ASTM C937-16
(Specification)Standard Specification for Grout Fluidifier for Preplaced-Aggregate Concrete
Standard Specification for Grout Fluidifier for Preplaced-Aggregate Concrete
ABSTRACT
This specification covers fluidifier for grout used for preplaced-aggregate (PA) concrete. Grout ingredients shall conform to the specified requirements for Portland cement, pozzolan, and fine aggregate composition. The fluidifier, tested in grout shall conform to the specified values of reduction in mixing water, expansion, bleeding, increase in water retentivity, initial and final setting time, and compressive strength.
SCOPE
1.1 This specification covers fluidifier for grout used for preplaced-aggregate (PA) concrete.
1.2 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.3 The following precautionary caveat pertains only to the test method portion, Section 8, of this standard: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C937 − 16
Standard Specification for
1
Grout Fluidifier for Preplaced-Aggregate Concrete
This standard is issued under the fixed designation C937; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope* C941 Test Method for Water Retentivity of Grout Mixtures
for Preplaced-Aggregate Concrete in the Laboratory
1.1 This specification covers fluidifier for grout used for
C942 Test Method for Compressive Strength of Grouts for
preplaced-aggregate (PA) concrete.
Preplaced-Aggregate Concrete in the Laboratory
1.2 The values stated in SI units are to be regarded as
C953 Test Method for Time of Setting of Grouts for
standard. No other units of measurement are included in this
Preplaced-Aggregate Concrete in the Laboratory
standard.
3. Terminology
1.3 The following precautionary caveat pertains only to the
test method portion, Section 8, of this standard: This standard 3.1 Definitions:
does not purport to address all of the safety concerns, if any,
3.1.1 For definitions of terms used in this test method, refer
associated with its use. It is the responsibility of the user of this to Terminologies C125 and C219.
standard to establish appropriate safety and health practices
4. Ordering Information
and determine the applicability of regulatory limitations prior
to use.
4.1 The purchaser shall specify the material desired as
“grout fluidifier for preplaced-aggregate concrete.” The mate-
2. Referenced Documents
rial shall meet the requirements of this specification.
2
2.1 ASTM Standards:
5. Materials
C33/C33M Specification for Concrete Aggregates
5.1 Grout ingredients shall conform to the following re-
C125 Terminology Relating to Concrete and Concrete Ag-
quirements:
gregates
5.1.1 Portland cement shall meet the requirements of Speci-
C150/C150M Specification for Portland Cement
fication C150/C150M for the type to be used.
C219 Terminology Relating to Hydraulic Cement
5.1.2 Pozzolan shall meet the requirements of Specification
C618 Specification for Coal Fly Ash and Raw or Calcined
C618.
Natural Pozzolan for Use in Concrete
5.1.3 Fine aggregate shall meet the requirements of Speci-
C637 Specification for Aggregates for Radiation-Shielding
fication C33/C33M except that grading shall conform to
Concrete
Specification C637, Table number 2, Grading 1 for Fine
C938 Practice for Proportioning Grout Mixtures for
Aggregate.
Preplaced-Aggregate Concrete
C939/C939M Test Method for Flow of Grout for Preplaced-
6. Physical Requirements
Aggregate Concrete (Flow Cone Method)
6.1 The fluidifier, when tested in grout as specified herein,
C940 Test Method for Expansion and Bleeding of Freshly
shall conform to the requirements of Table 1.
Mixed Grouts for Preplaced-Aggregate Concrete in the
Laboratory
7. Sampling
7.1 The test sample of fluidifier shall have a mass of at least
1
This specification is under the jurisdiction of ASTM Committee C09 on 225 g and shall be representative of the material supplied. If
Concrete and Concrete Aggregates and is the direct responsibility of Subcommittee
feasible, the test sample shall be composited from grab samples
C09.41 on Hydraulic Cement Grouts.
taken from not fewer than four packages selected at random.
Current edition approved Feb. 1, 2016. Published March 2016. Originally
approved in 1980. Last previous edition approved in 2010 as C937–10. DOI:
8. Test Methods
10.1520/C0937-16.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
8.1 Summary of Method—Physical properties of grout con-
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
taining fluidifier are determined and compared with corre-
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. sponding properties of grout made without fluidifier.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C937 − 16
TABLE 1 Physical Requirements for Grout with Fluidifier
and charge ingredients within a period of 2 min in the
Reduction in mixing water, following order: water, fluidifier (if used), pozzolan, cement,
min, % of control 1
and fine aggregate. Mix for 3 to 3 ⁄4 min.
(Test Method C939/C939M) 3
8.3.3.5 Determine time of efflux by Test Method C939/
Expansion Limits, %: . . .
C939M. If within acceptable range, proceed with tests to
provide data required for the ca
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C937 − 10 C937 − 16
Standard Specification for
1
Grout Fluidifier for Preplaced-Aggregate Concrete
This standard is issued under the fixed designation C937; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope*
1.1 This specification covers fluidifier for grout used for preplaced-aggregate (PA) concrete.
1.2 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information purposes
only.standard. No other units of measurement are included in this standard.
1.3 The following precautionary caveat pertains only to the test method portion, Section 98, of this standard: This standard does
not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard
to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C33C33/C33M Specification for Concrete Aggregates
C125 Terminology Relating to Concrete and Concrete Aggregates
C150C150/C150M Specification for Portland Cement
C219 Terminology Relating to Hydraulic Cement
C618 Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
C637 Specification for Aggregates for Radiation-Shielding Concrete
C938 Practice for Proportioning Grout Mixtures for Preplaced-Aggregate Concrete
C939C939/C939M Test Method for Flow of Grout for Preplaced-Aggregate Concrete (Flow Cone Method)
C940 Test Method for Expansion and Bleeding of Freshly Mixed Grouts for Preplaced-Aggregate Concrete in the Laboratory
C941 Test Method for Water Retentivity of Grout Mixtures for Preplaced-Aggregate Concrete in the Laboratory
C942 Test Method for Compressive Strength of Grouts for Preplaced-Aggregate Concrete in the Laboratory
C953 Test Method for Time of Setting of Grouts for Preplaced-Aggregate Concrete in the Laboratory
3. Terminology
3.1 Definitions:
3.1.1 For definitions of terms used in this test method, refer to Terminologies C125 and C219.
4. Ordering Information
4.1 The purchaser shall specify the material desired as “grout fluidifier for preplaced-aggregate concrete.” The material shall
meet the requirements of this specification.
5. Materials
5.1 Grout ingredients shall conform to the following requirements:
5.1.1 Portland cement shall meet the requirements of Specification C150C150/C150M for the type to be used.
5.1.2 Pozzolan shall meet the requirements of Specification C618.
1
This specification is under the jurisdiction of ASTM Committee C09 on Concrete and Concrete Aggregates and is the direct responsibility of Subcommittee C09.41 on
Hydraulic Cement Grouts.
Current edition approved June 15, 2010Feb. 1, 2016. Published July 2010March 2016. Originally approved in 1980. Last previous edition approved in 20022010 as
C937–02.–10. DOI: 10.1520/C0937-10.10.1520/C0937-16.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C937 − 16
TABLE 1 Expansion Limits
Alkali Content of Cement, %
Expansion Limits, %
Expressed as Na O
2
0.80 or more 7 to 14
0.40 to 0.79 5 to 12
0.39 or less 3 to 9
TABLE 1 Physical Requirements for Grout with Fluidifier
Reduction in mixing water,
min, % of control
(Test Method C939/C939M) 3
Expansion Limits, %: . . .
Expansion, 3 h after mixing,
(Test Method C940)
with the fluidifier: . . .
0.80 or more Alkali Content of Cement,
% expressed as Na O 7 to 14
2
0.40 to 0.79 Alkali Content of Cement,
% expressed as Na O 5 to 12
2
0.39 or less Alkali Content of Cement,
% expressed as Na O 3 to 9
2
Bleeding, 3 h after mixing,
(Test Method C940),
max, % with the fluidifier 2
Increase in water retentivity
(Test Method C941),
min, % of control 60
Initial setting time, min, h
(Test Method C953) 4
Final setting time, max, h
(Test M
...