Fixed firefighting systems - Components for sprinkler and water spray systems - Part 12: Pumps

This part of EN 12259 specifies requirements for construction and performance of single and multistage rotodynamic (centrifugal) pumps used in automatic sprinklers systems conforming to EN 12845 Clause 10 Pumps and TS 14816 Water spray systems

Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 12: Sprinklerpumpen

Installations fixes de lutte contre l'incendie - Composants des systèmes d'extinction du type sprinkleur et à pulvérisation d'eau - Partie 12 : Pompe pour sprinkleurs

Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s pršečo vodo - 12. del: Črpalke

General Information

Status
Not Published
Publication Date
02-Dec-2018
Withdrawal Date
02-Jun-2019
Current Stage
4098 - Decision to abandon - Enquiry
Completion Date
28-Jan-2019

Buy Standard

Draft
prEN 12259-12:2017
English language
30 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-julij-2017
9JUDMHQHQDSUDYH]DJDãHQMH6HVWDYQLGHOLVSULQNOHUVNLKVLVWHPRYLQVLVWHPRYV
SUãHþRYRGRGHOýUSDONH
Fixed firefighting systems - Components for sprinkler and water spray systems - Part 12:
Pumps
Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 12:
Sprinklerpumpen
Installations fixes de lutte contre l'incendie - Composants des systèmes d'extinction du
type sprinkleur et à pulvérisation d'eau - Partie 12 : Pompe pour sprinkleurs
Ta slovenski standard je istoveten z: prEN 12259-12
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

DRAFT
EUROPEAN STANDARD
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2017
ICS 13.220.20
English Version
Fixed firefighting systems - Components for sprinkler and
water spray systems - Part 12: Pumps
Installations fixes de lutte contre l'incendie - Ortsfeste Löschanlagen - Bauteile für Sprinkler- und
Composants des systèmes d'extinction du type Sprühwasseranlagen - Teil 12: Sprinklerpumpen
sprinkleur et à pulvérisation d'eau - Partie 12 : Pompe
pour sprinkleurs
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 191.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 12259-12:2017 E
worldwide for CEN national Members.

Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 5
3 Terms, definitions and symbols . 5
4 Product characteristics . 6
4.1 Operational Reliability and Performance parameters under fire conditions . 6
4.1.1 Working pressure . 6
4.1.2 Range of operation. 6
4.2 Durability of Operational Reliability and Performance parameters under fire
conditions . 7
4.2.1 Resistance to deterioration . 7
4.3 Connections . 7
5 Testing, assessment and sampling methods . 7
5.1 Operational Reliability and Performance parameters under fire conditions . 7
5.1.1 Working pressure . 7
5.1.2 Range of operation. 8
6 Evaluation of conformity . 9
6.1 General . 9
6.2 Type Testing . 9
6.2.1 General . 9
6.2.2 Test samples, testing and compliance criteria . 10
6.2.3 Test reports . 10
6.2.4 Shared other party results . 10
6.3 Factory production control (FPC) . 11
6.3.1 General . 11
6.3.2 Requirements . 11
6.3.3 Product specific requirements . 13
6.3.4 Initial inspection of factory and of FPC . 14
6.3.5 Continuous surveillance of FPC . 14
6.3.6 Procedure for modifications . 15
6.3.7 Pre-production products (e.g. prototypes) . 15
7 Marking, labelling and packaging . 16
7.1 General . 16
7.2 Marking . 16
Annex A (informative) Specimen of manufacturer’s name plate . 18
Annex B (normative) Pump characteristic curve sheets . 19
Annex C (informative) Documentation . 22
Annex ZA  (informative) Clauses of this European Standard addressing the provisions of
the EU Construction Products Regulation . 23
ZA.1 Scope and relevant characteristics . 23
ZA.2 Procedure for AVCP of Pumps . 24
ZA.2.1 System(s) of AVCP . 24
ZA.2.2 Declaration of Performance (DoP) . 25
ZA.3 CE marking and labelling . 28
Bibliography . 30

European foreword
This document (prEN 12259-12:2017) has been prepared by Technical Committee CEN/TC 191 “Fixed
fire fighting systems”, the secretariat of which is held by BSI.
This document is currently submitted to the Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports basic work requirements of Regulation (EU) 305/2011
as amended.
For relationship with EU Regulations see informative Annex ZA, which is an integral part of this
document.
1 Scope
This part of EN 12259 specifies requirements, test methods, evaluation of conformity and marking of
single stage and multi stage pumps with mechanical seal or soft packing intended to be used in
automatic sprinkler and water spray systems according to EN 12845 and CEN/TS 14816.
This European Standard is applicable for pumps made of the following materials:
• Body: cast iron, cast steel, stainless steel, bronze or aluminium bronze.
• Pump shafts: stainless steel.
• Protective sleeves for shafts, metal parts of mechanical seals, impellers, impeller fastenings
(impeller nuts, locking plates or washers and adjusting springs) and wear rings, including their
counterparts: bronze or stainless steel.
This European Standard is applicable for:
• end suction pumps;
• axial horizontal split case pumps;
• ring section pumps;
• inline pumps (Vertical shaft pump with inlet and outlet in line);
• vertical turbine pumps;
• submersible motor pumps.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN ISO 9906:2012, Rotodynamic pumps. Hydraulic performance acceptance tests. Grades 1 and 2
EN 12162:2001+A1:2009, Liquid pumps. Safety requirements. Procedures for hydrostatic testing
EN 12723, Liquid pumps. General terms for pumps and installations. Definitions, quantities, letter symbols
and units
EN 12845:2015, Fixed firefighting systems - Automatic sprinkler systems - Design, installation and
maintenance
3 Terms, definitions and symbols
For the purposes of this document, the terms, definitions and symbols given in EN 12723 and EN 12845
apply.
4 Product characteristics
4.1 Operational Reliability and Performance parameters under fire conditions
4.1.1 Working pressure
4.1.1.1 The pump shall meet the requirements of 4.1.1.2 to 4.1.1.4.
The performance shall be expressed as the working pressure in bar.
4.1.1.2 The maximum allowable casing working pressure shall be specified by the manufacturer and
shall be at least equal to the closed valve pressure at maximum rotational speed and maximum impeller
diameter plus maximum inlet pressure.
4.1.1.3 The assembled pump shall withstand internal hydrostatic pressure and meet the requirements
of EN 12162:2001+A1:2009 when tested in accordance with 5.1.1.1.
4.1.1.4 The pump casing shall withstand the hydrostatic pressure test without rupture in accordance
with EN 12162:2001+A1:2009 when tested in accordance with 5.1.1.2.
4.1.2 Range of operation
4.1.2.1 The pump shall meet the requirements of 4.1.2.2 to 4.1.2.7
The performance shall be expressed as description of the range of operation as follows:
• rated flow in l/min or m /h;
• rated speed in 1/min;
• total differential head at rated flow in m;
• pump characteristic curve sheet in accordance with Annex B.
4.1.2.2 Detailed shaft stress calculations shall be provided which show that the shaft is suitable for the
maximum impeller diameter at 105 % the maximum rated speed. Detailed shaft stress calculations shall
use a density of water of 1035 kg/m at 20 °C.
4.1.2.3 The rated speed shall be specified by the pump manufacturer.
The maximum allowable continuous speed, specified by the pump manufacturer shall be at least 105 %
of the rated speed.
4.1.2.4 When tested in accordance with 5.1.2.1 taking into account 5.1.2.3, pumps shall have a stable
characteristic curve H(Q) within the measurement uncertainty range as specified in EN ISO 9906:2012
Grade 2.
4.1.2.5 When tested in acc
...