SCOPE
1.1 This specification covers the manufacture and testing of the temporary protective equipotential bond mat used on or around de-energized electrical equipment.  
1.2 It is common practice for users of protective equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The use and maintenance of this equipment is beyond the scope of this specification.  
1.4 It is recognized that the use of temporary protective equipotential bond mats requires additional equipment for installation and use, typically temporary connecting jumper assemblies.  
1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    6 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.  
1.2 This specification discusses methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.  
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F855.  
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.  
1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    9 pages
    English language
  • Technical specification
    9 pages
    English language

ABSTRACT
These specifications provides the manufacture and testing, as well as individual design, electrical, mechanical, and workmanship requirements for a system of flexible insulated temporary bypass jumpers used on energized power lines and equipment. These specifications for a system of bypass jumpers are covered in four parts as follows: clamps for bypass jumpers; ferrules for bypass jumpers; cable for bypass jumpers; and bypass jumpers (complete assembly with clamps, ferrules, and cable). The use and maintenance of these equipments are not addressed in these specifications.
SCOPE
1.1 This specification covers the manufacture and testing of flexible insulated temporary By-Pass jumpers (By-Pass jumpers) used on energized power lines and equipment.  
1.2 It is common practice for the user of this protective equipment to prepare complete instructions and safety regulations to govern in detail the correct and safe use of such equipment. Also see 4.2.  
1.3 The use and maintenance of this equipment are beyond the scope of this specification.  
1.4 This specification for a system of By-Pass jumpers is covered in four parts as follows:    
Title  
Sections  
Clamps for By-Pass Jumpers  
5 – 17  
Ferrules for By-Pass Jumpers  
18 – 31  
Cable for By-Pass Jumpers  
32 – 40  
By-Pass Jumpers (complete assembly
with clamps, ferrules, and cable)  
41 – 55  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 The values stated in SI units are to be regarded as the standard. See IEEE/ASTM SI 10.  
1.7 The following precautionary caveat pertains only to the test method portions, Sections 13, 26, 48, and 55 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    11 pages
    English language
  • Technical specification
    11 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X1.  
Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater than 20 % (X/R ≧ 1.8), see Appendix X2.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X2.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X2 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X1 and Appendix X2 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issue...

  • Technical specification
    20 pages
    English language
  • Technical specification
    20 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.  
1.2 This specification discusses methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.  
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F855.  
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.  
1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    9 pages
    English language
  • Technical specification
    9 pages
    English language
  • Technical specification
    9 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X1.  
Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater than 20 % (X/R ≧ 1.8), see Appendix X2.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X2.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X2 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X1 and Appendix X2 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issue...

  • Technical specification
    19 pages
    English language
  • Technical specification
    19 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 These specifications cover the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.  
1.2 These specifications discuss methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.  
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F855.  
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.  
1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    9 pages
    English language
  • Technical specification
    9 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 These specifications cover the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.  
1.2 These specifications discuss methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.  
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F855.  
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.  
1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    9 pages
    English language
  • Technical specification
    9 pages
    English language

ABSTRACT
These specifications provides the manufacture and testing, as well as individual design, electrical, mechanical, and workmanship requirements for a system of flexible insulated temporary bypass jumpers used on energized power lines and equipment. These specifications for a system of bypass jumpers are covered in four parts as follows: clamps for bypass jumpers; ferrules for bypass jumpers; cable for bypass jumpers; and bypass jumpers (complete assembly with clamps, ferrules, and cable). The use and maintenance of these equipments are not addressed in these specifications.
SCOPE
1.1 These specifications cover the manufacture and testing of flexible insulated temporary By-Pass jumpers (By-Pass jumpers) used on energized power lines and equipment.  
1.2 It is common practice for the user of this protective equipment to prepare complete instructions and safety regulations to govern in detail the correct and safe use of such equipment. Also see 4.2.  
1.3 The use and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of By-Pass jumpers is covered in four parts as follows:    
Title  
Sections  
Clamps for By-Pass Jumpers  
5 – 17  
Ferrules for By-Pass Jumpers  
18 – 31  
Cable for By-Pass Jumpers  
32 – 40  
By-Pass Jumpers (complete assembly
with clamps, ferrules, and cable)  
41 – 55  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 The values stated in SI units are to be regarded as the standard. See IEEE/ASTM SI 10.  
1.7 The following precautionary caveat pertains only to the test method portions, Sections 13, 26, 48, and 55 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    11 pages
    English language
  • Technical specification
    11 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X1.  
Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R ≧ 1.8), see Appendix X2.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X2.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X2 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X1 and Appendix X2 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issue...

  • Technical specification
    20 pages
    English language
  • Technical specification
    20 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X1.  
Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R ≧ 1.8), see Appendix X2.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X2.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X2 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X1 and Appendix X2 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issue...

  • Technical specification
    20 pages
    English language
  • Technical specification
    20 pages
    English language

SCOPE
1.1 This specification covers the manufacture and testing of the temporary protective equipotential bond mat used on or around de-energized electrical equipment.  
1.2 It is common practice for users of protective equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The use and maintenance of this equipment is beyond the scope of this specification.  
1.4 It is recognized that the use of temporary protective equipotential bond mats requires additional equipment for installation and use, typically temporary connecting jumper assemblies.  
1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    6 pages
    English language
  • Technical specification
    6 pages
    English language
  • Technical specification
    6 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 These specifications cover the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.  
1.2 These specifications discuss methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.  
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F855.  
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.  
1.5 Units of measurement used in this specification are in the Metric system (SI) with English units given in parentheses.  
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    15 pages
    English language
  • Technical specification
    15 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X1. (A) Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20 % asymmetry factor (see 9.1 and 12.3.4.2).(B) Yield shall mean no permanent deformation such that the clamp cannot be reused throughout its entire range of application.(C) Ultimate rating represents a symmetrical current which the assembly or individual components shall carry for the specified time.(D) Ultimate values are based upon application of Onderdonk's equation to 98 % of nominal circular mil area allowed by Specifications B172 and B173.  
Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R ≧ 1.8), see Appendix X2.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X2.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X2 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X1 and Appendix X2 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specif...

  • Technical specification
    19 pages
    English language
  • Technical specification
    19 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X3. (A) Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20 % asymmetry factor (see 9.1 and 12.3.4.2).(B) Yield shall mean no permanent deformation such that the clamp cannot be reused throughout its entire range of application.(C) Ultimate rating represents a symmetrical current which the assembly or individual components shall carry for the specified time.(D) Ultimate values are based upon application of Onderdonk's equation to 98 % of nominal circular mil area allowed by Specifications B172 and B173.  
Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R ≧ 1.8), see Appendix X4.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X4.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X4 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X3 and Appendix X4 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specif...

  • Technical specification
    20 pages
    English language
  • Technical specification
    20 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 These specifications cover the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.  
1.2 These specifications discuss methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.  
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F855.  
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.  
1.5 Units of measurement used in this specification are in the Metric system (SI) with English units given in parentheses.  
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    7 pages
    English language
  • Technical specification
    7 pages
    English language

SCOPE
1.1 This specification covers the manufacture and testing of the temporary protective equipotential bond mat used on or around de-energized electrical equipment.  
1.2 It is common practice for users of protective equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The use and maintenance of this equipment is beyond the scope of this specification.  
1.4 It is recognized that the use of temporary protective equipotential bond mats requires additional equipment for installation and use, typically temporary connecting jumper assemblies.

  • Technical specification
    3 pages
    English language
  • Technical specification
    3 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.  
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:    
Sections  
Clamps for Temporary Protective Grounds  
4 – 16    
Ferrules for Temporary Protective Grounds  
17 – 30    
Cables for Temporary Protective Grounds  
31 – 39    
Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)  
40 – 52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X3. (A) Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20 % asymmetry factor (see 9.1 and 12.3.4.2).(B) Yield shall mean no permanent deformation such that the clamp cannot be reused throughout its entire range of application.(C) Ultimate rating represents a symmetrical current which the assembly or individual components shall carry for the specified time.(D) Ultimate values are based upon application of Onderdonk's equation to 98 % of nominal circular mil area allowed by Specifications B172 and B173.  
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R ≧ 1.8), see Appendix X4.  
Note 1: The above current values are based on electromechanical test values.
Note 2: Assemblies that have been subjected to these shall not be re-used.
Note 3: For use with currents exceeding 20 % asymmetry factor.
Note 4: See X4.7.2 for additional information.
Note 5: Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X4 for details.
Note 1: Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.  
1.6.2 See Appendix X3 and Appendix X4 for a discussion of these topics.  
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the respon...

  • Technical specification
    20 pages
    English language
  • Technical specification
    20 pages
    English language

SCOPE
1.1 These specifications cover the manufacture and testing of flexible insulated temporary By-Pass jumpers (By-Pass jumpers) used on energized power lines and equipment.  
1.2 It is common practice for the user of this protective equipment to prepare complete instructions and safety regulations to govern in detail the correct and safe use of such equipment. Also see 4.2.  
1.3 The use and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of By-Pass jumpers is covered in four parts as follows:    
Title  
Sections  
Clamps for By-Pass Jumpers  
5 – 17  
Ferrules for By-Pass Jumpers  
18 – 31  
Cable for By-Pass Jumpers  
32 – 40  
By-Pass Jumpers (complete assembly
with clamps, ferrules, and cable)  
41 – 55  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 The values stated in SI units are to be regarded as the standard. See IEEE/ASTM SI 10.  
1.7 The following precautionary caveat pertains only to the test method portions, Sections 13, 26, 48, and 55 of these specifications. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    11 pages
    English language
  • Technical specification
    11 pages
    English language

ABSTRACT
These specifications provides the manufacture and testing, as well as individual design, electrical, mechanical, and workmanship requirements for a system of flexible insulated temporary bypass jumpers used on energized power lines and equipment. These specifications for a system of bypass jumpers are covered in four parts as follows: clamps for bypass jumpers; ferrules for bypass jumpers; cable for bypass jumpers; and bypass jumpers (complete assembly with clamps, ferrules, and cable). The use and maintenance of these equipments are not addressed in these specifications.
SCOPE
1.1 These specifications cover the manufacture and testing of flexible insulated temporary bypass jumpers (bypass jumpers) used on energized power lines and equipment.  
1.2 It is common practice for the user of this protective equipment to prepare complete instructions and safety regulations to govern in detail the correct and safe use of such equipment. Also see 4.2.  
1.3 The use and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of bypass jumpers is covered in four parts as follows:    
Title  
Sections  
Clamps for Bypass Jumpers  
5 – 17  
Ferrules for Bypass Jumpers  
18 – 31  
Cable for Bypass Jumpers  
32 – 40  
Bypass Jumpers (complete assembly
with clamps, ferrules, and cable)  
41 – 55
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 The values stated in SI units are to be regarded as the standard. See ASTM IEEE/ASTM SI 10.  
1.7 The following precautionary caveat pertains only to the test method portions, Sections 13, 26, 48, and 55 of these specifications. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    10 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:
  Sections Clamps for Temporary Protective Grounds4-16  Ferrules for Temporary Protective Grounds17-30  Cables for Temporary Protective Grounds31-39  Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)40-52  
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.  
1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R ≤ 1.8). See Appendix X3.
1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R ≧ 1.8), see Appendix X4.
Note 1—Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.
1.6.2 See Appendix X3 and Appendix X4 for a discussion of these topics.
1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    19 pages
    English language
  • Technical specification
    19 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 These specifications cover the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.
1.2 These specifications discuss methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F 855.
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.
1.5 Units of measurement used in this specification are in the Metric system (SI) with English units given in parentheses.
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    8 pages
    English language

SCOPE
1.1 This specification covers the manufacture and testing of the temporary protective equipotential bond mat used on or around de-energized electrical equipment.  
1.2 It is common practice for users of protective equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.
1.3 The use and maintenance of this equipment is beyond the scope of this specification.
1.4 It is recognized that the use of temporary protective equipotential bond mats requires additional equipment for installation and use, typically temporary connecting jumper assemblies.

  • Technical specification
    3 pages
    English language
  • Technical specification
    3 pages
    English language

SCOPE
1.1 This specification covers the manufacture and testing of the temporary protective equipotential bond mat used on or around de-energized electrical equipment.  
1.2 It is common practice for users of protective equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.
1.3 The use and maintenance of this equipment is beyond the scope of this specification.
1.4 It is recognized that the use of temporary protective equipotential bond mats requires additional equipment for installation and use, typically temporary connecting jumper assemblies.

  • Technical specification
    3 pages
    English language

ABSTRACT
These specifications provides the manufacture and testing, as well as individual design, electrical, mechanical, and workmanship requirements for a system of flexible insulated temporary bypass jumpers used on energized power lines and equipment. These specifications for a system of bypass jumpers are covered in four parts as follows: clamps for bypass jumpers; ferrules for bypass jumpers; cable for bypass jumpers; and bypass jumpers (complete assembly with clamps, ferrules, and cable). The use and maintenance of these equipments are not addressed in these specifications.
SCOPE
1.1 These specifications cover the manufacture and testing of flexible insulated temporary bypass jumpers (bypass jumpers) used on energized power lines and equipment.
1.2 It is common practice for the user of this protective equipment to prepare complete instructions and safety regulations to govern in detail the correct and safe use of such equipment. Also see .
1.3 The use and maintenance of this equipment are beyond the scope of these specifications.
1.4 These specifications for a system of bypass jumpers is covered in four parts as follows:TitleSectionsClamps for Bypass JumpersFerrules for Bypass JumpersCable for Bypass JumpersBypass Jumpers (complete assemblywith clamps, ferrules, and cable)
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.
1.6 The values stated in SI units are to be regarded as the standard. See ASTM SI 10.
The following precautionary caveat pertains only to the test method portions, Sections , , , and of these specifications. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    10 pages
    English language

ABSTRACT
These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment. These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows: clamps, ferrules, cables, and temporary protective grounds. Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification. The clamps shall be subject to design tests for determining mechanical torque strength and electrical short circuit capacity. The ferrules shall be tested for electrical short-circuit capacity and continuous current rating. The elastomer or thermoplastic making up the jacket of the flexible cable shall be tested according to the specified methods.
SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:SectionsClamps for Temporary Protective Grounds4-16 Ferrules for Temporary Protective Grounds17-30 Cables for Temporary Protective Grounds31-39 Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)40-52
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.
1.6 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.
1.7 Currents presented in Table 1 and Table 2 are based upon cable melting times, as determined from equations by I. M. Onderdonk. See Appendix X3.
1.7.1 Currents presented in were determined by use of EPRI Project RP2446 Computer Program RTGC "A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables."
1.7.2 See Appendix X3 and Appendix X4 for a discussion of these values.
The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    19 pages
    English language

SCOPE
1.1 These specifications cover the equipment making up the flexible insulated temporary bypass jumpers (bypass jumpers) used on energized power lines and equipment.
1.2 It is common practice for the user of this protective equipment to prepare complete instructions and safety regulations to govern in detail the correct and safe use of such equipment.
1.3 The use and maintenance of this equipment are beyond the scope of these specifications.
1.4 These specifications for a system of bypass jumpers is covered in four parts as follows:TitleSectionsClamps for Bypass JumpersFerrules for Bypass JumpersCable for Bypass JumpersBypass Jumpers (complete assemblywith clamps, ferrules, and cable)
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.
1.6 The values stated in SI units are to be regarded as the standard. See ASTM SI 10.
1.7 The following precautionary caveat pertains only to the test method portions, Sections 13, 26, and of these specifications.This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    8 pages
    English language

SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.
1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:SectionsClamps for Temporary Protective Grounds4-16 Ferrules for Temporary Protective Grounds17-30 Cables for Temporary Protective Grounds31-39 Protective Grounds (Complete Assembly With Clamps, Ferrules, and Cable)40-52
1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.
1.6 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.
1.7 Currents presented in Table 1 and Table 2 are based upon cable melting times, as determined from equations by I. M. Onderdonk. See Appendix X3.
1.7.1 Currents presented in were determined by use of EPRI Project RP2446 Computer Program RTGC "A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables."
1.7.2 See Appendix X3 and Appendix X4 for a discussion of these values.
The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    19 pages
    English language

ABSTRACT
This specification covers the in-service inspection and electrical testing of temporary protective grounding jumper assemblies used by electrical workers in the field on de-energized electric power lines, circuits, and equipment. These assemblies consist of flexible cables, ferrules, clamps, and connectors. The test procedures detailed here provide an objective means of determining if a grounding jumper assembly meets minimum electrical specifications. The application, care, use, and maintenance of this equipment are not addressed in this specification.
SCOPE
1.1 These specifications cover the in-service inspection and electrical testing of temporary protective grounding jumper assemblies which have been used by electrical workers in the field.
1.2 These specifications discuss methods for testing grounding jumper assemblies, which consist of the flexible cables, ferrules, clamps and connectors used in the temporary protective grounding of de-energized circuits.
1.3 Manufacturing specifications for these grounding jumper assemblies are in Specifications F 855.
1.4 The application, care, use, and maintenance of this equipment are beyond the scope of this specification.
1.5 Units of measurement used in this specification are in the Metric system (SI) with English units given in parentheses.
1.6 The following safety hazards caveat pertains only to the test portions of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

  • Technical specification
    7 pages
    English language

SCOPE
1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.
1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.  
1.3 The use and maintenance of this equipment are beyond the scope of these specifications.  
1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:  Sections Clamps for Temporary Grounding Jumpers 4 to 16 Ferrules for Temporary Grounding Jumpers 17 to 30 Cables for Temporary Grounding Jumpers 31 to 39 Jumpers (complete assembly of clamps, ferrules, and cable) 40 to 53
1.5 Each of the four parts is an entity of itself if desired, but is listed as a part of the system for completeness and clarification.  
1.6 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.  
1.7 Currents presented in Tables 1 and 3 are based upon cable melting times, as determined from equations by I.M. Onderdonk. See Appendix X3.  
1.7.1 Currents presented in Table 5 were determined by use of EPRI Project RP2446 Computer Program RTGC "A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables".  
1.7.2 See Appendix X3 for a discussion of these values.  
1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For a specific precautionary statement, see 32.2.3.

  • Technical specification
    19 pages
    English language

Frequently Asked Questions

F18.45 is a Technical Committee within ASTM International. It is named "Mechanical Apparatus". This committee has published 30 standards.

F18.45 develops ASTM standards in the area of Information technology. Currently, there are 30 published standards from this technical committee.

ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.

A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.

Loading...