Standard Specification for Perpendicularly Oriented Mineral Fiber Roll and Sheet Thermal Insulation for Pipes and Tanks

ABSTRACT
This specification covers perpendicularly oriented mineral fiber roll and sheet thermal insulation for use on the flat, curved, or round surfaces of pipes and tanks. The orientation of the rock, slag, or glass fibers within the roll or sheet insulation is essentially perpendicular to the heated/cooled surface. Materials covered in this specification do not include flat block, board, duct wrap, or preformed pipe mineral fiber insulation where the insulation fiber orientation is generally parallel to the heated/cooled surface. In low-temperature applications, properly installed protective vapor retarders should be used to prevent water vapor from moving through or around the insulation towards the colder surface. The materials are classified into six types according to the maximum use temperature and maximum apparent thermal conductivity and into two categories according to minimum compressive resistance. Samples taken from the materials should be tested according to the recommended procedures and should conform to the required values of corrosiveness to steel, stress corrosion to austenitic stainless steel, shot content, maximum use temperature, maximum exothermic temperature rise, and compressive resistance.
SCOPE
1.1 This specification covers the composition, dimensions, and physical properties of compression-resistant, perpendicularly oriented mineral fiber (rock, slag, or glass) roll and sheet insulation intended for use on flat, curved, or round surfaces up to 1000°F (538°C). This product (pipe and tank insulation) is typically used on nominal 24 in. (610 mm) or greater diameter surfaces. For specific applications, the actual use temperatures and diameters shall be agreed upon between the manufacturer and the purchaser.
1.2 The orientation of the fibers within the roll or sheet insulation is essentially perpendicular to the heated/cooled surface (parallel to heat flow). This specification does not apply to flat block, board, duct wrap, or preformed pipe mineral fiber insulation where the insulation fiber orientation is generally parallel to the heated/cooled surface (across the heat flow).
1.3 For satisfactory performance, properly installed protective vapor retarders must be used in low-temperature (below ambient) applications to prevent movement of water vapor through or around the insulation towards the colder surface.
1.4 The values stated in inch-pound units are to be regarded as standard. The SI equivalents of inch-pound units are given in parentheses for information only and may be approximate.
1.5 When the installation or use of thermal materials, accessories, and systems may pose safety or health problems, the manufacturer shall provide the user-appropriate current information regarding any known problems associated with the recommended use of the company's products and shall also recommend protective measures to be employed in their safe utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Aug-2006
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1393-00a(2006)e1 - Standard Specification for Perpendicularly Oriented Mineral Fiber Roll and Sheet Thermal Insulation for Pipes and Tanks
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM C1393-00a(2006)e1 - Standard Specification for Perpendicularly Oriented Mineral Fiber Roll and Sheet Thermal Insulation for Pipes and Tanks
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
e1
Designation: C 1393 – 00a (Reapproved 2006)
Standard Specification for
Perpendicularly Oriented Mineral Fiber Roll and Sheet
Thermal Insulation for Pipes and Tanks
This standard is issued under the fixed designation C1393; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
e NOTE—Sections 2.2 and 11.5 were editorially corrected in June 2008.
1. Scope priate safety and health practices and determine the applica-
bility of regulatory limitations prior to use.
1.1 This specification covers the composition, dimensions,
and physical properties of compression-resistant, perpendicu-
2. Referenced Documents
larly oriented mineral fiber (rock, slag, or glass) roll and sheet
2.1 ASTM Standards:
insulationintendedforuseonflat,curved,orroundsurfacesup
C165 Test Method for Measuring Compressive Properties
to 1000°F (538°C). This product (pipe and tank insulation) is
of Thermal Insulations
typically used on nominal 24 in. (610 mm) or greater diameter
C168 Terminology Relating to Thermal Insulation
surfaces. For specific applications, the actual use temperatures
C177 Test Method for Steady-State Heat Flux Measure-
and diameters shall be agreed upon between the manufacturer
ments and Thermal Transmission Properties by Means of
and the purchaser.
the Guarded-Hot-Plate Apparatus
1.2 The orientation of the fibers within the roll or sheet
C303 Test Method for Dimensions and Density of Pre-
insulation is essentially perpendicular to the heated/cooled
formed Block and Board−Type Thermal Insulation
surface(paralleltoheatflow).Thisspecificationdoesnotapply
C390 Practice for Sampling and Acceptance of Thermal
toflatblock,board,ductwrap,orpreformedpipemineralfiber
Insulation Lots
insulation where the insulation fiber orientation is generally
C411 Test Method for Hot-Surface Performance of High-
parallel to the heated/cooled surface (across the heat flow).
Temperature Thermal Insulation
1.3 For satisfactory performance, properly installed protec-
C447 Practice for Estimating the Maximum Use Tempera-
tive vapor retarders must be used in low-temperature (below
ture of Thermal Insulations
ambient) applications to prevent movement of water vapor
C518 Test Method for Steady-State Thermal Transmission
through or around the insulation towards the colder surface.
Properties by Means of the Heat Flow Meter Apparatus
1.4 The values stated in inch-pound units are to be regarded
C665 Specification for Mineral-Fiber Blanket Thermal In-
as standard. The SI equivalents of inch-pound units are given
sulation for Light Frame Construction and Manufactured
in parentheses for information only and may be approximate.
Housing
1.5 When the installation or use of thermal materials,
C680 Practice for Estimate of the Heat Gain or Loss and
accessories, and systems may pose safety or health problems,
the Surface Temperatures of Insulated Flat, Cylindrical,
the manufacturer shall provide the user-appropriate current
and Spherical Systems by Use of Computer Programs
informationregardinganyknownproblemsassociatedwiththe
C795 Specification for Thermal Insulation for Use in Con-
recommended use of the company’s products and shall also
tact with Austenitic Stainless Steel
recommend protective measures to be employed in their safe
C 1045 Practice for Calculating Thermal Transmission
utilization. The user shall establish appropriate safety and
Properties Under Steady-State Conditions
health practices and determine the applicability of regulatory
C1058 Practice for Selecting Temperatures for Evaluating
requirements prior to use.
and Reporting Thermal Properties of Thermal Insulation
1.6 This standard does not purport to address all of the
C1104/C1104M Test Method for Determining the Water
safety concerns, if any, associated with its use. It is the
Vapor Sorption of Unfaced Mineral Fiber Insulation
responsibility of the user of this standard to establish appro-
C 1114 TestMethodforSteady-StateThermalTransmission
This specification is under the jurisdiction of ASTM Committee C16 on
Thermal Insulation and is the direct responsibility of Subcommittee C16.20 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Homogeneous Inorganic Thermal Insulations. contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved Sept. 1, 2006. Published September 2006. Originally Standards volume information, refer to the standard’s Document Summary page on
approved in 2000. Last previous edition approved in 2000 as C1393-00a. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
e1
C 1393 – 00a (2006)
Properties by Means of the Thin-Heater Apparatus shown in Table 1. This classification is based upon the
C1136 Specification for Flexible, Low Permeance Vapor maximum use temperature, maximum apparent thermal con-
Retarders for Thermal Insulation ductivity, and compressive resistance properties.
C1335 TestMethodforMeasuringNon-FibrousContentof 4.1.1 Types:
Man-Made Rock and Slag Mineral Fiber Insulation 4.1.1.1 Type I—Maximum use temperature up to 450°F
E84 Test Method for Surface Burning Characteristics of (232°C).
Building Materials 4.1.1.2 Type II—Maximum use temperature up to 650°F
2.2 Other Referenced Documents: (343°C).
CAN/ULC-S102 Standard Method of Test for Surface 4.1.1.3 Type IIIA—Maximum use temperature up to 850°F
BurningCharacteristicsofBuildingMaterialsandAssem- (454°C).
blies 4.1.1.4 Type IIIB—Maximum use temperature up to 850°F
(454°C).
3. Terminology
4.1.1.5 Type IVA—Maximum use temperature up to 1000°F
3.1 Definitions—Definitions pertaining to insulation are in (538°C).
accordance with Terminology C168. 4.1.1.6 Type IVB—Maximum use temperature up to 1000°F
(538°C).
3.2 Definitions of Terms Specific to This Standard:
3.2.1 delivered density—the actual density of the product 4.1.2 Categories:
4.1.2.1 Category 1—Greater minimum compressive resis-
shipped by the manufacturer or the seller and received by the
purchaser. tance properties are required.
3.2.2 facing—alayerorfoundationofthinmaterialwhichis 4.1.2.2 Category 2—Lesser minimum compressive resis-
adhered to the insulation to form a continuous roll or sheet of tance properties are required.
insulation.
5. Ordering Information
3.2.3 mean temperature—the sum of the cold surface tem-
5.1 The type, category, dimensions, and facing shall be
perature and the hot surface temperature divided by two.
specified by the purchaser. Shot content and delivered density
4. Classification certificationmayberequestedbythepurchaserafterconsulting
with the supplier or the manufacturer.
4.1 Mineral fiber roll or sheet insulation covered by this
specification is classified into the six types and two categories
6. Materials and Manufacture
6.1 Composition—Mineral fiber roll or sheet shall be com-
posed of rock, slag, or glass processed from the molten state
Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarbor-
into fibrous form, bonded with an organic binder, and the
ough, Ontario, Canada M1R 3A9.
A
TABLE 1 Physical Property Requirements
Properties Type I Type II Type IIIA Type IIIB Type IVA Type IVB
Maximum Use Temperature,° F (°C) Up to 450 (232) 650 (343) 850 (454) 850 (454) 1000 (538) 1000 (538)
See Caution in 6.2.1
Apparent thermal conductivity Maximum Btu
in./h·ft °F (W/m·K) Mean temperature,° F (°C)
75 (24) 0.27(0.039) 0.27(0.039) 0.27(0.039) 0.27(0.039) 0.27(0.039) 0.28(0.040)
100 (38) 0.29(0.042) 0.29(0.042) 0.29(0.042) 0.29(0.042) 0.29(0.042) 0.30(0.043)
200 (93) 0.38(0.055) 0.38(0.055) 0.38(0.055) 0.36(0.052) 0.36(0.052) 0.36(0.052)
300 (149) 0.48(0.069) 0.48(0.069) 0.48(0.069) 0.45(0.065) 0.45(0.065) 0.43(0.062)
400 (204) 0.61(0.088) 0.61(0.088) 0.61(0.088) 0.54(0.078) 0.54(0.078) 0.50(0.072)
500 (260) 0.81(0.117) 0.81(0.117) 0.66(0.095) 0.66(0.095) 0.58(0.084)
600 (316) 0.82(0.118) 0.67(0.097)
Category 1—Greater compressive resistance,
minimum load required to produce a 10 % 120 (5.7) 120 (5.7) 120 (5.7) 120 (5.7) 120 (5.7) 200 (9.6)
reduction in thickness, lb/ft (kPa)
Category 2—Lesser compressive resistance,
minimum load required to produce a 10 % 25 (1.2) 25 (1.2) 25 (1.2) 25 (1.2) 25 (1.2) 25 (1.2)
reduction in thickness, lb/ft (kPa)
Water vapor sorption, max % by weight 5.0 5.0 5.0 5.0 5.0 5.0
3 3 B
Density, maximum lb/ft (kg/m ) 6 (96) 6 (96) 6 (96) 6 (96) 6 (96) 8 (128)
Surface burning characteristics:
Maximum flame spread index 25 25 25 25 25 25
Maximum smoke developed index 50 50 50 50 50 50
A
Refer to Section 7 for additional physical property requirements.
B
The maximum density specified is for weight design purposes only. Additional density requirements may be specified as agreed upon between the purchaser and the
manufacturer.
e1
C 1393 – 00a (2006)
orientation of the fibers within the roll or sheet insulation is flame, or glow during hot surface exposure. No evidence of
essentially perpendicular to the heated or cooled surface melting or fiber degradation shall be evident upon posttest
(parallel to heat flow). inspection.
7.6 Maximum Exothermic Temperature Rise—When tested
6.2 Facings:
in accordance with 11.1, the midpoint temperature shall not at
6.2.1 The purchaser must specify the insulation facing and
any point in time exceed the hot surface temperature by more
type required. (Warning—The user is advised that the maxi-
than200°F(111°C).The200°Fcriterionappliesduringheatup
mum use temperature of the facings and adhesives may be
as well as steady state conditions. Exceeding this limit shall
lowerthanthemaximumusetemperatureoftheinsulation.The
constitute noncompliance to this specification and
specifier shall ensure that sufficient insulation thickness is
rejection.(Warning—Organic binders, adhesives, and some
installed so none of the accessory items (facing and adhesive)
facingsmaythermallydecomposeathightemperaturescausing
are exposed to temperatures above their maximum use tem-
an exothermic temperature rise to occur. A double-layered
perature. Practice C680 can be used to predict surface tem-
installationofperpendicularlyorientedmineralfiberinsulation
peratures.)
andfacingonsurfaceshotterthan450°F(232°C)mayincrease
6.2.2 Typical Facings:
thepossibilityofinternalexothermictemperatureriseandmay
6.2.2.1 Fiber glass nonreinforced mat.
destroy the fiber.)
6.2.2.2 Laminated aluminum foil, reinforced fiber glass
7.7 Compressive Resistance—Shall be tested in accordance
scrim, and natural Kraft paper generally known as FRK or
with 11.8.
FSK.
NOTE 1—At conditions above 450°F (232°C) hot surface temperatures,
6.2.2.3 Laminated white Kraft paper, reinforced fiber glass
the compressive resistance of the installed insulation material may
scrim, and aluminum foil generally known asASJ (All Service
decrease.Contactthemanufacturerforreducedcompressionresistancesat
Jacket).
maximum temperature conditions.
6.2.2.4 All vapor retarder facings shall comply with Speci-
fication C1136. 8. Dimensions and Permissible Variations
6.2.2.5 Other kinds or compositions of facings may be
8.1 Dimensions—Standard sizes of roll and sheet insulation
specified.
are as follows:
6.3 Manufacturing/Fabrication—Mineral (rock, slag, or 8.1.1 Rolls:
glass) fiberboard is normally manufactured with the fiber 8.1.1.1 Length—Willvarydependingonthickness,upto50
essentially oriented parallel with the face or a facing. Fiber ft (15.2 m).
directiondescribedinthisspecificationissubstantiallyperpen- 8.1.1.2 Width—24 in. (610 mm) and 36 in. (914 mm).
1 1
dicular to a facing.This construction aligns mineral fiberboard 8.1.1.3 Thickness— ⁄2 to 6 in. (12.7 to 152 mm) in ⁄2-in.
inawaythatoneendofthecutfiberisadheredtoafacing.The (12.7-mm) increments.
finished product is wound into rolls or cut into sheets. 8.1.2 Sheets:
8.1.2.1 Length—48 in. (1.2 m) and 96 in. (2.4 m).
8.1.2.2 Width—24 in. (610 mm) and 36 in. (914 mm).
7. Physical Properties
1 1
8.1.2.3 Thickness— ⁄2 to 6 in. (12.7 to 152 mm) in ⁄2-in.
7.1 Theperpendicularlyorientedmineralfiberrollandsheet
(12.7-mm) increments.
thermal insulation shall conform to the following requirements
8.2 Dimensional Tolerances—The average measured
in Table 1: maximum use temperature, maximum apparent
length, width, and thickness shall differ from the manufactur-
thermal conductivity, minimum compressive resistance, water
er’s standard dimensions by not more than the following:
vapor sorption, maximum design density, and maximum indi-
Roll Sheet
ces for surface burning characteristics.
Length =−0in. (0 mm) Excess permitted 6 ⁄8 in. (3 mm)
1 1
7.2 Corrosiveness to Steel—Whentestedinaccordancewith Width = 6 ⁄4 in. (6 mm) 6 ⁄8 in. (3 mm)
1 1
Thickness = 6 ⁄16 in. (2 mm) 6 ⁄16 in. (2 mm)
11.6,thecorrosionresultingfromtheinsulationincontactwith
steel plates shall be judged to be no greater than for compara-
9. Workmanship, Finish and Appearance
tiveplatesincontactwithsterilecotton.(Warning—Thereare
9.1 The insulation shall have good workmanship and shall
facingadhesivesthatcancausecorrosiontosteelwhentheyare
not have defects which adversely affect its installation and
in contact with water or water vapor and the steel. Currently,
performance qualities.
there is no test method available to satisfy every potential
corrosion application.)
10. Sampling
7.3 Stress Corrosion to Austenitic Stainless Steel—When
specified, shall be tested and evaluated in accordance with 10.1 Inspectionandqualificationoftheinsulationshallbein
accordance with Criteria C390. Other provisions for sampling
11.9.
can be agreed upon between the purchaser, supplier, and the
7.4 Non-fibrous Content (Shot)—The average maximum
manufacturer.
shot content of rock and slag mineral fiber products shall not
exceed30%byweightinaccordancewith11.3.1.Non-fibrous
11. Test Methods
content is not applicable to glass mineral fiber products.
7.5 Maximum Use Temperature—When tested in accor- 11.1 Maximum Use and Exothermic Rise Temperature—
dance with 11.1, the insulation with facing shall not warp, TestinaccordancewithTestMethodC411andthehotsurface
e1
C 1393 – 00a (2006)
performance section of Practice C447 at the manufacturer’s 11.4.5 Conduct final analysis of the thermal data in accor-
maximum recommended thickness for each temperature. The dance with Practice C1045 to generate a thermal conductivity
test surface shall be at the intended surface temperature when versus temperature relationship for the specimen.
the test begins. 11.4.6 The final step of Practice C1045 analysis would be
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
e1
Designation:C1393–00 Designation: C 1393 – 00a (Reapproved 2006)
Standard Specification for
Perpendicularly Oriented Mineral Fiber Roll and Sheet
Thermal Insulation for Pipes and Tanks
This standard is issued under the fixed designation C 1393; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
e NOTE—Sections 2.2 and 11.5 were editorially corrected in June 2008.
1. Scope
1.1 This specification covers the composition, dimensions, and physical properties of compression-resistant, perpendicularly
orientedmineralfiber(rock,slag,orglass)rollandsheetinsulationintendedforuseonflat,curved,orroundsurfacesupto1000°F
(538°C). This product (pipe and tank insulation) is typically used on nominal 24 in. (610 mm) or greater diameter surfaces. For
specific applications, the actual use temperatures and diameters shall be agreed upon between the manufacturer and the purchaser.
1.2 The orientation of the fibers within the roll or sheet insulation is essentially perpendicular to the heated/cooled surface
(parallel to heat flow). This specification does not apply to flat block, board, duct wrap, or preformed pipe mineral fiber insulation
where the insulation fiber orientation is generally parallel to the heated/cooled surface (across the heat flow).
1.3 Forsatisfactoryperformance,properlyinstalledprotectivevaporretardersmustbeusedinlow-temperature(belowambient)
applications to prevent movement of water vapor through or around the insulation towards the colder surface.
1.4 The values stated in inch-pound units are to be regarded as standard. The SI equivalents of inch-pound units are given in
parentheses for information only and may be approximate.
1.5 When the installation or use of thermal materials, accessories, and systems may pose safety or health problems, the
manufacturer shall provide the user-appropriate current information regarding any known problems associated with the
recommended use of the company’s products and shall also recommend protective measures to be employed in their safe
utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory
requirements prior to use.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2.1 ASTM Standards:
C 165 Test Method for Measuring Compressive Properties of Thermal Insulations
C 168 Terminology Relating to Thermal Insulation Materials
C 177 Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the
Guarded-Hot-Plate Apparatus
C 303Test Method for Density of Preformed Block-Type Thermal Insulation Test Method for Dimensions and Density of
Preformed Block and BoardType Thermal Insulation
C 390Criteria Practice for Sampling and Acceptance of Preformed Thermal Insulation Lots
C 411 Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation
C 447 Practice for Estimating the Maximum Use Temperature of Thermal Insulations
C 518 Test Method for Steady-State Heat Flux Measurements andThermalTransmission Properties by Means of the Heat Flow
Meter Apparatus
C 665 Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
This specification is under the jurisdiction of ASTM Committee C-16 on Thermal Insulation and is the direct responsibility of Subcommittee C16.20 on Homogeneous
Inorganic Thermal Insulation.
Current edition approved Jan. 10, 2000. Published March 2000.
This specification is under the jurisdiction of ASTM Committee C16 on Thermal Insulation and is the direct responsibility of Subcommittee C16.20 on Homogeneous
Inorganic Thermal Insulations.
Current edition approved Sept. 1, 2006. Published September 2006. Originally approved in 2000. Last previous edition approved in 2000 as C 1393 - 00a.
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
, Vol 04.06.volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
e1
C 1393 – 00a (2006)
C 680 Practice for DeterminationEstimate of the Heat Gain or Loss and the Surface Temperatures of Insulated Pipe Flat,
Cylindrical, and EquipmentSpherical Systems by the Use of a Computer Program Programs
C 795 Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel
C 1045 Practice for Calculating Thermal Transmission Properties Under Steady-State Conditions
C 1058 Practice for Selecting Temperatures for Evaluating and Reporting Thermal Properties of Thermal Insulation
C 1104/C 1104M Test Method for Determining the Water Vapor Sorption of Unfaced Mineral Fiber Insulation
C 1114 Test Method for Steady-State Thermal Transmission Properties by Means of the Thin-Heater Apparatus
C 1136 Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation
C 1335 Test Method for Measuring the Non-Fibrous Content of Man-Made Rock and Slag Mineral Fiber Insulation
E 84Test Method for Surface Burning Characteristics of Building Materials Test Method for Surface Burning Characteristics
of Building Materials
2.2 Other Referenced Documents:
CAN/ULC-S102 Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies
3. Terminology
3.1 Definitions— Definitions pertaining to insulation are in accordance with Terminology C 168.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 delivered density—the actual density of the product shipped by the manufacturer or the seller and received by the
purchaser.
3.2.2 facing—a layer or foundation of thin material which is adhered to the insulation to form a continuous roll or sheet of
insulation.
3.2.3 mean temperature—the sum of the cold surface temperature and the hot surface temperature divided by two.
4. Classification
4.1 Mineral fiber roll or sheet insulation covered by this specification is classified into the six types and two categories shown
in Table 1. This classification is based upon the maximum use temperature, maximum apparent thermal conductivity, and
compressive resistance properties.
4.1.1 Types:
Annual Book of ASTM Standards, Vol 04.07.
Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarborough, Ontario, Canada M1R 3A9.
A
TABLE 1 Physical Property Requirements
Properties Type I Type II Type IIIA Type IIIB Type IVA Type IVB
Maximum Use Temperature,° F (°C) Up to 450 (232) 650 (343) 850 (454) 850 (454) 1000 (538) 1000 (538)
See Caution in 6.2.1
Apparent thermal conductivity Maximum Btu
in./h·ft °F (W/m·K) Mean temperature,° F (°C)
75 (24) 0.27(0.039) 0.27(0.039) 0.27(0.039) 0.27(0.039) 0.27(0.039) 0.28(0.040)
100 (38) 0.29(0.042) 0.29(0.042) 0.29(0.042) 0.29(0.042) 0.29(0.042) 0.30(0.043)
200 (93) 0.38(0.055) 0.38(0.055) 0.38(0.055) 0.36(0.052) 0.36(0.052) 0.36(0.052)
300 (149) 0.48(0.069) 0.48(0.069) 0.48(0.069) 0.45(0.065) 0.45(0.065) 0.43(0.062)
400 (204) 0.61(0.088) 0.61(0.088) 0.61(0.088) 0.54(0.078) 0.54(0.078) 0.50(0.072)
500 (260) 0.81(0.117) 0.81(0.117) 0.66(0.095) 0.66(0.095) 0.58(0.084)
600 (316) 0.82(0.118) 0.67(0.097)
Category 1—Greater compressive resistance,
minimum load required to produce a 10 % 120 (5.7) 120 (5.7) 120 (5.7) 120 (5.7) 120 (5.7) 200 (9.6)
reduction in thickness, lb/ft (kPa)
Category 2—Lesser compressive resistance,
minimum load required to produce a 10 % 25 (1.2) 25 (1.2) 25 (1.2) 25 (1.2) 25 (1.2) 25 (1.2)
reduction in thickness, lb/ft (kPa)
Water vapor sorption, max % by weight 5.0 5.0 5.0 5.0 5.0 5.0
3 3 B
Density, maximum lb/ft (kg/m ) 6 (96) 6 (96) 6 (96) 6 (96) 6 (96) 8 (128)
Surface burning characteristics:
Maximum flame spread index 25 25 25 25 25 25
Maximum smoke developed index 50 50 50 50 50 50
A
Refer to Section 7 for additional physical property requirements.
B
The maximum density specified is for weight design purposes only. Additional density requirements may be specified as agreed upon between the purchaser and the
manufacturer.
e1
C 1393 – 00a (2006)
4.1.1.1 Type I—Maximum use temperature up to 450°F (232°C).
4.1.1.2 Type II—Maximum use temperature up to 650°F (343°C).
4.1.1.3 Type IIIA—Maximum use temperature up to 850°F (454°C).
4.1.1.4 Type IIIB—Maximum use temperature up to 850°F (454°C).
4.1.1.5 Type IVA—Maximum use temperature up to 1000°F (538°C).
4.1.1.6 Type IVB—Maximum use temperature up to 1000°F (538°C).
4.1.2 Categories:
4.1.2.1 Category 1—Greater minimum compressive resistance properties are required.
4.1.2.2 Category 2—Lesser minimum compressive resistance properties are required.
5. Ordering Information
5.1 The type, category, dimensions, and facing shall be specified by the purchaser. Shot content and delivered density
certification may be requested by the purchaser after consulting with the supplier or the manufacturer.
6. Materials and Manufacture
6.1 Composition— Mineral fiber roll or sheet shall be composed of rock, slag, or glass processed from the molten state into
fibrous form, bonded with an organic binder, and the orientation of the fibers within the roll or sheet insulation is essentially
perpendicular to the heated or cooled surface (parallel to heat flow).
6.2 Facings:
6.2.1 The purchaser must specify the insulation facing and type required. (CAUTION:Warning—The user is advised that the
maximum use temperature of the facings and adhesives may be lower than the maximum use temperature of the insulation. The
specifier shall ensure that sufficient insulation thickness is installed so none of the accessory items (facing and adhesive) are
exposed to temperatures above their maximum use temperature. Practice C 680 can be used to predict surface temperatures.)
6.2.2 Typical Facings:
6.2.2.1 Fiber glass nonreinforced mat.
6.2.2.2 Laminated aluminum foil, reinforced fiber glass scrim, and natural Kraft paper generally known as FRK or FSK.
6.2.2.3 Laminated white Kraft paper, reinforced fiber glass scrim, and aluminum foil generally known as ASJ (All Service
Jacket).
6.2.2.4 All vapor retarder facings shall comply with Specification C 1136.
6.2.2.5 Other kinds or compositions of facings may be specified.
6.3 Manufacturing/Fabrication—Mineral (rock, slag, or glass) fiberboard is normally manufactured with the fiber essentially
oriented parallel with the face or a facing. Fiber direction described in this specification is substantially perpendicular to a facing.
This construction aligns mineral fiberboard in a way that one end of the cut fiber is adhered to a facing. The finished product is
wound into rolls or cut into sheets.
7. Physical Properties
7.1 The perpendicularly oriented mineral fiber roll and sheet thermal insulation shall conform to the following requirements in
Table 1: maximum use temperature, maximum apparent thermal conductivity, minimum compressive resistance, water vapor
sorption, maximum design density, and maximum indices for surface burning characteristics.
7.2 Corrosiveness to Steel—When tested in accordance with 11.6, the corrosion resulting from the insulation in contact with
steel plates shall be judged to be no greater than for comparative plates in contact with sterile cotton. (Caution:Warning—There
are facing adhesives that can cause corrosion to steel when they are in contact with water or water vapor and the steel. Currently,
there is no test method available to satisfy every potential corrosion application.)
7.3 Stress Corrosion to Austenitic Stainless Steel—When specified, shall be tested and evaluated in accordance with 11.9.
7.4 Non-fibrous Content (Shot) —The average maximum shot content of rock and slag mineral fiber products shall not exceed
30 % by weight in accordance with 11.3.1. Non-fibrous content is not applicable to glass mineral fiber products.
7.5 Maximum Use Temperature—Whentestedinaccordancewith11.1,theinsulationwithfacingshallnotwarp,flame,orglow
during hot surface exposure. No evidence of melting or fiber degradation shall be evident upon posttest inspection.
7.6 Maximum Exothermic Temperature Rise—When tested in accordance with 11.1, the midpoint temperature shall not at any
point in time exceed the hot surface temperature by more than 200°F (111°C). The 200°F criterion applies during heat up as well
as steady state conditions. Exceeding this limit shall constitute noncompliance to this specification and rejection.(Caution:
Warning—Organic binders, adhesives, and some facings may thermally decompose at high temperatures causing an exothermic
temperature rise to occur.Adouble-layered installation of perpendicularly oriented mineral fiber insulation and facing on surfaces
hotter than 450°F (232°C) may increase the possibility of internal exothermic temperature rise and may destroy the fiber.)
7.7 Compressive Resistance—Shall be tested in accordance with 11.8.
NOTE 1—At conditions above 450°F (232°C) hot surface temperatures, the compressive resistance of the installed insulation material may decrease.
Contact the manufacturer for reduced compression resistances at maximum temperature conditions.
8. Dimensions and Permissible Variations
8.1 Dimensions—Standard sizes of roll and sheet insulation are as follows:
e1
C 1393 – 00a (2006)
8.1.1 Rolls:
8.1.1.1 Length—Will vary depending on thickness, up to 50 ft (15.2 m).
8.1.1.2 Width—24 in. (610 mm) and 36 in. (914 mm).
1 1
8.1.1.3 Thickness— ⁄2 to 6 in. (12.7 to 152 mm) in ⁄2-in. (12.7-mm) increments.
8.1.2 Sheets:
8.1.2.1 Length—48 in. (1.2 m) and 96 in. (2.4 m).
8.1.2.2 Width—24 in. (610 mm) and 36 in. (914 mm).
1 1
8.1.2.3 Thickness— ⁄2 to 6 in. (12.7 to 152 mm) in ⁄2-in. (12.7-mm) increments.
8.2 Dimensional Tolerances—The average measured length, width, and thickness shall differ from the manufacturer’s standard
dimensions by not more than the following:
Roll Sheet
Length =−0in. (0 mm) Excess permitted 6 ⁄8 in. (3 mm)
1 1
Width = 6 ⁄4
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.