ASTM E119-12a
(Test Method)Standard Test Methods for Fire Tests of Building Construction and Materials
Standard Test Methods for Fire Tests of Building Construction and Materials
SIGNIFICANCE AND USE
These test methods are intended to evaluate the duration for which the types of building elements noted in 1.1 contain a fire, retain their structural integrity, or exhibit both properties during a predetermined test exposure.
The test exposes a test specimen to a standard fire controlled to achieve specified temperatures throughout a specified time period. When required, the fire exposure is followed by the application of a specified standard fire hose stream applied in accordance with Practice E2226. The test provides a relative measure of the fire-test-response of comparable building elements under these fire exposure conditions. The exposure is not representative of all fire conditions because conditions vary with changes in the amount, nature and distribution of fire loading, ventilation, compartment size and configuration, and heat sink characteristics of the compartment. Variation from the test conditions or test specimen construction, such as size, materials, method of assembly, also affects the fire-test-response. For these reasons, evaluation of the variation is required for application to construction in the field.
The test standard provides for the following:
For walls, partitions, and floor or roof test specimens:
Measurement of the transmission of heat.
Measurement of the transmission of hot gases through the test specimen.
For loadbearing elements, measurement of the load carrying ability of the test specimen during the test exposure.
For individual loadbearing members such as beams and columns:
Measurement of the load carrying ability under the test exposure with consideration for the end support conditions (that is, restrained or not restrained).
The test standard does not provide the following:
Information as to performance of test specimens constructed with components or lengths other than those tested.
Evaluation of the degree by which the test specimen contributes to the fire hazard by generation of smoke, toxic gases, or o...
SCOPE
1.1 The test methods described in this fire-test-response standard are applicable to assemblies of masonry units and to composite assemblies of structural materials for buildings, including loadbearing and other walls and partitions, columns, girders, beams, slabs, and composite slab and beam assemblies for floors and roofs. They are also applicable to other assemblies and structural units that constitute permanent integral parts of a finished building.
1.2 It is the intent that classifications shall register comparative performance to specific fire-test conditions during the period of exposure and shall not be construed as having determined suitability under other conditions or for use after fire exposure.
1.3 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions.
1.4 These test methods prescribe a standard fire exposure for comparing the test results of building construction assemblies. The results of these tests are one factor in assessing predicted fire performance of building construction and assemblies. Application of these test results to predict the performance of actual building construction requires the evaluation of test conditions.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.7 The text of th...
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E119 − 12a AnAmerican National Standard
Standard Test Methods for
1
Fire Tests of Building Construction and Materials
This standard is issued under the fixed designation E119; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
INTRODUCTION
The performance of walls, columns, floors, and other building members under fire-exposure
conditions is an item of major importance in securing constructions that are safe, and that are not a
menace to neighboring structures or to the public. Recognition of this is registered in the codes of
many authorities, municipal and other. It is important to secure balance of the many units in a single
building, and of buildings of like character and use in a community; and also to promote uniformity
in requirements of various authorities throughout the country. To do this it is necessary that the
fire-resistivepropertiesofmaterialsandassembliesbemeasuredandspecifiedaccordingtoacommon
standard expressed in terms that are applicable alike to a wide variety of materials, situations, and
conditions of exposure.
Such a standard is found in the test methods that follow.They prescribe a standard exposing fire of
controlledextentandseverity.Performanceisdefinedastheperiodofresistancetostandardexposure
elapsing before the first critical point in behavior is observed. Results are reported in units in which
field exposures can be judged and expressed.
The test methods may be cited as the “Standard FireTests,” and the performance or exposure shall
1
be expressed as “2-h,” “6-h,” “ ⁄2-h,” etc.
When a factor of safety exceeding that inherent in the test conditions is desired, a proportional
increase should be made in the specified time-classification period.
1. Scope period of exposure and shall not be construed as having
determined suitability under other conditions or for use after
1.1 The test methods described in this fire-test-response
fire exposure.
standard are applicable to assemblies of masonry units and to
1.3 This standard is used to measure and describe the
composite assemblies of structural materials for buildings,
response of materials, products, or assemblies to heat and
including loadbearing and other walls and partitions, columns,
flame under controlled conditions, but does not by itself
girders,beams,slabs,andcompositeslabandbeamassemblies
incorporate all factors required for fire hazard or fire risk
for floors and roofs. They are also applicable to other assem-
assessment of the materials, products or assemblies under
blies and structural units that constitute permanent integral
actual fire conditions.
parts of a finished building.
1.4 These test methods prescribe a standard fire exposure
1.2 Itistheintentthatclassificationsshallregistercompara-
for comparing the test results of building construction assem-
tive performance to specific fire-test conditions during the
blies. The results of these tests are one factor in assessing
predictedfireperformanceofbuildingconstructionandassem-
blies. Application of these test results to predict the perfor-
1
ThesetestmethodsareunderthejurisdictionofASTMCommitteeE05onFire
mance of actual building construction requires the evaluation
Standards and are the direct responsibility of Subcommittee E05.11 on Fire
of test conditions.
Resistance.
Current edition approved July 15, 2012. Published September 2012. Originally
1.5 Thevaluesstatedininch-poundunitsaretoberegarded
approved in 1917. Last previous edition approved in 2012 as E119–12. DOI:
as standard. The values given in parentheses are mathematical
10.1520/E0119-12A.
conversions to SI units that are provided for information only
These test methods, of which the present standard represents a revision, were
preparedbySectionalCommitteeonFireTestsofMaterialsandConstruction,under and are not considered standard.
thejointsponsorshipoftheNationalBureauofStandards,theANSIFireProtection
1.6 This standard does not purport to address all of the
Group, and ASTM, functioning under the procedure of the American National
Standards Institute. safety concerns, if any, associated with its use. It is the
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
E119 − 12a
responsibility of the user of this standard to establish appro- 4.3.1.2 Measurement of the transmission of hot gases
priate safety and health practices and determine the applica- through the test specimen.
bility of regulatory limitations prior
...
This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
An American National Standard
Designation:E119–12 Designation:E119–12a
Standard Test Methods for
1
Fire Tests of Building Construction and Materials
This standard is issued under the fixed designation E119; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
INTRODUCTION
The performance of walls, columns, floors, and other building members under fire-exposure
conditions is an item of major importance in securing constructions that are safe, and that are not a
menace to neighboring structures or to the public. Recognition of this is registered in the codes of
many authorities, municipal and other. It is important to secure balance of the many units in a single
building, and of buildings of like character and use in a community; and also to promote uniformity
in requirements of various authorities throughout the country. To do this it is necessary that the
fire-resistivepropertiesofmaterialsandassembliesbemeasuredandspecifiedaccordingtoacommon
standard expressed in terms that are applicable alike to a wide variety of materials, situations, and
conditions of exposure.
Such a standard is found in the test methods that follow. They prescribe a standard exposing fire of
controlled extent and severity. Performance is defined as the period of resistance to standard exposure
elapsing before the first critical point in behavior is observed. Results are reported in units in which
field exposures can be judged and expressed.
The test methods may be cited as the “Standard Fire Tests,” and the performance or exposure shall
1
be expressed as “2-h,” “6-h,” “ ⁄2-h,” etc.
When a factor of safety exceeding that inherent in the test conditions is desired, a proportional
increase should be made in the specified time-classification period.
1. Scope
1.1 Thetestmethodsdescribedinthisfire-test-responsestandardareapplicabletoassembliesofmasonryunitsandtocomposite
assemblies of structural materials for buildings, including loadbearing and other walls and partitions, columns, girders, beams,
slabs, and composite slab and beam assemblies for floors and roofs. They are also applicable to other assemblies and structural
units that constitute permanent integral parts of a finished building.
1.2 It is the intent that classifications shall register comparative performance to specific fire-test conditions during the period
of exposure and shall not be construed as having determined suitability under other conditions or for use after fire exposure.
1.3 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,
products or assemblies under actual fire conditions.
1.4 Thesetestmethodsprescribeastandardfireexposureforcomparingthetestresultsofbuildingconstructionassemblies.The
results of these tests are one factor in assessing predicted fire performance of building construction and assemblies. Application
of these test results to predict the performance of actual building construction requires the evaluation of test conditions.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1
These test methods are under the jurisdiction ofASTM Committee E05 on Fire Standards and are the direct responsibility of Subcommittee E05.11 on Fire Resistance.
Current edition approved Jan.July 15, 2012. Published JanuarySeptember 2012. Originally approved in 1917. Last previous edition approved in 20112012 as
E119–11a.E119 – 12. DOI: 10.1520/E0119-12A.
These test methods, of which the present standard represents a revision, were prepared by Sectional Committee on Fire Tests of Materials and Construction, under the
joint sponsorship of the National Bureau of Standards, the ANSI Fire Protection
...