CEN/TC 107/WG 5 - Fittings and valves
WG 5 is responsible for EN 448 and 488.
Fittings and valves
WG 5 is responsible for EN 448 and 488.
General Information
This document specifies requirements and test methods for fittings of factory made thermally insulated bonded twin pipe assemblies for hot water networks in accordance with EN 13941 1, comprising two steel service fittings and/or valves, polyurethane foam thermal insulation and one casing of polyethylene.
The pipe assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document covers the following assemblies:
- fittings: bends, T-pieces and reducers;
- valve construction.
This document applies to fitting and valve assemblies with a minimum design pressure of 1,6 MPa (overpressure).
- Standard13 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for factory made thermally insulated bonded valve assemblies for hot water networks in accordance with EN 13941 1, comprising a steel valve, rigid polyurethane foam thermal insulation and a casing of polyethylene.
The valve assembly could also include the following additional elements: measuring wires, spacers and diffusion barriers.
- Standard26 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for straight lengths of factory made thermally insulated bonded twin pipe assemblies for directly buried hot water networks in accordance with EN 13941 1, comprising two steel service pipes, rigid polyurethane foam thermal insulation and one casing of polyethylene.
The pipe assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
- Standard15 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for factory made thermally insulated bonded fitting assemblies for hot water networks in accordance with EN 13941 1, comprising a steel service fitting, rigid polyurethane foam thermal insulation and a casing of polyethylene.
The fitting assembly could also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document covers the following fitting assemblies: bend, tee, reducer, single use compensator and anchor.
This document applies to fitting assemblies with a minimum design pressure of 1,6 MPa (overpressure).
- Standard31 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for fitting and steel valve assemblies of factory made thermally insulated bonded twin pipe assemblies for hot water networks in accordance with EN 13941-1, comprising two steel service pipes, in most cases steel fittings and/or steel valves, steel components, polyurethane (PUR) foam thermal insulation and one casing of polyethylene.
NOTE Steel components can be e.g. fixing bars.
The twin pipe assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document covers the following assemblies:
- fittings: bends, T-pieces and reducers;
- valves for main line.
This document applies to fitting assemblies with an internal pressure of at least 1,6 MPa and steel valve assemblies with a maximum internal pressure of 2,5 MPa.
- Draft18 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for factory made thermally insulated bonded fitting assemblies for hot water networks in accordance with EN 13941-1, comprising a steel service pipe, in most cases a steel fitting, polyurethane (PUR) foam thermal insulation and a casing of polyethylene.
The fitting assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document specifies the characteristics of the following fitting assemblies:
- bends, T-pieces, and reducers.
This document applies to fitting assemblies with a design pressure of at least 1,6 MPa.
- Draft34 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for straight lengths of factory made thermally insulated bonded twin pipe assemblies for directly buried hot water networks in accordance with EN 13941-1, comprising two steel service pipes, polyurethane (PUR) foam thermal insulation and a casing of polyethylene.
The twin pipe assembly can also include the following additional elements: Measuring wires, spacers and diffusion barriers.
- Draft18 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for factory made thermally insulated bonded steel shut-off valve assemblies for hot water networks in accordance with EN 13941-1, comprising a steel valve, valve extension pipes, polyurethane (PUR) foam thermal insulation and a casing of polyethylene.
This document applies to steel valve assemblies with an internal pressure of maximum 2,5 MPa.
The principles of this document can be applied to thermal insulated bonded steel valve assemblies with internal pressures higher than 2,5 MPa, provided that special attention is paid to the effects of pressure.
The steel shut-off valve assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
- Draft27 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements for factory made thermally insulated bonded steel service valve assemblies for filling, draining, venting and operation purposes for directly buried hot and cold water networks in accordance with EN 13941-1, comprising a steel service valve, steel service pipe, polyurethane (PUR) foam thermal insulation and a casing of polyethylene (PE).
This document applies of steel service valve assemblies with an internal pressure of maximum 2,5 MPa.
The principles of this document can be applied to thermal insulated bonded steel service valve assemblies with internal pressures higher than 2,5 MPa, provided that special attention is paid to the effects of pressure.
The steel service valve assembly can also include the following additional elements: measuring wires, spacers, and diffusion barriers.
- Draft14 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for valves of prefabricated thermally insulated valve assemblies comprising a steel valve, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with pre-insulated pipe assemblies in accordance with EN 253. This standard applies only to insulated valve assemblies for continuous operation with hot water at various temperatures in accordance with EN 253, Clause 1 and the valve assemblies with a maximum operation pressure of 25 bar. For higher pressures additional demands apply. Guidelines for quality inspection are given in Annex A of this standard. NOTE For this application the following valve types are commonly used: ball valves, gate valves, and butterfly valves. This standard does not include calculation rules for loads and stresses. These depend on the configuration of the system as it is installed. The design and installation rules are given in EN 13941.
- Draft4 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for valves of prefabricated thermally insulated valve assemblies comprising a steel valve, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with pre-insulated pipe assemblies in accordance with EN 253.
This European Standard applies only to factory made prefabricated insulated valve assemblies for continuous operation with hot water at various temperatures in accordance with EN 253:2009+A1:2013, Clause 1 and the valve assemblies with a maximum operation pressure of 25 bar. For higher pressures, additional demands apply.
NOTE For this application, the following valve types are commonly used: ball valves, gate valves, and butterfly valves.
This European Standard does not include calculation rules for loads and stresses. These depend on the configuration of the system as it is installed. The design and installation rules are given in EN 13941.
- Standard29 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for fittings of prefabricated thermally insulated pipe-in-pipe assemblies comprising a steel service fitting from DN 20 to DN 1200, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with preinsulated pipe assemblies in accordance with EN 253.
This European Standard covers the following fittings: bend, tee, reducer, single use compensator and anchor.
This European Standard applies only to factory made prefabricated fitting assemblies and single use compensators for continuous operation with hot water at various temperatures in accordance with EN 253.
This European Standard applies to fitting assemblies with a minimum design pressure of 16 bar (overpressure) complying with EN 13941.
This European Standard does not include calculation rules for loads and stresses. The design and installation rules, for the system, are given in EN 13941.
- Standard30 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for fittings of prefabricated thermally insulated twin pipe assemblies comprising steel service fittings and/or valves from DN 15 to DN 250, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with preinsulated twin pipe assemblies in accordance with EN 15698 1:2009.
This European Standard covers the following:
- fitting assemblies, such as T-pieces, reducers and anchors;
- valve assemblies.
This European Standard applies only to insulated fitting assemblies for continuous operation with hot water at various temperatures in accordance with the scope EN 15698 1:2009.
This European Standard applies to fitting and valve assemblies with a minimum design pressure of 16 bar (overpressure) complying with EN 13941.
Guidelines for quality inspection and testing of fitting assemblies are given in EN 448:2015, Annex A and EN 15698 1:2009, Annex A.
Guidelines for quality inspection and testing of valve assemblies are given in EN 488:2015, Annex A and EN 15698 1:2009, Annex A.
Procedures for PE-welding are given in EN 448:2015, Annex B.
NOTE This European Standard does not include rules for calculation of loads and stresses.
- Standard16 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for valves of prefabricated thermally insulated valve assemblies comprising a steel valve, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with pre-insulated pipe assemblies in accordance with EN 253.
This European Standard applies only to insulated valve assemblies for continuous operation with hot water at various temperatures in accordance with EN 253:2009, Clause 1 and the valve assemblies with a maximum operation pressure of 25 bar. For higher pressures, additional demands apply.
Guidelines for quality inspection are given in Annex A of this European Standard.
NOTE For this application, the following valve types are commonly used: ball valves, gate valves, and butterfly valves.
This European Standard does not include calculation rules for loads and stresses. These depend on the configuration of the system as it is installed. The design and installation rules are given in EN 13941:2009+A1:2010.
- Standard30 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for fittings of prefabricated thermally insulated pipe-in-pipe assemblies comprising a steel service fitting from DN 20 to DN 1200, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with preinsulated pipe assemblies in accordance with EN 253.
This European Standard covers the following fittings: bends, T-pieces, reducers, single use compensators and anchors.
This European Standard applies only to insulated fitting assemblies and single use compensators for continuous operation with hot water at various temperatures in accordance with EN 253:2009, Clause 1.
This European Standard applies to fitting assemblies with a minimum design pressure of 16 bar (overpressure) complying with EN 13941.
Guidelines for quality inspection are given in Annex A of this European Standard.
Procedures for PE-welding are given in Annex B of this European Standard.
NOTE This European Standard does not include rules for calculation of loads and stresses.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for valves of prefabricated thermally insulated valve assemblies comprising a steel valve, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with pre-insulated pipe assemblies in accordance with EN 253.
This European Standard applies only to insulated valve assemblies for continuous operation with hot water at various temperatures in accordance with EN 253:2009, Clause 1 and the valve assemblies with a maximum operation pressure of 25 bar. For higher pressures, additional demands apply.
Guidelines for quality inspection are given in Annex A of this European Standard.
NOTE For this application, the following valve types are commonly used: ball valves, gate valves, and butterfly valves.
This European Standard does not include calculation rules for loads and stresses. These depend on the configuration of the system as it is installed. The design and installation rules are given in EN 13941.
- Standard32 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for valves of prefabricated thermally insulated valve assemblies comprising a steel valve, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with preinsulated pipe assemblies in accordance with prEN 253.
This standard applies only to insulated valve assemblies for continuous operation with hot water at various temperatures in accordance with clause 1 of prEN 253:2002.
Guidelines for quality inspection are given in annex A of this standard.
Guidelines for installation of valves are given in annex B of this standard.
NOTE For this application the following valve types are commonly used: Ball valves, gate valves, and butterfly valves.
NOTE This standard does not include rules for calculation of loads and stresses.
- Standard16 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies requirements and test methods for fittings of prefabricated thermally insulated pipe-in-pipe assemblies comprising a steel service fitting from DN 20 to DN 1200, rigid polyurethane foam insulation and an outer casing of polyethylene for use in directly buried hot water networks with preinsulated pipe assemblies in accordance with prEN 253.
This standard covers the following fittings: Bends, T-pieces, reducers and anchors.
This standard applies only to insulated fitting assemblies for continuous operation with hot water at various temperatures in accordance with clause 1 of prEN 253:2002.
Guidelines for quality inspection are given in annex A of this standard.
Procedures for PE-welding are given in annex B of this standard.
NOTE This standard does not include rules for calculation of loads and stresses.
- Standard28 pagesEnglish languagesale 10% offe-Library read for1 day