oSIST prEN ISO 14644-7:2026
(Main)Cleanrooms and associated controlled environments - Part 7: Separative devices (ISO/DIS 14644-7:2026)
- Abstract
ISO 14644-7:2004 specifies the minimum requirements for the design, construction, installation, test and approval of separative devices, in those respects where they differ from cleanrooms as described in ISO 14644-4 and 14644-5.
The application of ISO 14644-7:2004 takes into account the following limitations: user requirements are as agreed by customer and supplier; application-specific requirements are not addressed; specific processes to be accommodated in the separative-device installation are not specified; fire, safety and other regulatory matters are not considered specifically; where appropriate, national and local regulations apply.
ISO 14644-7:2004 is not applicable to full-suits.
- Status
- Not Published
- Public Enquiry End Date
- 14-Dec-2026
- Technical Committee
- I13 - Imaginarni 13
- Current Stage
- 4020 - Public enquire (PE) (Adopted Project)
- Start Date
- 26-Oct-2026
- Due Date
- 15-Mar-2027
oSIST prEN ISO 14644-7:2026 is the Slovenian adoption of prEN ISO 14644-7, based on ISO/DIS 14644-7:2026 and published by SIST. It specifies minimum requirements for the design, construction, installation, test and setting to work of separative devices used in cleanrooms and associated controlled environments. The document is aimed at people who need to choose, design, build, verify or operate devices that control contaminant ingress or egress by physical or aerodynamic separation.
What does oSIST prEN ISO 14644-7:2026 specify?
oSIST prEN ISO 14644-7:2026 sets the minimum requirements for separative devices where they differ from cleanrooms described in ISO 14644-4. It covers devices used to prevent contaminant ingress into a device, or contaminant egress from it, and it gives design, testing and operational parameters to distinguish between different device types and performance levels.
The scope includes a broad range of devices used inside or outside a cleanroom, including free-standing and mobile arrangements. The document is organized into clauses on scope, normative references, terms and definitions, symbols and abbreviations, requirements, design, construction, installation, start-up and verification, and specific separative device tests, followed by informative annexes.
| Annex | What it covers |
|---|---|
| Annex A | Concepts and types of separative devices |
| Annex B | Separation index testing, including worked examples |
| Annex C | Air-handling systems and gas systems |
| Annex D | Access devices |
| Annex E | Transfer device examples |
| Annex F | Verification testing |
What are the key requirements of oSIST prEN ISO 14644-7:2026?
The document starts with an initial risk assessment. Clause 5.1 requires the customer and supplier to consider product quality, personnel safety and environmental safety early in the project. In practice, this means the device has to be matched to the process, the material flow, the utilities, the maintenance strategy and the operating cycle before design is frozen.
Clause 5.1 also asks the parties to define the usage conditions, installation constraints and surrounding influences. That includes intended use, entry and exit of materials and waste, lifecycle changes, location, dimensions, cleaning and decontamination, reliability, backup strategy and personnel access. This matters because many failures in practice come from poor fit with the process rather than from the device concept itself.
Clause 5.1.4 requires agreement on control and monitoring. The standard points to performance parameters, acceptance criteria, alert and alarm limits, environmental monitoring, and energy efficiency targets. It also notes that critical parameters should be continuously monitored and alarmed, which is important where loss of separation would affect product, process or containment.
Clause 5.2 requires the customer and supplier to agree on the separation method and, where applicable, the associated separation index (SI). They also need to agree on the test method, test conditions and any access or transfer devices. In practical terms, the device must be specified together with the way it will be proven to work.
Clause 5.3 requires the agreed requirements to be documented so that later changes can be managed traceably. The document notes that this is often called a User Requirement Specification (URS). This gives the project a controlled baseline for design reviews, testing and handover.
Clause 6 describes a staged design process:
- Conceptual design (CD) defines the separation principle, the air handling concept, access devices, transfer devices and the overall dimensions.
- Basic design (BD) adds layout drawings, utility data, airflow and pressure-cascade schematics, supporting calculations, filtration, control strategy, maintenance strategy and verification approach.
- Detailed design (DD) develops the approved basic design far enough to support construction and verification, including quality control requirements.
This staged approach matters because the document treats design review and verification as separate checkpoints, not as an afterthought.
Clause 6.6 focuses on typical design aspects such as the separation concept, critical attributes and fail-safe design. Depending on the device, critical parameters can include air velocity, differential pressure, contaminant concentration, humidity, temperature and construction materials. This means teams must identify which parameters are critical, then control, record or alarm them as needed.
Clauses 6.7 to 6.9 deal with access devices, transfer devices and air handling systems. Access devices must allow manipulation without compromising separation, and glove systems should allow glove change without breaching the device. Transfer devices must not reduce device performance and are selected according to the level of separation and functional performance needed. Air handling systems must maintain the specified cleanliness level in operation and transient conditions, and their effect on the surrounding cleanroom airflow must be assessed.
Clauses 7 to 9 cover construction, installation, start-up and verification. Construction must follow approved drawings and specifications, with a clean build protocol where appropriate. The supplier performs Factory Acceptance Testing (FAT), and the customer performs Site Acceptance Testing (SAT) after installation. Commissioning includes setting to work, in-situ verification, training, handover, periodic testing and decommissioning planning.
Clause 10 gives the specific separative device tests. The separation index test is the fundamental performance test. The clause also covers quantitative leak testing for devices with physical barriers and a glove breach test where gloves are fitted. These tests are the main way to confirm that the device provides the intended separation in practice.
What terms does oSIST prEN ISO 14644-7:2026 define?
- Separative device - equipment that uses a physical barrier, aerodynamic means, or both, to create assured levels of separation for a work zone or internal volume.
- Separation index (SI) - a numerical expression of separation performance under specified test conditions, used for ingress, egress, or both.
- Access device - a component that lets an operator manipulate materials, equipment or products inside the device without compromising separation.
- Transfer device - a mechanism for moving materials into or out of the device while minimizing contaminant ingress or egress.
- Isolator - an enclosure that provides separation by physical and aerodynamic means and is operated through access devices.
- Work zone - the designated part of the separative device where the specified activities are carried out.
- Factory Acceptance Testing (FAT) - verification carried out at the supplier’s premises after construction and before transport to the site.
- Site Acceptance Testing (SAT) - verification carried out after installation and integration at the customer’s premises.
Who uses oSIST prEN ISO 14644-7:2026?
Design engineers use this standard to define the separation concept, access arrangements, airflow, utilities and verification approach. Suppliers and integrators use it to build, test and document the device before handover. Customer engineering, quality and validation teams use it to agree requirements, review design evidence, and plan FAT, SAT, commissioning and periodic testing.
It is relevant in industries where contamination control matters, including aerospace, microelectronics, pharmaceuticals, medical devices, healthcare, nuclear, fine finishing and food. It is especially useful where a process needs both controlled air cleanliness and some level of containment, such as with isolators, gloveboxes, Biological Safety Cabinets, RABS and minienvironments.
What changed in oSIST prEN ISO 14644-7:2026 from the previous edition?
This edition is updated in response to user and expert feedback validated by international enquiry. It is also described as better integrated with the other parts of ISO 14644, especially the latest editions of parts 1, 2, 3 and 4. The introduction also shows a stronger distinction between prevention of ingress and prevention of egress, which helps users match the standard to the actual purpose of the separative device.
Which standards are used with oSIST prEN ISO 14644-7:2026?
Clause 2 names the following normative references:
- ISO 14644-1 - used for air cleanliness classification by particle concentration.
- ISO 14644-2 - used for monitoring to provide evidence of cleanroom performance related to air cleanliness by particle concentration.
- ISO 14644-3 - used for test methods, including several verification tests and the separation index framework referenced in the annexes.
- ISO 14644-4 - used for design, construction and start-up of cleanrooms and associated controlled environments.
- ISO 14644-14 - used where equipment suitability is assessed by airborne particle concentration.
- ISO 14644-15 - used where equipment and materials are assessed by airborne chemical concentration.
- ISO 14644-16 - used for energy efficiency in cleanrooms and separative devices.
- ISO 14644-18 - used for assessing the suitability of consumables.
What does the oSIST prEN ISO 14644-7:2026 document contain?
The document contains the core requirements for defining, designing, building and verifying separative devices, plus annexes that explain the device concepts and the test methods. Annex B gives the separation index procedure and includes worked examples for an isolator and a ventilated transfer hatch. Annex C describes air-handling and gas-system arrangements, including inert gas and pressure-relief features. Annex D describes glove systems and half-suits, and Annex E illustrates transfer device configurations such as pass-through boxes, transfer chambers and transfer containers.
Annex F is particularly useful for verification planning because it summarizes the possible test set, including separation index testing, leak testing, glove tests and other checks selected by risk analysis. The document also uses formulas, figures and table-based examples to show how different separative device types behave and how their performance is assessed.
Relations
- Effective Date
- 07-Aug-2024
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
oSIST prEN ISO 14644-7:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Cleanrooms and associated controlled environments - Part 7: Separative devices (ISO/DIS 14644-7:2026)". This standard covers: ISO 14644-7:2004 specifies the minimum requirements for the design, construction, installation, test and approval of separative devices, in those respects where they differ from cleanrooms as described in ISO 14644-4 and 14644-5. The application of ISO 14644-7:2004 takes into account the following limitations: user requirements are as agreed by customer and supplier; application-specific requirements are not addressed; specific processes to be accommodated in the separative-device installation are not specified; fire, safety and other regulatory matters are not considered specifically; where appropriate, national and local regulations apply. ISO 14644-7:2004 is not applicable to full-suits.
ISO 14644-7:2004 specifies the minimum requirements for the design, construction, installation, test and approval of separative devices, in those respects where they differ from cleanrooms as described in ISO 14644-4 and 14644-5. The application of ISO 14644-7:2004 takes into account the following limitations: user requirements are as agreed by customer and supplier; application-specific requirements are not addressed; specific processes to be accommodated in the separative-device installation are not specified; fire, safety and other regulatory matters are not considered specifically; where appropriate, national and local regulations apply. ISO 14644-7:2004 is not applicable to full-suits.
oSIST prEN ISO 14644-7:2026 is classified under the following ICS (International Classification for Standards) categories: 13.040.35 - Cleanrooms and associated controlled environments. The ICS classification helps identify the subject area and facilitates finding related standards.
oSIST prEN ISO 14644-7:2026 has the following relationships with other standards: It is inter standard links to SIST EN ISO 14644-7:2005. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
oSIST prEN ISO 14644-7:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 access device
- 3.2 barrier
- 3.3 breach velocity
- 3.4 containment
- 3.5 decontamination
- 3.6 glove (of separative devices)
- 3.7 glove port
- 3.8 glove sleeve system
- 3.9 Isolator
- 3.10 leak (of a separative device)
- 3.11 pressure integrity
- 3.12 Separation
- 3.15 separative device
- 3.16 transfer device
- 3.17 work zone
- 3.18 cleanliness
- 3.19 cleanroom
- 3.20 clean zone
- 3.21 contamination
- 3.22 controlled zone
- 3.23 service life
- 3.24 verification
- 3.25 contaminant
- 4 Symbols and abbreviations
- 5 Requirements
- 5.1 General Requirements
- 5.2 Specific Requirements
- 5.3 Documentation
- 6 Design
- 6.1 General
- 6.2 Conceptual design
- 6.3 Basic design
- 6.4 Detailed Design
- 6.5 Change management
- 6.6 Typical Design Aspects
- 6.7 Access Devices
- 6.8 Transfer Devices
- 6.9 Air handling systems
- 7 Construction
- 7.1 General
- 7.2 Clean build protocol
- 7.3 Construction Verification
- 8 Installation
- 8.1 General
- 8.2 Installation Verification
- 9 Start-up and verification
- 9.1 General
- 9.2 Commissioning
- 9.3 Training
- 9.4 Handover
- 9.5 Periodic testing
- 9.6 Decommissioning
- 10 Specific Separative Device Tests
- 10.1 General
- 10.2 Separation Index Test
- 10.3 Quantitative leak testing
- 10.4 Glove breach test
- Annex A
- Annex B
- Annex C
- Annex D
- 3 O-ring seal
- Annex E
- 5 HEPA filter
- Annex F
- Bibliography
Introduction
Cleanrooms and associated controlled environments provide for the control of airborne and surface contamination to levels appropriate for contamination-sensitive activities. Contamination control can be beneficial for protection of product or process in industries such as aerospace, microelectronics, pharmaceuticals, medical devices, healthcare, nuclear, fine finishing and food. This part of ISO 14644 sets out considerations for the design and testing of separative devices and this edition of this part is in response to user and expert feedback validated by international enquiry. This edition has been updated to better integrate with the other parts of ISO 14644 and in particular the latest editions of parts 1, 2, 3 and 4.
The term ‘separative device’ was originally developed by Technical Committee ISO/TC 209 to encompass the wide continuum of configurations from open unrestricted air overspill to wholly physically contained systems. Separative devices provide protection in varying levels by utilising physical or aerodynamic means, or a combination of both, to create separation between an internal environment and the background environment. The original continuum of separative devices did not properly distinguish between prevention of ingress of contaminants (air cleanliness) within the device and prevention of egress of contaminants from the device (containment). The new continuum recognises that separative devices can provide a variety of combinations of air cleanliness and containment with varying degrees of effectiveness. Part 1 of ISO 14644 defines cleanrooms and clean zones. Clean zones ‘can be a defined space within a cleanroom or might be achieved by a separative device. Such a device can be located inside or outside a cleanroom.’ This part of ISO 14644 is intended to apply to a broad range of devices, examples of which are given in the scope portion of this document. They may be integrated into the cleanroom structure or freestanding within it. Some separative devices can be independent of a cleanroom and some can be mobile. Where a separative device provides air cleanliness, it can be classified, monitored, and tested in accordance with parts 1, 2, 3 and 4 of ISO 14644. Where it provides containment, the containment may be tested and monitored by part 3 or other methods. In all cases the effectiveness of separation can be expressed by a characterizing separation index, the basis for calculation and testing of this index is described herein. ISO 14644 is intended to be broadly applicable; but, as isolators have special requirements, there is an emphasis in this Part 7 on physical separation – this should be considered when using this standard.
oSIST prEN ISO 14644-7:2026 DRAFT International Standard ISO/DIS 14644-7:2026(en) Cleanrooms and associated controlled environments — Part 7:
Separative devices
1 Scope
This part of ISO 14644 specifies the minimum requirements for the design, construction, installation, test and setting to work of separative devices, in those respects where they differ from cleanrooms as described in ISO 14644-4.
It is intended to be complimentary to the requirements of other national and international standards and guidelines for separative devices as listed below.
This part includes devices providing segregation using either physical or aerodynamic separation for the purposes of preventing the ingress of contaminants to the device or preventing the egress of contaminants from the device. It provides design, testing and operational parameters to distinguish between devices with different purposes and performance characteristics.
Separative devices covered by this section addresses:
- Unidirectional Airflow Devices
- Material Handling Booths
- Restricted Access Barrier Systems (with or without access devices)
- Isolators (open or closed isolators, with or without transfer devices)
- Transfer Containers
- Biological Safety Cabinets Class II and III
- Gloveboxes
- Pass-Through Boxes or Transfer Hatches
- Minienvironments Refer to Annex A for further information on the above devices. This part of ISO 14644 excludes:
- Devices designed solely for containment, not associated with cleanrooms or clean zones.
- Environmental health or safety requirements which might drive the need for containment.
- Application-specific requirements
- Specific processes to be accommodated in the separative-device installation.
- Fire, safety and other regulatory matters, specifically where appropriate national and local regulations apply.
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en)
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
ISO 14644-1, Cleanrooms and associated controlled environments — Part 1: Classification of air cleanliness by particle concentration ISO 14644-2, Cleanrooms and associated controlled environments — Part 2: Monitoring to provide evidence of cleanroom performance related to air cleanliness by particle concentration ISO 14644-3, Cleanrooms and associated controlled environments — Part 3: Test methods ISO 14644-4, Cleanrooms and associated controlled environments — Part 4: Design, construction and start-up ISO 14644-14, Cleanrooms and associated controlled environments — Part 14: Assessment of suitability for use of equipment by airborne particle concentration ISO 14644-15, Cleanrooms and associated controlled environments — Part 15: Assessment of suitability for use of equipment and materials by airborne chemical concentration ISO 14644-16, Cleanrooms and associated controlled environments — Part 16: Energy efficiency in cleanrooms and separative devices ISO 14644-18, Cleanrooms and associated controlled environments — Part 18: Assessment of suitability of consumables
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 10648-2, 14644-1, 14644-2 14644- 4, and 14644-14 and the following apply
3.1 access device
component of a separative device which allows an operator outside the barrier to manipulate materials, equipment or products within the separative device without compromising the separation.
3.2 barrier
means employed to provide separation
3.3 breach velocity
speed of air through an aperture in a barrier Note 1 to entry: Sufficient airflow through a breach will prevent movement of airborne contamination in the opposite direction (aerodynamic separation)
3.4 containment
resistance to egress of airborne contaminant Note 1 to entry: The contaminant can be airborne particles, microorganisms or chemicals
3.5 decontamination
reduction of unwanted matter to a defined level
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en)
3.6 glove (of separative devices)
component of an access device that maintains an effective barrier while enabling the hands of an operator to enter the enclosed volume of a separative device.
Note 1 to entry: Gloves can be two-piece glove and sleeve systems or one-piece glove and sleeve (gauntlet).
3.7 glove port
attachment site for glove sleeve system
3.8 glove sleeve system
multi-component access device that maintains an effective barrier while enabling the replacement of sleeve piece, connecting cuff piece and the glove
3.9 Isolator
enclosure providing separation by physical and aerodynamic means which is operated via access devices. Note 1 to entry: isolators for aseptic processing are capable of being subject to reproducible interior biodecontamination. [SOURCE: ISO 11139:2018, modified]
3.10 leak (of a separative device)
defect allowing egress from or ingress to the working zone
3.11 pressure integrity
capability to provide a quantifiable leakage rate repeatable under quantitative leak test conditions
3.12 Separation
Reduction of ingress or egress of contaminants between a working zone and the surrounding environment. 3.13 Separation index SI ,
numerical abbreviation expressing the prevention of ingress into a working zone from the surrounding environment of the separative device under specified test conditions Note 1 to entry: for formula see section 9.3.2, Formula A.1 Note 2 to entry: the index can be applied for contaminants such as particles, chemicals or microorganisms 3.14 Separation index SI , e numerical abbreviation expressing the prevention of egress of a contaminant from the internal volume of a separative device into the surrounding environment under specified test conditions Note 1 to entry: for formula see 9.3.2 , Formula A.2 Note 2 to entry: the index can be applied for contaminants such as particles, chemicals or microorganisms
3.15 separative device
equipment utilizing a physical barrier or aerodynamic means to create assured levels of separation described by separation indices Note 1 to entry: The device has the purpose of preventing egress from or ingress into a specified area or volume (e.g. work zone) or both
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en) Note 2 to entry: Some industry specific examples of separative devices are unidirectional airflow devices, containment enclosures, glove boxes, isolators and minienvironments.
3.16 transfer device
mechanism to effect movement of materials into or out of a separative devices while minimizing ingress or egress of contamination
3.17 work zone
designated part of a separative device in which specified activities are carried out
3.18 cleanliness
condition not exceeding a specified level of contamination [SOURCE: ISO 14644-14:2016, 3.1] Note 1 to entry: In this document, contamination refers to particles, chemicals or viables.
3.19 cleanroom
room within which the number concentration of airborne particles is controlled and classified, and which is designed, constructed and operated in a manner to control the introduction, generation, and retention of particles inside the room Note 1 to entry: The class of airborne particle concentration is specified. Note 2 to entry: Levels of other cleanliness attributes such as chemical, viable or nanoscale concentrations in the air, and also surface cleanliness in terms of particle, nanoscale, chemical and viable concentrations might also be specified and controlled.
Note 3 to entry: Other relevant physical parameters might also be controlled as required, e.g. temperature, humidity, pressure, vibration and electrostatic.
[SOURCE: ISO 14644-1:2015, 3.1.1]
3.20 clean zone
defined space within which the number concentration of airborne particles is controlled and classified, and which is constructed and operated in a manner to control the introduction, generation, and retention of contaminants inside the space Note 1 to entry: The class of airborne particle concentration is specified. Note 2 to entry: Levels of other cleanliness attributes such as chemical, viable or nanoscale concentrations in the air, and also surface cleanliness in terms of particle, nanoscale, chemical and viable concentrations might also be specified and controlled.
Note 3 to entry: A clean zone(s) can be a defined space within a cleanroom or might be achieved by a separative device. Such a device can be located inside or outside a cleanroom.
Note 4 to entry: Other relevant physical parameters might also be controlled as required, e.g. temperature, humidity, pressure, vibration and electrostatic.
[SOURCE: ISO 14644-1:2015, 3.1.2]
3.21 contamination
unwanted matter in an undesirable location [SOURCE: ISO 14644-13:2017, 3.4]
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en)
3.22 controlled zone
designated space in which the concentration of at least one contamination category (particles, chemical, biocontamination) in air and on surfaces is controlled and specified and which is constructed and used in a manner to minimize the introduction and impact of contamination Note 1 to entry: Levels of cleanliness attributes such as chemical and viable concentrations in the air or cleanliness in terms of particle, chemical and viable concentrations on surfaces should be specified by level(s) as described in the ISO standard series.
Note 2 to entry: Other relevant parameters may also be controlled as necessary, e.g. temperature, humidity and pressure, vibration and electrostatic.
Note 3 to entry: A controlled zone can be a defined space within a cleanroom or may be achieved by a separative device. Such a device can be located inside or outside a cleanroom. [SOURCE: ISO 14644-15:2016, 3.9]
3.23 service life
length of time or number of cycles an item is suitable for use Note 1 to entry: In this document, items are considered as consumable. Note 2 to entry: Service life is depending on appropriate use. [SOURCE: ISO 14644-18:2023, 3.19]
3.24 verification
confirmation, through the provision of objective evidence that specified requirements have been fulfilled Note 1 to entry: The objective evidence needed for a verification can be the result of an Inspection or of other forms of determination such as performing alternative calculations or reviewing documents. Note 2 to entry: The activities carried out for verification are sometimes called a qualification Process. Note 3 to entry: The word “verified” is used to designate the corresponding status. [SOURCE: ISO 9000:2015, 3.8.12, modified: Cross-references to other terms deleted]
3.25 contaminant
particle, chemical or microorganism that adversely affects the product or process [SOURCE: ISO 14644-4:2022, 3.1.7] Note 1 to entry: For this standard, contaminant can also adversely affect the environment, personnel or other materials
4 Symbols and abbreviations
The following symbols and abbreviations are used in this part of ISO 14644 Table 1 — Common symbols used in cleanrooms and associated controlled environments Symbol Meaning BD Basic Design BSC Biological Safety Cabinet BMS Building Management System CD Concept Design DD Detailed Design
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en) TTabablele 1 1 ((ccoonnttiinnueuedd)) Symbol Meaning EMS Environmental Monitoring System FAT Factory Acceptance Testing HEPA filter High Efficiency Particulate Air filter LSAPC Light-scattering airborne particle counter RABS Restricted Access Barrier System SAT Site Acceptance Testing SI Separation index SMIF Standard Mechanical Interfaces UDAF Unidirectional Airflow ULPA Ultra Low Penetration Air filter
5 Requirements
5.1 General Requirements
Taking into consideration the contamination control concepts and overall strategy for contamination control, an initial risk assessment shall be conducted to establish the requirements with respect to product quality and safety aspects for personnel and environment.
The following items listed shall be considered and specified as appropriate, by customer and supplier before, or in the early stages of, the design process.
5.1.1 Usage
a) The intended use of the separative device and the operations to be carried out therein; Note 1 Intended use can include purpose of containment Note 2 Considerations include material compatibility, residues and effluents. b) Entry and exit of equipment, materials and waste, in terms of quantity, movement and controls applied such as decontamination; Note 1 Access devices and transfer devices can be part of these considerations Note 2 Ergonomics are an integral part of entry and exit of materials c) Intended life cycle of the separative device d) Changes of the separative device anticipated over time to be provided for in the design e) Intended operational cycles and turn-down periods; Note When systems are planned to be turned off, a detailed process impact assessment should be documented and an appropriate shutdown and return to service procedure outlined. Shutting systems off generally result in loss of separation and loss of cleanliness.
f) The intended location of the separative device and any constraints of the installation g) The identification of surrounding environmental influences; h) Critical dimensions and weight restrictions, including those related to available space. Note This includes circulation space and access for personnel and material movements.
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en) i) Process and product requirements that affect the separative device such as air velocity, light sensitivity or radioactivity.
j) Cleaning and decontamination requirements.
k) Utility requirements l) Process hazards; m) Internal surfaces and finish requirements (including request for smooth, impervious finishes which are cleanable and resistant to cleaning and decontamination agents and free of gaps to uncontrolled areas); n) Required availability, reliability level and back-up strategy; o) Strategy of maintenance operations, space and time needed to maintain the installations during the process cycle; p) Access of personnel over all phases of operation, including PPE, access devices and the like.
5.1.2 References
a) Regulatory requirements; b) The number, edition and year of publication of the relevant parts of ISO 14644 that will be used; c) Methods of testing, measurement and monitoring, to meet the acceptance criteria and related documentation.
Note It might be necessary to have special provisions (access or connections) for testing and monitoring of separative devices.
5.1.3 Conditions
a) The air cleanliness class at the designated particle size(s) and the defined occupancy states in accordance with ISO 14644-1; b) Any other requirements with respect to particles or other contaminants in air or on surfaces (e.g. particle number concentration and particle deposition rate); c) Considerations of any other influences e.g., electrostatic discharge (ESD), vibration; d) Sources of contamination and their source strength data;
5.1.4 Control / Monitoring
a) Performance parameters and their acceptance criteria with any specific requirements for alert (warning) and action (alarm) limits and their management; Note Management includes initial acceptance testing as well as ongoing monitoring b) Cleanroom environmental control by stand-alone systems or integrated into building management system (BMS); c) Requirements for monitoring of environmental and other parameters, both inside and outside of the separative device.; Note Guidance for monitoring to provide evidence of cleanroom and separative performance related to air cleanliness by particle concentration can be found in ISO 14644-2. It is recommended for critical parameters to be continuously monitored and alarmed. d) The preferred contamination control concepts and overall strategy for contamination control, including physical or chemical decontamination processes;
oSIST prEN ISO 14644-7:2026 ISO/DIS 14644-7:2026(en) e) Environmental and energy efficiency targets; Note Guidance for these targets can be found in ISO 14644-16 - Energy efficiency in cleanrooms and separative devices Any other factors or constraints, not listed above, imposed by operating requirements over the lifecycle of the separative devices.
5.2 Specific Requirements
The items listed below shall be specified and agreed by customer and supplier:
a) Description of the method of separation and associated separation index (where applicable). b) An appropriate test method to verify that the specified separation has been achieved. Note For verification, please refer to clause 10, an example of the separation index test can be found in Annex B, other tests are provided in Annex F c) Procedures, conditions and environment(s) for testing d) If applicable, access and transfer devices, appropriate to process and routine operation.
...