SIST EN 60831-1:2015
(Main)Shunt power capacitors of the self-healing type for a.c. systems having a rated voltage up to and including 1000 V - Part 1: General - Performance, testing and rating - Safety requirements - Guide for installation and operation
Shunt power capacitors of the self-healing type for a.c. systems having a rated voltage up to and including 1000 V - Part 1: General - Performance, testing and rating - Safety requirements - Guide for installation and operation
This part of the IEC 60831 series is applicable to both capacitor units and capacitor banks
intended to be used, particularly, for power-factor correction of a.c. power systems having a
rated voltage up to and including 1 000 V and frequencies of 15 Hz to 60 Hz.
This part of IEC 60831 also applies to capacitors intended for use in power filter circuits.
Additional definitions, requirements, and tests for power filter capacitors are given in Annex A.
The following capacitors are excluded from this part of IEC 60831:
– Shunt power capacitors of the non-self-healing type for a.c. systems having a rated
voltage up to and including 1 000 V (IEC 60931-, -2 and -3).
– Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V
(IEC 60871-1, -2, -3 and -4).
– Capacitors for inductive heat-generating plants operating at frequencies between 40 Hz
and 24 000 Hz (IEC 60110-1 and -2)
– Series capacitors (IEC60143-1, -2, -3 and -4)
– AC motor capacitors (IEC 60252-1 and -2)
– Coupling capacitors and capacitor dividers (IEC 60358-1)
– Capacitors for power electronic circuits (IEC 61071).
– Small a.c. capacitors to be used for fluorescent and discharge lamps (IEC 61048 and
IEC 61049).
– Capacitors for suppression of radio interference (under consideration).
– Capacitors intended to be used in various types of electrical equipment, and thus
considered as components.
– Capacitors intended for use with d.c. voltage superimposed on the a.c. voltage.
Accessories such as insulators, switches, instrument transformers, fuses, etc., should be in
accordance with the relevant IEC standards and are not covered by the scope of this part of
IEC 60831.
The object of this part of IEC 60831 is to:
a) formulate uniform rules regarding performances, testing and rating;
b) formulate specific safety rules;
c) provide a guide for installation and operation.
/
Condensateurs shunt de puissance autorégénérateurs pour réseaux à courant alternatif de tension assignée inférieure ou égale à 1000 V - Partie 1: Généralités - Caractéristiques fonctionnelles, essais et valeurs assignées - Exigences de sécurité - Guide d'installation et d'exploitation
NEW! IEC 60831-1:2014 est disponible sous forme de IEC Standards+ 60831-1:2014 qui contient la Norme internationale et sa version Redline, illustrant les modifications du contenu technique depuis l'édition précédente. IEC 60831-1:2014 s'applique aux condensateurs unitaires et aux batteries de condensateurs autorégénérateurs destinés plus particulièrement à la correction du facteur de puissance des réseaux à courant alternatif de tension assignée inférieure ou égale à 1 000 V et de fréquence comprise entre 15 Hz et 60 Hz. Cette partie de la CEI 60831 s'applique également aux condensateurs destinés à être utilisés dans des circuits de filtrage. Les définitions, les exigences et les essais complémentaires pour les condensateurs de filtrage en courants forts sont indiqués dans l'Annexe A. La présente partie de la CEI 60831 a pour objet: - de formuler des règles uniformes pour les performances, les essais et les caractéristiques assignées; - de formuler des règles spécifiques de sécurité; - de fournir un guide pour l'installation et l'utilisation. Cette troisième édition annule et remplace la seconde édition parue en 1996 et l'Amendement 1:2002. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente: - mise à jour des références normatives; - clarification des conditions d'essai; - clarification de l'essai de stabilité thermique; - clarification de la tension maximale et du courant maximal autorisés; - modification des mesures de sécurité et des exigences en matière de qualité du plastique pour la protection de l'environnement. Mots clés: condensateurs unitaires et aux batteries de condensateurs autorégénérateurs, règles uniformes pour les performances, essais et les caractéristiques assignées règles spécifiques de sécurité; guide pour l'installation et l'utilisation.
Samoozdravljivi vzporedni energetski kondenzatorji za izmenične tokovne sisteme z naznačeno napetostjo do vključno 1000 V - 1. del: Splošno - Lastnosti, preskušanje in razvrščanje - Varnostne zahteve - Navodilo za inštaliranje in obratovanje
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 60831-1:2015
01-junij-2015
1DGRPHãþD
SIST EN 60831-1:1999
SIST EN 60831-1:1999/A1:2003
6DPRR]GUDYOMLYLY]SRUHGQLHQHUJHWVNLNRQGHQ]DWRUML]DL]PHQLþQHWRNRYQHVLVWHPH
]QD]QDþHQRQDSHWRVWMRGRYNOMXþQR9GHO6SORãQR/DVWQRVWL
SUHVNXãDQMHLQUD]YUãþDQMH9DUQRVWQH]DKWHYH1DYRGLOR]DLQãWDOLUDQMHLQ
REUDWRYDQMH
Shunt power capacitors of the self-healing type for a.c. systems having a rated voltage
up to and including 1000 V - Part 1: General - Performance, testing and rating - Safety
requirements - Guide for installation and operation
/
Condensateurs shunt de puissance autorégénérateurs pour réseaux à courant alternatif
de tension assignée inférieure ou égale à 1000 V - Partie 1: Généralités -
Caractéristiques fonctionnelles, essais et valeurs assignées - Exigences de sécurité -
Guide d'installation et d'exploitation
Ta slovenski standard je istoveten z: EN 60831-1:2014
ICS:
31.060.70 0RþQRVWQLNRQGHQ]DWRUML Power capacitors
SIST EN 60831-1:2015 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 60831-1:2015
---------------------- Page: 2 ----------------------
SIST EN 60831-1:2015
EUROPEAN STANDARD EN 60831-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2014
ICS 29.120.99; 31.060.70 Supersedes EN 60831-1:1996
English Version
Shunt power capacitors of the self-healing type for a.c. systems
having a rated voltage up to and including 1 000 V - Part 1:
General - Performance, testing and rating - Safety requirements
- Guide for installation and operation
(IEC 60831-1:2014)
Condensateurs shunt de puissance autoregénérateurs pour Selbstheilende Leistungs-Parallelkondensatoren für
réseaux à courant alternatif de tension assignée inférieure Wechselstromanlagen mit einer Bemessungsspannung bis
ou égale à 1 000 V - Partie 1: Généralités - Caractéristiques 1 000 V - Teil 1: Allgemeines - Leistungsanforderungen,
fonctionnelles, essais et valeurs assignées - Règles de Prüfung und Bemessung - Sicherheitsanforderungen -
sécurité - Guide d'installation et d'exploitation Anleitung für Errichtung und Betrieb
(CEI 60831-1:2014) (IEC 60831-1:2014)
This European Standard was approved by CENELEC on 2014-03-18. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 60831-1:2014 E
---------------------- Page: 3 ----------------------
SIST EN 60831-1:2015
EN 60831-1:2014 - 2 -
Foreword
The text of document 33/543/FDIS, future edition 3 of IEC 60831-1, prepared by IEC/TC 33, "Power
capacitors and their applications" was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN 60831-1:2014.
The following dates are fixed:
(dop) 2014-12-18
• latest date by which the document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2017-03-18
standards conflicting with the
document have to be withdrawn
This document supersedes EN 60831-1:1996 + A1:2003.
EN 60831-1:2014 includes the following significant technical changes with respect to EN 60831-
1:1996 + A1:2003:
a) Updating of the normative references;
b) Test conditions have been clarified;
c) Thermal stability test has been clarified;
d) Maximum permissible voltage and current have been clarified;
e) The protection of the environment has been amended with safety concerns and plastic quality
requirements.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights.
This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment
Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC).
Endorsement notice
The text of the International Standard IEC 60831-1:2014 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 60060-2:2010 NOTE Harmonised as EN 60060-2:2011 (not modified).
IEC 60110-1:1998 NOTE Harmonised as EN 60110-1:1998 (not modified).
IEC 60143-1 NOTE Harmonised as EN 60143-1 (not modified).
IEC 60143-2 NOTE Harmonised as EN 60143-2 (not modified).
IEC 60143-3 NOTE Harmonised as EN 60143-3 (not modified).
IEC 60143-4 NOTE Harmonised as EN 60143-4 (not modified).
IEC 60252-1:2010 NOTE Harmonised as EN 60252-1:2011 (not modified).
---------------------- Page: 4 ----------------------
SIST EN 60831-1:2015
- 3 - EN 60831-1:2014
IEC 60358-1 NOTE Harmonised as EN 60358-1 (not modified).
IEC 61048:2006 NOTE Harmonised as EN 61048:2006 (not modified).
IEC 61049:1991 NOTE Harmonised as EN 61049:1993 (modified).
IEC 61071 (series) NOTE Harmonised as EN 61071 (series) (not modified).
---------------------- Page: 5 ----------------------
SIST EN 60831-1:2015
EN 60831-1:2014 - 4 -
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu
Publication Year Title EN/HD Year
IEC 60060-1 2010 High-voltage test techniques - Part 1: General EN 60060-1 2010
definitions and test requirements
IEC 60269-1 2006 Low-voltage fuses - Part 1: General EN 60269-1 2007
requirements
IEC 60695-2-12 2010 Fire hazard testing - Part 2-12: Glowing/hot- EN 60695-2-12 2010
wire based test methods - Glow-wire
flammability index (GWFI) test method for
materials
IEC 60831-2 2014 Shunt power capacitors of the self-healing EN 60831-2 2014
type for a.c. systems having a rated voltage
up to and including 1000 V - Part 2: Ageing
test, self-healing test and destruction test
IEC 61000-2-2 2002 Electromagnetic compatibility (EMC) - Part 2- EN 61000-2-2 2002
2: Environment - Compatibility levels for low-
frequency conducted disturbances and
signalling in public low-voltage power supply
systems
IEC 61000-4-1 2006 Electromagnetic compatibility (EMC) - Part 4- EN 61000-4-1 2007
1: Testing and measurement techniques -
Overview of IEC 61000-4 series
---------------------- Page: 6 ----------------------
SIST EN 60831-1:2015
IEC 60831-1
®
Edition 3.0 2014-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Shunt power capacitors of the self-healing type for a.c. systems having a rated
voltage up to and including 1 000 V –
Part 1: General – Performance, testing and rating – Safety requirements – Guide
for installation and operation
Condensateurs shunt de puissance autoregénérateurs pour réseaux à courant
alternatif de tension assignée inférieure ou égale à 1 000 V –
Partie 1: Généralités – Caractéristiques fonctionnelles, essais et valeurs
assignées – Règles de sécurité – Guide d'installation et d'exploitation
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
W
CODE PRIX
ICS 29.120.99; 31.060.70 ISBN 978-2-8322-1391-9
Warning! Make sure that you obtained this publication from an authorized distributor.
Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 7 ----------------------
SIST EN 60831-1:2015
– 2 – 60831-1 © IEC:2014
CONTENTS
FOREWORD . 5
1 Scope . 7
2 Normative references . 8
3 Terms and definitions . 8
4 Service conditions . 11
4.1 Normal service conditions . 11
4.2 Unusual service conditions . 12
5 Test requirements. 12
5.1 General . 12
5.2 Test conditions . 13
6 Classification of tests . 13
6.1 Routine tests. 13
6.2 Type tests . 13
6.3 Acceptance tests . 14
7 Capacitance measurement and output calculation . 14
7.1 Measuring procedure . 14
7.2 Capacitance tolerances . 14
8 Measurement of the tangent of the loss angle (tan δ) of the capacitor . 15
8.1 Measuring procedure . 15
8.2 Loss requirements . 15
9 Voltage tests between terminals . 15
9.1 Routine test . 15
9.2 Type test . 15
10 Voltage tests between terminals and container . 16
10.1 Routine test . 16
10.2 Type test . 16
11 Test of internal discharge device . 17
12 Sealing test . 17
13 Thermal stability test . 17
14 Measurement of the tangent of the loss angle (tan δ) of the capacitor at elevated
temperature . 19
14.1 Measuring procedure . 19
14.2 Requirements . 19
15 Lightning impulse voltage test between terminals and container . 19
16 Discharge test . 19
17 Ageing test . 20
18 Self-healing test . 20
19 Destruction test . 20
20 Maximum permissible voltage . 20
20.1 Long-duration voltages . 20
20.2 Switching voltages . 21
21 Maximum permissible current . 21
22 Discharge device . 21
23 Container connections . 22
---------------------- Page: 8 ----------------------
SIST EN 60831-1:2015
60831-1 © IEC:2014 – 3 –
24 Protection of the environment . 22
25 Other safety requirements . 22
26 Marking of the unit . 22
26.1 Rating plate . 22
26.2 Standardized connection symbols . 23
26.3 Warning plate . 23
27 Marking of the bank . 23
27.1 Instruction sheet or rating plate . 23
27.2 Warning plate . 23
28 General . 24
29 Choice of the rated voltage . 24
30 Operating temperature . 25
30.1 General . 25
30.2 Installation . 25
30.3 High ambient air temperature . 25
30.4 Evaluation of losses . 25
31 Special service conditions . 26
32 Overvoltages . 26
33 Overload currents . 27
34 Switching and protective devices and connections . 27
35 Choice of creepage distance . 28
36 Capacitors connected to systems with audio-frequency remote control . 29
37 Electromagnetic compatibility (EMC) . 29
37.1 Emission . 29
37.2 Immunity . 29
37.2.1 General . 29
37.2.2 Low-frequency disturbances . 29
37.2.3 Conducted transients and high-frequency disturbances . 29
37.2.4 Electrostatic discharges . 29
37.2.5 Magnetic disturbances . 30
37.2.6 Electromagnetic disturbances . 30
Annex A (normative) Additional definitions, requirements and tests for power filter
capacitors . 31
A.1 Terms and definitions . 31
A.2 Quality requirements and tests . 31
A.2.1 Capacitance tolerance . 31
A.2.2 Voltage test between terminals (see Clause 9) . 32
A.2.3 Thermal stability test (see Clause 13) . 32
A.3 Overloads – Maximum permissible current (see Clause 21) . 32
A.4 Markings – Instruction sheet or rating plate (see 27.1) . 32
A.5 Guide for installation and operation – Choice of the rated voltage (see
Clause 29) . 32
Annex B (informative) Formulae for capacitors and installations . 33
B.1 Computation of the output of three-phase capacitors from three single-
phase capacitance measurements . 33
B.2 Resonance frequency . 33
B.3 Voltage rise . 33
---------------------- Page: 9 ----------------------
SIST EN 60831-1:2015
– 4 – 60831-1 © IEC:2014
B.4 Inrush transient current . 34
B.4.1 Switching in of single capacitor . 34
B.4.2 Switching of capacitors in parallel with energized capacitor(s) . 34
B.4.3 Discharge resistance in single-phase units or in one-phase or
polyphase units . 34
Bibliography . 36
Figure B.1 – k values depending on the method of connection of the resistors with the
capacitor units . 35
Table 1 – Letter symbols for upper limit of temperature range . 12
Table 2 – Ambient air temperature for the thermal stability test . 18
Table 3 – Admissible voltage levels in service . 20
---------------------- Page: 10 ----------------------
SIST EN 60831-1:2015
60831-1 © IEC:2014 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
SHUNT POWER CAPACITORS OF THE SELF-HEALING TYPE FOR A.C.
SYSTEMS HAVING A RATED VOLTAGE UP TO AND INCLUDING 1 000 V –
Part 1: General – Performance, testing and rating –
Safety requirements – Guide for installation and operation
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60831-1 has been prepared by IEC technical committee 33: Power
capacitors and their applications.
This third edition cancels and replaces the second edition published in 1996 and Amendment
1:2002. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) Updating of the normative references;
b) Test conditions have been clarified;
c) Thermal stability test has been clarified;
d) Maximum permissible voltage and current have been clarified;
---------------------- Page: 11 ----------------------
SIST EN 60831-1:2015
– 6 – 60831-1 © IEC:2014
e) The protection of the environment has been amended with safety concerns and plastic
quality requirements.
The text of this standard is based on the following documents:
FDIS Report on voting
33/543/FDIS 33/550/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 60831 series, published under the general title Shunt power
capacitors of the self-healing type for a.c. systems having a rated voltage up to and including,
1 000 V can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of May 2014 have been included in this copy.
---------------------- Page: 12 ----------------------
SIST EN 60831-1:2015
60831-1 © IEC:2014 – 7 –
SHUNT POWER CAPACITORS OF THE SELF-HEALING TYPE FOR A.C.
SYSTEMS HAVING A RATED VOLTAGE UP TO AND INCLUDING 1 000 V –
Part 1: General – Performance, testing and rating –
Safety requirements – Guide for installation and operation
1 Scope
This part of the IEC 60831 series is applicable to both capacitor units and capacitor banks
intended to be used, particularly, for power-factor correction of a.c. power systems having a
rated voltage up to and including 1 000 V and frequencies of 15 Hz to 60 Hz.
This part of IEC 60831 also applies to capacitors intended for use in power filter circuits.
Additional definitions, requirements, and tests for power filter capacitors are given in Annex A.
The following capacitors are excluded from this part of IEC 60831:
– Shunt power capacitors of the non-self-healing type for a.c. systems having a rated
voltage up to and including 1 000 V (IEC 60931-, -2 and -3).
– Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V
(IEC 60871-1, -2, -3 and -4).
– Capacitors for inductive heat-generating plants operating at frequencies between 40 Hz
and 24 000 Hz (IEC 60110-1 and -2)
– Series capacitors (IEC60143-1, -2, -3 and -4)
– AC motor capacitors (IEC 60252-1 and -2)
– Coupling capacitors and capacitor dividers (IEC 60358-1)
– Capacitors for power electronic circuits (IEC 61071).
– Small a.c. capacitors to be used for fluorescent and discharge lamps (IEC 61048 and
IEC 61049).
– Capacitors for suppression of radio interference (under consideration).
– Capacitors intended to be used in various types of electrical equipment, and thus
considered as components.
– Capacitors intended for use with d.c. voltage superimposed on the a.c. voltage.
Accessories such as insulators, switches, instrument transformers, fuses, etc., should be in
accordance with the relevant IEC standards and are not covered by the scope of this part of
IEC 60831.
The object of this part of IEC 60831 is to:
a) formulate uniform rules regarding performances, testing and rating;
b) formulate specific safety rules;
c) provide a guide for installation and operation.
---------------------- Page: 13 ----------------------
SIST EN 60831-1:2015
– 8 – 60831-1 © IEC:2014
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60060-1:2010, High-voltage test technique
...
Questions, Comments and Discussion