Standard Specification for Crosslinked Styrene-Butadiene (SBR) Synthetic Rubber Jacket for Wire and Cable

SCOPE
1.1 This specification covers a crosslinked styrene-butadiene (SBR) synthetic rubber compound suitable for use as the outer covering or jacket on insulated electrical wires or cables for heavy-duty service.  
1.2 This jacket is not recommended for installation at a temperature lower than -35°C.
1.3 The values stated in inch-pound units are the standard except in cases where SI units are more appropriate. The values in parentheses are for information only.

General Information

Status
Historical
Publication Date
09-Apr-1999
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM D866-99 - Standard Specification for Crosslinked Styrene-Butadiene (SBR) Synthetic Rubber Jacket for Wire and Cable
English language
1 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn. Contact ASTM
International (www.astm.org) for the latest information.
An American National Standard
Designation: D 866 – 99
Standard Specification for
Crosslinked Styrene-Butadiene (SBR) Synthetic Rubber
Jacket for Wire and Cable
This standard is issued under the fixed designation D866; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope 4. Physical Properties
4.1 The jacket shall conform to the requirements for physi-
1.1 This specification covers a crosslinked styrene-
butadiene(SBR)syntheticrubbercompoundsuitableforuseas cal properties prescribed in Table 1.
the outer covering or jacket on insulated electrical wires or
cables for heavy-duty service.
1.2 This jacket is not recommended for installation at a
A
TABLE 1 Physical Properties
temperature lower than −35°C.
1.3 Whenever two sets of values are presented, in different
Unaged Requirements:
Tensile strength, min, psi (MPa) 1800 (12.4)
units, the values in the first set are the standard, while those in
Elongation at rupture, min, % 300
parentheses are for information only.
B
Tension set, max, % 20
Aged Requirements:
2. Referenced Documents
After oxygen pressure test at 70 6 1°C for 96 h:
Tensile strength, min, psi (MPa) 1400 (9.7)
2.1 ASTM Standards:
Elongation at rupture, min, % 200
D470 TestMethodsforCrosslinkedInsulationsandJackets After Air Oven Test at 70 6 1°C for 168 h:
Tensile strength, min, psi (MPa) 1400 (9.7)
for Wire and Cable
Elongation at rupture, min, % 200
D1711 Terminology Relating to Electrical Insulation
A
The values specified are applicable only to jacket having a nominal wall
thickness of 0.030 in. (0.76 mm) or greater.
3. Terminology
B
Set in 2 in. (50 mm).
3.1 Definitions—For definitions of terms used in this speci-
fication, refer to Terminology D1711.
3.2 Definitions of Terms Specific to This Standard:
5. Sampling
3.2.1 aging (act of), n—exposure of materials to air a
...