The present document contains requirements for:
- the output performance of the direct current (DC) power equipment at the interface "A";
- the input of the telecommunications equipment connected to interface "A" powered by DC.
The DC voltage at interface "A" may be derived from the AC primary supply. The DC supply may incorporate a backup battery. If any other equipment e.g. datacom equipment, are connected to interface "A" in parallel to telecommunications equipment, all requirements addressed in clause 4 of the present document must be fulfilled. The present document aims at providing compatibility between the power supply equipment and the power consuming telecommunications equipment, and also between different system blocks connected to the same power supply. NOTE 1: The present document is applicable only to -48 VDC power supply interfaces. However, during a
transitional period, other DC voltages may be used in existing installations. Annex A gives guidance on working in conjunction with existing -60 VDC supply systems.
The power supply interface, interface "A", is a physical point to which all the requirements are related (see figure 1). This point is situated between the power supply system(s) and the power consuming telecommunications equipment. NOTE 2: Interface "A" is located at the power terminals of the telecommunications equipment. Subject to the installation preconditions this point may be located at any other point between the power supply system and the telecommunications equipment by mutual agreement of the relevant parties. The requirements at interface "A" apply to:
- the output of the power supply equipment or power supply installation of telecommunications centres;
- the power supply input of telecommunications equipment installed at telecommunication centres;
- telecommunications equipment, installed in customers' premises, whose DC interface "A" is also used by equipment requiring a supply to this specification.
NOTE 3: Normally there is more than one load unit connected to interface "A". In these cases, interface "A" will undergo further restrictions with respect to noise limits or other disturbances specified in clause 4.8. NOTE 4: Disturbances on the power supply interface "A" relating to the continuous wave phenomena below 20 kHz are covered within the present document.
NOTE 5: An example of a configuration in which interface "A" is identified is given in annex D.
- Standard33 pagesEnglish languagesale 10% offe-Library read for1 day
The present document contains requirements for:
- the output performance of the direct current (dc) power equipment at the interface "A";
- the input of the telecommunications equipment connected to interface "A" powered by dc.
The dc voltage at interface "A" may be derived from the AC primary supply. The dc supply may incorporate a backup battery. If any other equipment e.g. datacom equipment, are connected to interface "A" in parallel to telecommunications equipment, all requirements addressed in clause 4 of the present document must be fulfilled. The present document aims at providing compatibility between the power supply equipment and the power consuming telecommunications equipment, and also between different system blocks connected to the same power supply. NOTE 1: The present document is applicable only to -48 Vdc power supply interfaces. However, during a transitional period, other dc voltages may be used in existing installations. Annex A gives guidance on working in conjunction with existing -60 Vdc supply systems. The power supply interface, interface "A", is a physical point to which all the requirements are related (see figure 1). This point is situated between the power supply system(s) and the power consuming telecommunications equipment.
NOTE 2: Interface "A" is located at the power terminals of the telecommunications equipment. Subject to the installation preconditions this point may be located at any other point between the power supply system and the telecommunications equipment by mutual agreement of the relevant parties. The requirements at interface "A" apply to:
- the output of the power supply equipment or power supply installation of telecommunications centres;
- the power supply input of telecommunications equipment installed at telecommunication centres;
- telecommunications equipment, installed in customers' premises, whose dc interface "A" is also used by equipment requiring a supply to this specification.
NOTE 3: Normally there is more than one load unit connected to interface "A". In these cases, interface "A" will undergo further restrictions with respect to noise limits or other disturbances specified in clause 4.8. NOTE 4: Disturbances on the power supply interface "A" relating to the continuous wave phenomena below 20 kHz are covered within the present document. NOTE 5: An example of a configuration in which interface "A" is identified is given in annex D.
- Standard33 pagesEnglish languagesale 10% offe-Library read for1 day
The present document contains harmonized definitions and measurement methods for a range of user perceivable Quality of Service (QoS) parameters for the voice telephony service. The set of parameters have been produced in response to the ONP Voice Telephony Directive 98/10/EC. The present document addresses the parameters listed in annex 3 of the Directive.The purpose of these parameters is to define objective and comparable measures of the QoS delivered to
users/customers for use by NRAs as set out in the Directive. The establishment of target values for QoS is beyond the scope of the present document. The Quality of Service parameters apply to the services governed by the Voice Telephony Directive (98/10/EC [1]), i.e. fixed public telephone services, irrespective of the network technology chosen by the service provider, e.g. PSTN,
ISDN or other technology, and the destination of the call. The parameters specified apply to fixed public telephony services irrespective of whether supplementary services are offered, subscribed to or invoked for a particular call. Annex E provides a proforma for the provision of statistics to an NRA.
- Guide27 pagesEnglish languagesale 10% offe-Library read for1 day