Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814

SIGNIFICANCE AND USE
4.1 The methods and procedures set forth in this guide relate to the extension of the fire test results to firestop systems that have not been tested.  
4.2 Users of this guide must have knowledge and understanding of the provisions of Test Method E119 and Test Method E814 including those pertaining to conditions of acceptance.  
4.3 In order to apply some of the principles described in this guide, reference to the original fire test report will be necessary.  
4.4 In Test Method E814, the specimens are subjected to specific laboratory fire test exposure conditions. Differences between the tested assembly and the as-built assembly impact the fire-test-response characteristics. Substitution of different test conditions also impacts the fire-test-response characteristics.  
4.5 The extension of data is valid only for the fire test exposure described in Test Method E814.  
4.6 This guide shall not be used to extrapolate the fire resistance rating to a higher value.  
4.7 Limitations:  
4.7.1 The extension of fire resistance data is to be used only for changes to the tested specimen that fall within normal and reasonable limits of accepted construction practices.  
4.7.2 Conclusions derived from using this guide are valid only if the identified change is the only change in the construction or properties of the components.  
4.7.3 Evaluation of changes to the fire-resistive assembly in which the firestop is installed is governed by the Extension of Data principles in Guide E2032.  
4.8 The statements in this guide are based on a single change to a system.
Note 2: It is possible that multiple changes have a different cumulative effect than that of individual changes evaluated separately. The principles contained herein may provide useful information for the application of sound engineering principles to evaluate the effect of multiple differences between tested and installed firestops.  
4.9 Extensions of data using this document shall be done by individuals...
SCOPE
1.1 This guide covers the extension of results obtained from fire tests performed in accordance with Test Method E814 to applications that have not been tested. Test Method E814 evaluates the duration for which test specimens will contain a fire, retain their integrity, or both during a predetermined fire test exposure. Firestops are intended for use in fire-resistive walls and floors that are evaluated in conformance with Test Method E119.
Note 1: Data obtained from firestops tested in accordance with Test Methods E119 with positive pressure can also be used.  
1.2 This guide is based on principles involving the extension of test data using simple considerations. The acceptance of these principles and their application is based substantially on an analogous worst-case proposition.  
1.3 These principles are only applicable to temperature conditions represented by the standard time-temperature curve described in Test Method E814, for systems falling within the scope of Test Method E814. This test method is a fire-test-response standard.  
1.4 The types of building constructions which are part of this guide are as follows: floors, walls, partitions, floor/ceiling and roof/ceiling assemblies.  
1.5 This guide applies to:  
1.5.1 a single penetrating item, or  
1.5.2 multiple penetrating items.  
1.6 This guide does not apply to joints systems tested to E119, E1966 and E2307.  
1.7 Penetrating items can be one of the following: metallic pipe, non-metallic pipe, metallic tubing, non-metallic tubing, metallic conduit, non-metallic conduit, flexible metal conduit, cables, cable trays, bus ducts, insulated pipes, insulated tubing, insulated conduit, insulated and non-insulated ducts, and structural members.    
Metallic pipe, tubing or conduit  
6.7  
Insulated pipe, tubing or conduit  
6.8  
Non-metallic pipe, tubing or conduit  
6.9 and 6.10  
Flexible metal conduit  
6.11.1.4 and 6.11.1.5  
Cables  
...

General Information

Status
Historical
Publication Date
31-Oct-2017
Technical Committee
Drafting Committee
Current Stage
Ref Project

Buy Standard

Guide
ASTM E2750-17 - Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview
Guide
REDLINE ASTM E2750-17 - Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E2750 − 17 An American National Standard
Standard Guide for
Extension of Data from Penetration Firestop System Tests
1
Conducted in Accordance with ASTM E814
This standard is issued under the fixed designation E2750; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
Metallic pipe, tubing or conduit 6.7
Insulated pipe, tubing or conduit 6.8
1.1 This guide covers the extension of results obtained from
Non-metallic pipe, tubing or conduit 6.9 and 6.10
fire tests performed in accordance with Test Method E814 to Flexible metal conduit 6.11.1.4 and 6.11.1.5
Cables 6.11
applications that have not been tested. Test Method E814
Cable tray 6.12
evaluates the duration for which test specimens will contain a
Bus duct 6.13
fire, retain their integrity, or both during a predetermined fire Non-insulated duct 6.14
Insulated duct 6.14.2
test exposure. Firestops are intended for use in fire-resistive
Non-structural or service support member 6.15
walls and floors that are evaluated in conformance with Test
Mixed penetrations 6.16
Method E119.
1.8 Assemblies can be one of the following; concrete floors
NOTE 1—Data obtained from firestops tested in accordance with Test
or walls, masonry walls, gypsum walls, wood floor/ceiling
Methods E119 with positive pressure can also be used.
assemblies, concrete floor/ceiling assemblies, chase wall in
1.2 This guide is based on principles involving the exten-
floor/ceiling assemblies and fire-rated insulated walls.
sionoftestdatausingsimpleconsiderations.Theacceptanceof
Concrete floors or walls 6.1
these principles and their application is based substantially on
Masonry walls 6.1
an analogous worst-case proposition.
Gypsum board wall assemblies 6.2
Wood floor/ceiling assemblies 6.3
1.3 These principles are only applicable to temperature
Floor/ceiling assembly with concrete floor 6.4
Chase wall intersecting a floor/ceiling assembly 6.5
conditions represented by the standard time-temperature curve
Fire-resistance insulated walls 6.6
described in Test Method E814, for systems falling within the
scope of Test Method E814. This test method is a fire-test- 1.9 The extension of data using numerical calculations
response standard.
based on empirical data or theoretical models is not covered in
this guide.
1.4 The types of building constructions which are part of
this guide are as follows: floors, walls, partitions, floor/ceiling
1.10 This guide does not cover the substitution of one
and roof/ceiling assemblies.
proprietary material for another proprietary material, or mate-
rials for which fire-test data are not presently available.
1.5 This guide applies to:
1.5.1 a single penetrating item, or
1.11 This guide is used to predict or provide a quantitative
1.5.2 multiple penetrating items.
measureofthefirehazardfromaspecifiedsetoffireconditions
1.6 This guide does not apply to joints systems tested to involving specific materials, products, or assemblies. This
assessment does not necessarily predict the hazard of actual
E119, E1966 and E2307.
fires which involve conditions other than those assumed in the
1.7 Penetrating items can be one of the following: metallic
analysis.
pipe, non-metallic pipe, metallic tubing, non-metallic tubing,
metallic conduit, non-metallic conduit, flexible metal conduit,
1.12 This guide is used to measure and describe the re-
cables, cable trays, bus ducts, insulated pipes, insulated tubing, sponse of materials, products, or assemblies to heat and flame
insulated conduit, insulated and non-insulated ducts, and struc-
under controlled conditions, but does not by itself incorporate
tural members. all factors required for fire hazard or fire risk assessment of the
materials, products or assemblies under actual fire conditions.
1.13 The values stated in SI units are to be regarded as
1
This standard guide is under the jurisdiction ofASTM Committee E05 on Fire
standard. No other units of measurement are included in this
Standards and is the direct responsibility of Subcommittee E05.11 on Fire
Resistance. standard.
Current edition approved Nov. 1, 2017. Published December 2017. Originally
ɛ1
1.14 This standard does not purport to address all of the
approved in 2011. Last previous edition approved in 2013 as E2750-13 . DOI:
10.1520/E2750-17. safety concerns, if any, associated with its use. It is the
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2750 − 17
responsibility of the user of this standard to establish appro- 4.5 The extension of data is valid
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: E2750 − 13 E2750 − 17 An American National Standard
Standard Guide for
Extension of Data from Penetration Firestop System Tests
1
Conducted in Accordance with ASTM E814
This standard is issued under the fixed designation E2750; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
ε NOTE—The title of this guide was corrected editorially in February 2013.
1. Scope
1.1 This guide covers the extension of results obtained from fire tests performed in accordance with Test Method E814 to
applications that have not been tested. Test Method E814 evaluates the duration for which test specimens will contain a fire, retain
their integrity, or both during a predetermined fire test exposure. Firestops are intended for use in fire-resistive walls and floors that
are evaluated in conformance with Test Method E119.
NOTE 1—Data obtained from firestops tested in accordance with Test Methods E119 with positive pressure can also be used.
1.2 This guide is based on principles involving the extension of test data using simple considerations. The acceptance of these
principles and their application is based substantially on an analogous worst-case proposition.
1.3 These principles are only applicable to temperature conditions represented by the standard time-temperature curve described
in Test Method E814, for systems falling within the scope of Test Method E814. This test method is a fire-test-response standard.
1.4 The types of building constructions which are part of this guide are as follows: floors, walls, partitions, floor/ceiling and
roof/ceiling assemblies.
1.5 This guide applies to:
1.5.1 a single penetrating item, or
1.5.2 multiple penetrating items.
1.6 This guide does not apply to joints systems tested to E119, E1966 and E2307.
1.7 Penetrating items can be one of the following: metallic pipe, non-metallic pipe, metallic tubing, non-metallic tubing,
metallic conduit, non-metallic conduit, flexible metal conduit, cables, cable trays, bus ducts, insulated pipes, insulated tubing,
insulated conduit, insulated and non-insulated ducts, and structural members.
Metallic pipe, tubing or conduit 6.7
Insulated pipe, tubing or conduit 6.8
Non-metallic pipe, tubing or conduit 6.9 and 6.10
Flexible metal conduit 6.11.1.4 and 6.11.1.5
Cables 6.11
Cable tray 6.12
Bus duct 6.13
Non-insulated duct 6.14
Insulated duct 6.14.2
Non-structural or service support member 6.15
Mixed penetrations 6.16
1.8 Assemblies can be one of the following; concrete floors or walls, masonry walls, gypsum walls, wood floor/ceiling
assemblies, concrete floor/ceiling assemblies, chase wall in floor/ceiling assemblies and fire-rated insulated walls.
Concrete floors or walls 6.1
Masonry walls 6.1
Gypsum board wall assemblies 6.2
Wood floor/ceiling assemblies 6.3
Floor/ceiling assembly with concrete floor 6.4
Chase wall intersecting a floor/ceiling assembly 6.5
Fire-resistance insulated walls 6.6
1
This standard guide is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.
Current edition approved Jan. 1, 2013Nov. 1, 2017. Published February 2013December 2017. Originally approved in 2011. Last previous edition approved in 20112013
ɛ1
as E2750-11.-13 . DOI: 10.1520/E2750-13E01.10.1520/E2750-17.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2750 − 17
1.9 The extension of data using numerical calculations based on empirical data or theoretical models is not covered in this guide.
1.10 This guide does not cover the substitution of one proprietary material for another proprietary material, or materials for
which fire-test data are not presently available.
1.11 This guide is used to predict or provide a quantitative measure of the fire hazard from a specified set of fire conditions
involving specific materials, products, or assemblies. This assessment does not necessarily predict the hazard of actual fires which
involve conditions other than those assumed in the analysis.
1.12 This guide is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire hazard or
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.