ASTM F1735-96
(Specification)Standard Specification for Poly (Vinyl Chloride) (PVC) Profile Strip for PVC Liners for Rehabilitation of Existing Man-Entry Sewers and Conduits
Standard Specification for Poly (Vinyl Chloride) (PVC) Profile Strip for PVC Liners for Rehabilitation of Existing Man-Entry Sewers and Conduits
SCOPE
1.1 This specification covers requirements and test methods for materials, dimensions, workmanship, extrusion quality, and a form of marking for extruded poly (vinyl chloride)(PVC) profile strips used for field fabrication of PVC liners for existing man-entry (36 to 144 in. (900 to 3650 mm) in vertical dimension) sewer and conduit rehabilitation.
1.2 Profile strip produced to this specification is for use in field fabrication of PVC liners in non-pressure pipe and conduit rehabilitation where the liner is installed into the existing sewer or conduit and the annular space between the liner and the existing sewer or conduit is grouted with cementitious grout.
Note 1—The practice for the installation of PVC liner covered by this specification is Practice F 1698.
1.3 This specification includes extruded profile strips made only from materials specified in 6.1.
1.4 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or
withdrawn. Contact ASTM International (www.astm.org) for the latest information.
Designation: F 1735 – 96
AMERICAN SOCIETY FOR TESTING AND MATERIALS
100 Barr Harbor Dr., West Conshohocken, PA 19428
Reprinted from the Annual Book of ASTM Standards. Copyright ASTM
Standard Specification for
Poly (Vinyl Chloride) (PVC) Profile Strip for PVC Liners for
1
Rehabilitation of Existing Man-Entry Sewers and Conduits
This standard is issued under the fixed designation F 1735; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
3
1. Scope moplastic Pipe and Fittings
D 2152 Test Method For Degree Of Fusion Of Extruded
1.1 This specification covers requirements and test methods
Poly (Vinyl Chloride) (PVC) Pipe And Molded Fittings By
for materials, dimensions, workmanship, extrusion quality, and
3
Acetone Immersion
a form of marking for extruded poly (vinyl chloride) (PVC)
D 2240 Test Method for Rubber Property—Durometer
profile strips used for field fabrication of PVC liners for
4
Hardness
existing man-entry (36 to 144 in. (900 to 3650 mm) in vertical
F 412 Definitions Of Terms Relating To Plastic Piping
dimension) sewer and conduit rehabilitation.
3
Systems
1.2 Profile strip produced to this specification is for use in
2.2 Federal Standard:
field fabrication of PVC liners in non-pressure pipe and conduit
Federal Standard No. 123 Marking For Shipment (Civil
rehabilitation where the liner is installed into the existing sewer
5
Agencies)
or conduit and the annular space between the liner and the
2.3 Military Standard:
existing sewer or conduit is grouted with cementitious grout.
5
MIL-STD-129 Marking for Shipment and Storage
NOTE 1—An ASTM Practice for the installation of PVC liner is under
3. Terminology
preparation and will be referenced in this specification when published.
3.1 General—Definitions are in accordance with Terminol-
1.3 This specification includes extruded profile strips made
ogy D 883 and Terminology F 412. Abbreviations are in
only from materials specified in 6.1.
accordance with Terminology D 1600, unless otherwise indi-
1.4 The values stated in inch-pound units are to be regarded
cated.
as the standard. The values given in parentheses are for
3.2 Definitions of Terms Specific to this Standard—See Fig.
information only.
1, to clarify terminology.
1.5 This standard does not purport to address all of the
3.2.1 coextruded flexible PVC seal, n—a flexible (soft) bead
safety concerns, if any, associated with its use. It is the
of PVC coextruded in the joiner strip to provide compression
responsibility of the user of this standard to establish appro-
sealing of the mechanical joint made when the joiner strip
priate safety and health practices and determine the applica-
locks adjacent edges of former strip.
bility of regulatory limitations prior to use.
3.2.2 extruded PVC joiner strip, n—a companion product to
2. Referenced Documents
the profile former strip of such configuration as to provide the
locking mechanism at the edges of the former strips.
2.1 ASTM Standards:
3.2.3 extruded PVC profile former strip, n—a product,
D 618 Practice for Conditioning Plastics and Electrical
2
available in various sizes, consisting of a smooth inner surface
Insulating Materials For Testing
and a ribbed outer surface (profile) with edge configurations to
D 790 Test Method for Flexural Properties of Unreinforced
allow mechanical locking of adjacent strips.
and Reinforced Plastics and Electrical Insulating Materi-
2
3.2.4 production run, n—a continuous extrusion of a given
als
2
profile type.
D 883 Terminology Relating To Plastics
2
3.2.5 PVC liner, n—a product field fabricated from extruded
D 1600 Abbreviations Of Terms Relating To Plastic
PVC profile strip into a shape which substantially conforms to
D 1784 Specification For Rigid Poly (Vinyl Chloride)
the shape of the inner surface of the existing pipe or conduit
(PVC) Compounds And Chlorinated Poly (Vinyl Chloride)
2
over some portion or all of its inner circumference.
(CPVC) Compounds
D 2122 Test Method of Determining Dimensions of Ther-
4. Significance and Use
4.1 The requirements of this specification are intended to
1
This specification is under the jurisdiction of ASTM Committee F-17 on Plastic
3
Piping Systems and is the direct responsibility of Subcommittee F17.67 on Annual Book of ASTM Standards, Vol 08.04.
4
Trenchless Plastic Pipeline Technology. Annual Book of ASTM Standards, Vol 09.01.
5
Current edition approved Oct. 10, 1996. Published November 1997. Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700
2
Annual Book of ASTM Standards, Vol 08.01. Robbins Ave., Philadelphia, PA 19111–5094, Attn: NPODS.
1
---------------------- Page: 1 -----
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.