées.
Elle s'applique également aux tubes en cuivre ronds sans soudure en cuivre destinés a etre gainés avant utilisation pour l'une des applications ci-dessus.

Baker in bakrove zlitine - Nevarjene (narejene iz celega) bakrene cevi z okroglim prerezom za vodo in plin, ki se uporabljajo za sanitarne in ogrevalne namene

General Information

Status
Withdrawn
Publication Date
30-Jun-2006
Withdrawal Date
28-Feb-2010
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
01-Mar-2010
Due Date
24-Mar-2010
Completion Date
01-Mar-2010

Relations

Buy Standard

Standard
EN 1057:2006
English language
37 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Baker in bakrove zlitine - Nevarjene (narejene iz celega) bakrene cevi z okroglim prerezom za vodo in plin, ki se uporabljajo za sanitarne in ogrevalne nameneKupfer und Kupferlegierungen - Nahtlose Rundrohre aus Kupfer für Wasser- und Gasleitungen für Sanitärinstallationen und HeizungsanlagenCuivre et alliages de cuivre - Tubes ronds sans soudure en cuivre pour l'eau et le gaz dans les applications sanitaires et de chauffageCopper and copper alloys - Seamless, round copper tubes for water and gas in sanitary and heating applications77.150.30Bakreni izdelkiCopper products23.040.15Cevi iz neželeznih kovinNon-ferrous metal pipesICS:Ta slovenski standard je istoveten z:EN 1057:2006SIST EN 1057:2006en01-julij-2006SIST EN 1057:2006SLOVENSKI
STANDARDSIST EN 1057:19981DGRPHãþD



SIST EN 1057:2006



EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 1057May 2006ICS 23.040.15Supersedes EN 1057:1996
English VersionCopper and copper alloys - Seamless, round copper tubes forwater and gas in sanitary and heating applicationsCuivre et alliages de cuivre - Tubes ronds sans soudure encuivre pour l'eau et le gaz dans les applications sanitaireset de chauffageKupfer und Kupferlegierungen - Nahtlose Rundrohre ausKupfer für Wasser- und Gasleitungen fürSanitärinstallationen und HeizungsanlagenThis European Standard was approved by CEN on 23 March 2006.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2006 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 1057:2006: ESIST EN 1057:2006



EN 1057:2006 (E) 2 Contents Page Foreword.4 Introduction.6 1 Scope.7 2 Normative references.7 3 Terms and definitions.8 4 Designations.9 4.1 Material.9 4.1.1 General.9 4.1.2 Symbol.9 4.1.3 Number.9 4.2 Material condition.9 4.3 Product.9 5 Ordering information.10 6 Material characteristics.11 6.1 Safety in case of fire – Reaction to fire.11 6.2 Properties at high temperature.11 6.3 Weldability.11 7 Requirements.11 7.1 Composition.11 7.2 Mechanical properties.11 7.3 Dimensions and tolerances.14 7.3.1 General.14 7.3.2 Nominal dimensions.14 7.3.3 Tolerances on outside diameter.15 7.3.4 Tolerances on wall thickness.16 7.3.5 Tolerances on length.16 7.4 Freedom from defects.17 7.5 Surface quality.17 7.6 Bending.17 7.7 Drift expanding.17 7.8 Flanging.17 8 Evaluation of conformity.18 8.1 General.18 8.2 Type testing.18 8.2.1 Initial type testing.18 8.2.2 Sampling, testing and conformity criteria.19 8.3 Factory production control (FPC).19 8.3.1 General.19 8.3.2 General FPC requirements.20 8.3.3 Manufacturer-specific FPC system requirements.20 9 Sampling.21 10 Test methods.22 10.1 Analysis.22 10.2 Tensile test.22 10.3 Hardness test.22 10.4 Carbon content test.22 10.5 Carbon film test.22 10.6 Bending test.22 10.7 Drift-expanding test.23 10.8 Flanging test.23 10.9 Freedom from defects tests.24 10.10 Retests.24 SIST EN 1057:2006



EN 1057:2006 (E) 3 11 Inspection documentation.24 12 Marking and form of delivery.24 12.1 Marking.24 12.2 Form of delivery.25 Annex A (normative)
Standardized dimensions for reconsideration at a future revision.26 Annex B (normative)
Carbon film test.27 B.1 Preparation of the test piece.27 B.2 Procedure.27 B.3 Detection and assessment of films.27 Annex C (normative)
Freedom from defects tests.28 C.1 Eddy current test.28 C.2 Hydrostatic test.28 C.3 Pneumatic test.28 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive (CPD) 89/106/EEC.30 ZA.1 Scope and relevant characteristics.30 ZA.2 Procedure(s) for attestation of conformity of pipes.32 ZA.2.1 System(s) of attestation of conformity.32 ZA.2.2 EC Certificate and Declaration of conformity.33 ZA.3 CE marking and labelling.34 Annex ZB (informative)
Relationship between this European Standard and the Essential Requirements of the EU Pressure Equipment Directive (PED) 97/23/EC.36 Bibliography.37
Tables Table 1 — Mechanical properties.12 Table 2 — Minimal elongation values for R250 (half hard) material condition tubes.13 Table 3 — Standardized dimensions.15 Table 4 — Tolerances on outside diameter.16 Table 5 — Tolerances on wall thickness.16 Table 6 — Quantitative and qualitative specification for carbon residues.17 Table 7 — Testing of
bending, drift expanding and flanging.18 Table 8 — Sampling rate.21 Table 9 — Minimum radius of curvature.23 Table 10 — Recommended form of delivery.25 Table A.1 — Standardized dimensions for reconsideration at a future revision.26 Table C.1 — Maximum drill diameters for the reference standard tube.28 Table C.2 — Hydraulic pressure test.28 Table ZA.1 — Relevant clauses.31 Table ZA.2 — Systems of attestation of conformity.32 Table ZA.3.1 — Assignment of evaluation of conformity tasks for pipes under system 3 — 1/5.33 Table ZA.3.2 — Assignment of evaluation of conformity tasks for pipes under system 4 — 2/5.33 Table ZB.1 — Correspondence between this European Standard and Directive 97/23/EC.36
SIST EN 1057:2006



EN 1057:2006 (E) 4 Foreword This document (EN 1057:2006) has been prepared by Technical Committee CEN/TC 133 “Copper and copper al-loys”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by November 2006, and conflicting national standards shall be withdrawn at the latest by February 2008. This document supersedes EN 1057:1996. Within its programme of work, Technical Committee CEN/TC 133 requested CEN/TC 133/WG 3 "Copper tubes (installation and industrial)" to prepare the revision of the following standard: EN 1057:1996, Copper and copper alloys — Seamless, round copper tubes for water and gas in sanitary and
heating applications This document has been prepared within the framework of two mandates given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of the
EU Construction Products Directive (CPD) 89/106/EEC and the EU Pressure Equipment Directive (PED) 97/23/EC. For relationship with EU Directives, see informative Annexes ZA and ZB, which are integral parts of this document. In comparison with the first edition of EN 1057:1996, the following significant technical changes were made:  harmonization of the standard to the Construction Product Directive (CPD) and to the Pressure Equipment
Directive (PED);  introduction of two new definitions: "permanently marked" and "durably marked";  updating of the definitions regarding soldering, brazing, fusion welding, braze welding and mean diameter;  introduction of five new items in Clause 5 "Ordering information" regarding options on tests and documents;  due to the process of harmonization to the CPD, introduction of three new characteristics in Clause 6 "Material characteristics" inherent to copper material which are not to be tested;  modification of Table 3 "Standardized dimensions";  simplification of Table 6 "Quantitative and qualitative specification for carbon residues": Suppression of the residual and potential carbon and application of the thresholds to the total carbon;  text in Clause 8 "Evaluation of conformity" added due to the process of harmonization to the CPD;  for permanent and durable markings, specification of their applicability in 12.1 "Marking";  modification of the table in Annex A, introduction of new diameters and wall thicknesses;  due to the process of harmonization to the CPD and PED introduction of Annexes ZA and ZB. This is one of a series of European Standards for copper and copper alloy tubes. Other products are specified as
follows: EN 12449, Copper and copper alloys — Seamless, round tubes for general purposes EN 12450, Copper and copper alloys — Seamless, round copper capillary tubes EN 12451, Copper and copper alloys — Seamless, round tubes for heat exchangers SIST EN 1057:2006



EN 1057:2006 (E) 5 EN 12452, Copper and copper alloys — Rolled, finned, seamless tubes for heat exchangers EN 12735-1, Copper and copper alloys — Seamless, round copper tubes for air conditioning and refrigeration — Part 1: Tubes for piping systems EN 12735-2, Copper and copper alloys — Seamless, round copper tubes for air conditioning and refrigeration — Part 2: Tubes for equipment EN 13348, Copper and copper alloys — Seamless, round copper tubes for medical gases or vacuum EN 13349, Copper and copper alloys — Pre-insulated copper tubes with solid covering EN 13600, Copper and copper alloys — Seamless copper tubes for electrical purposes According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following coun-tries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Esto-nia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
SIST EN 1057:2006



EN 1057:2006 (E) 6 Introduction Products in conformity with this European Standard are considered suitable for drinking water applications subject to either a) compliance with any national regulations in the country of intended destination; or b) compliance in due course with the proposed European Acceptance Scheme (EAS) that will introduce common EU requirements for testing for fitness for contact with drinking water. When the EAS is
implemented, this European Standard will have added to it a special Annex (Z/EAS) to incorporate the provi-sions of the EC mandate M/136 and a) will no longer be applicable. This European Standard provides the basis for the assessment of a manufacturer's production process for products manufactured in accordance with this European Standard. The assessment could be based on initial and continuing surveillance of the factory production control system which could be concurrent with an assessment of the
manufacturer's quality management system against EN ISO 9001. Regulatory marking and the means by which regulatory marking is applied, is dealt with in Annex ZA. Tubes having an outside diameter of not more than 108 mm are suitable for soldering, brazing or assembling by
mechanical compression, collared, push-fit or press fittings. For tubes having an outside diameter of more than 108 mm, assembly should preferably be performed by welding or braze welding. Reference can be made to this European Standard for tubes intended for other applications or for the
transportation of other fluids. In such cases special requirements (for specifications, conditioning or delivery
conditions) can be agreed between the purchaser and the supplier. NOTE Appropriate precautions should be taken if applying insulating/protecting material because it could be detrimental to the copper tube. SIST EN 1057:2006



EN 1057:2006 (E) 7 1 Scope This European Standard specifies the requirements, sampling, test methods and conditions of delivery for seam-less round copper tubes. It is applicable to tubes having an outside diameter from 6 mm up to and including 267 mm for:  distributing networks for hot water and cold water;  hot water heating systems, including panel heating systems (under-floor, wall, overhead);  domestic gas and liquid fuel distribution;  waste water sanitation. It is also applicable to seamless round copper tubes intended to be pre-insulated before use for any of the above purposes. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 723, Copper and copper alloys — Combustion method for determination of carbon on the inner surface of
copper tubes or fittings EN 1971, Copper and copper alloys — Eddy current test for tubes EN 10002-1, Metallic materials — Tensile testing — Part 1: Method of test at ambient temperature EN 10204:2004, Metallic products — Types of inspection documents EN ISO 8491, Metallic materials — Tube (in full section) — Bend test (ISO 8491:1998) EN ISO 8493, Metallic materials — Tube — Drift-expanding test (ISO 8493:1998) EN ISO 8494, Metallic materials — Tube — Flanging test (ISO 8494:1998) EN ISO 6507-1, Metallic materials — Vickers hardness test — Part 1: Test method (ISO 6507-1:2005) EN ISO 9001, Quality management systems — Requirements (ISO 9001:2000) ISO 1553, Unalloyed copper containing not less than 99,90 % of copper — Determination of copper content — Electrolytic method ISO 4741, Copper and copper alloys — Determination of phosphorus content — Molybdovanadate spectrometric method NOTE Informative references to documents used in the preparation of this standard, and cited at the appropriate places in the text, are listed in the Bibliography. SIST EN 1057:2006



EN 1057:2006 (E) 8 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 seamless round copper tube hollow semi-finished product, circular in cross-section, made of copper, having a uniform wall thickness, which at all stages of production has a continuous periphery 3.2 soldering/brazing joining process in which, during or after heating, molten filler metal is drawn into or retained in the space between closely adjacent surfaces of the parts to be joined by capillary attraction
3.2.1 soldering soft soldering joining process using filler metal with a liquidus temperature of 450 °C or less [ISO 857-2:2005] 3.2.2 brazing hard soldering joining process using filler metal with a liquidus temperature above 450 °C [ISO 857-2:2005] 3.3 fusion welding welding without application of outer force in which the facing surface(s) has (have) to be molten; usually, but not necessarily, molten filler metal is added [ISO 857-1:1998] 3.4 braze welding method of welding by using a filler metal that liquefies above 450 °C and below the solid state of the base metals. Unlike brazing, in braze welding, the filler metal is not distributed in the joint by capillary action 3.5 mean diameter arithmetical mean of the maximum and minimum outside diameters through the same cross-section of the tube 3.6 deviation from circular form difference between the maximum and minimum outside diameters measured at any one cross-section of the tube 3.7 deviation from concentricity half of the difference between the maximum and minimum wall thicknesses at the same cross-section of the tube 3.8 production batch definite quantity of products of the same form, the same material condition and the same cross-sectional
dimensions manufactured during the same production sequence under uniform conditions SIST EN 1057:2006



EN 1057:2006 (E) 9 3.9 permanently marked marked in such a way that the marking will remain readable up to the end of the life of the installation, e.g. by stamping, etching or engraving 3.10 durably marked marked in such a way that the marking will remain readable up to the time of commissioning of the installation EXAMPLE ink marking 4 Designations 4.1 Material 4.1.1 General The material is designated either by symbol or number (see 7.1). 4.1.2 Symbol The material symbol designation is based on the designation system given in ISO 1190-1. 4.1.3 Number The material number designation is in accordance with the system given in EN 1412. 4.2 Material condition For the purposes of this European Standard, the following designation, which is in accordance with the system given in EN 1173, applies for the material condition (see Table 1): R. Material condition designated by the minimum value of tensile strength requirement for the product with mandatory tensile strength and elongation requirements. 4.3 Product The product designation provides a standardized pattern of designation from which a rapid and unequivocal
description of a product is conveyed in communication. It provides mutual comprehension at the international level with regard to products which meet the requirements of the relevant European Standard. The product designation is no substitute for the full content of the standard. The product designation for products to this European Standard shall consist of:  denomination (Copper tube);  number of this European Standard (EN 1057);  material condition designation (see Table 1);  nominal cross-sectional dimensions in millimetres: outside diameter × wall thickness. The derivation of a product designation is shown in the following example. EXAMPLE Copper tube conforming to this European Standard, material condition R220 (annealed), nominal outside
diameter 12 mm, nominal wall thickness 1,0 mm, shall be designated as follows: SIST EN 1057:2006



EN 1057:2006 (E) 10 DenominationCopper tubeEN 1057R22012×1,0Number of this European StandardMaterial condition designationNominal cross-sectionaldimensions in millimetres-- 5 Ordering information In order to facilitate the enquiry, order and confirmation of order procedures between the purchaser and the
supplier, the purchaser shall state on his enquiry and order the following information: a) quantity of product required (in metres); b) denomination (Copper tube); c) number of this European Standard (EN 1057); d) material condition designation (see 4.2 and Table 1); e) nominal cross-sectional dimensions: outside diameter × wall thickness (see Table 3 and Annex A); f) nominal length (see 12.2); g) form of delivery (see 12.2); In addition, the purchaser shall also state on the enquiry and order any of the following, if required: h) drift expanding test: other than the mandatory cases, by agreement between the purchaser and the supplier, (see 7.7); i) flanging test: by agreement between the purchaser and the supplier (see 10.8); j) hardness test: by agreement between the p
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.