EN 1366-9:2024
(Main)Fire resistance tests for service installations - Part 9: Single compartment smoke extraction ducts
Fire resistance tests for service installations - Part 9: Single compartment smoke extraction ducts
This part of EN 1366 specifies a test method for determining the fire resistance of smoke extraction ducts that are used for single compartment applications only. In such applications, the smoke extraction system is only intended to function up to flashover (typically 600 °C).
This method of test is only suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
It is applicable only to four sided and circular ducts. One-, two- and three-sided ducts are not covered. This document is applicable only for the standard sizes or smaller as described.
This test method of part 9 is applicable only to smoke extraction ducts that do not pass into other fire compartments. For smoke extraction ducts that pass into other compartments, the method of test described in EN 1366-8 is used.
The smoke extraction duct is part of the smoke extraction system which also includes smoke control dampers and smoke extract fans.
Feuerwiderstandsprüfungen für Installationen - Teil 9: Entrauchungsleitungen für einen Einzelabschnitt
Dieser Teil von EN 1366 legt ein Prüfverfahren zur Ermittlung der Feuerwiderstandsfähigkeit von Entrauchungsleitungen fest, die nur für die Anwendung in einem Einzelabschnitt eingesetzt werden. Bei solchen Anwendungen ist beabsichtigt, dass die Rauchabzugsanlage nur bis zum Flashover (typischerweise 600 °C) arbeitet.
Dieses Prüfverfahren ist nur für aus nichtbrennbaren Baustoffen (Klasse A1 und A2 s1, d0 nach EN 13501 1) konstruierte Leitungen geeignet.
Es ist nur für vierseitige und kreisförmige Leitungen geeignet. Ein-, zwei- und dreiseitige Leitungen werden nicht abgedeckt. Dieses Dokument gilt nur für Standardmaße oder kleinere Größen, wie beschrieben.
Dieses Prüfverfahren von Teil 9 gilt nur für Entrauchungsleitungen, die nicht in weitere Brandabschnitte führen. Für Entrauchungsleitungen, die in weitere Brandabschnitte hineinführen, ist das in EN 1366 8 beschriebene Prüfverfahren anzuwenden.
Die Entrauchungsleitung ist Bestandteil der Rauchabzugsanlage, welche ebenfalls Entrauchungsklappen und Rauchabzüge umfasst.
Essais de résistance au feu des installations techniques - Partie 9 : Conduits d'extraction de fumées relatifs à un seul compartiment
La présente partie de l’EN 1366 spécifie une méthode d’essai pour déterminer la résistance au feu des conduits d’extraction de fumées qui sont utilisés pour des applications relatives à un seul compartiment. Dans de telles applications, le système d’extraction de fumées vise à fonctionner seulement jusqu’à l’embrasement généralisé (600 °C en général).
Cette méthode d’essai n’est valable que pour des conduits fabriqués à partir de matériaux non combustibles (classe A1 et A2-s1, d0 conformément à l’EN 13501-1).
Les essais ne s’appliquent qu’aux conduits à quatre faces et aux conduits circulaires. Les conduits à une seule face, à deux ou trois faces ne sont pas couverts. Le présent document ne s’applique qu’aux tailles standards ou inférieures conformément à la description.
Cette méthode d’essai de la partie 9 est applicable seulement aux conduits d’extraction de fumées qui ne passent pas dans d’autres compartiments feu. Pour les conduits d’extraction de fumées qui passent dans d’autres compartiments, la méthode d’essai décrite dans l’EN 1366-8 est utilisée.
Le conduit d’extraction de fumées fait partie intégrante du système d’extraction de fumées qui comprend également des volets de désenfumage et des ventilateurs de désenfumage.
Preskusi požarne odpornosti servisnih inštalacij - 9. del: Kanali za odvod dima iz enega požarnega sektorja
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-december-2024
Nadomešča:
SIST EN 1366-9:2008
Preskusi požarne odpornosti servisnih inštalacij - 9. del: Kanali za odvod dima iz
enega požarnega sektorja
Fire resistance tests for service installations - Part 9: Single compartment smoke
extraction ducts
Feuerwiderstandsprüfungen für Installationen - Teil 9: Entrauchungsleitungen für einen
Einzelabschnitt
Essais de résistance au feu des installations techniques - Partie 9 : Conduits d'extraction
de fumées relatifs à un seul compartiment
Ta slovenski standard je istoveten z: EN 1366-9:2024
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 1366-9
EUROPEAN STANDARD
NORME EUROPÉENNE
October 2024
EUROPÄISCHE NORM
ICS 13.220.50; 91.140.30 Supersedes EN 1366-9:2008
English Version
Fire resistance tests for service installations - Part 9:
Single compartment smoke extraction ducts
Essais de résistance au feu des installations techniques Feuerwiderstandsprüfungen für Installationen - Teil 9:
- Partie 9 : Conduits d'extraction de fumées relatifs à un Entrauchungsleitungen für einen Einzelabschnitt
seul compartiment
This European Standard was approved by CEN on 2 September 2024.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1366-9:2024 E
worldwide for CEN national Members.
Contents Page
European foreword . 5
Introduction . 7
1 Scope . 8
2 Normative references . 8
3 Terms and definitions . 9
4 Test equipment . 10
4.1 General. 10
4.2 Furnace . 10
4.3 Perforated plate . 10
4.4 Air velocity measuring station . 11
4.5 Ambient temperature leakage measuring device . 11
4.6 Pressure sensors for differential pressure control . 11
4.7 Welded connecting tube . 11
4.8 Extract fan connecting duct . 11
4.9 Extraction fan . 12
4.10 Thermocouples . 12
4.11 Oxygen measuring equipment . 12
4.12 Oxygen measurement probes . 12
4.13 Restraint equipment . 12
4.14 Deflection measurements . 12
5 Test conditions . 12
5.1 Differential pressure conditions . 12
5.2 Heating and pressure conditions . 12
6 Test specimen . 13
6.1 Size . 13
6.1.1 Length. 13
6.1.2 Cross-section . 13
6.2 Number . 13
6.3 Design . 13
7 Installation of test specimen . 14
7.1 General. 14
7.2 Supporting construction . 14
7.3 Duct arrangement . 14
7.4 Restraint of ducts . 14
7.4.1 Inside the furnace . 14
7.4.2 Outside the furnace . 14
7.5 Perforated plate . 15
8 Conditioning . 15
8.1 General. 15
8.2 Water based sealing materials . 15
9 Application of instrumentation . 15
9.1 Thermocouples . 15
9.1.1 Furnace thermocouples (plate thermometers) . 15
9.1.2 Gas temperature within flow nozzles . 15
9.2 Pressure . 15
9.2.1 Furnace pressure . 15
9.2.2 Differential under-pressure in duct . 15
9.3 Oxygen measurements . 16
9.4 Deflection measurement for determination of reduction of internal cross-sectional area
............................................................................................................................................................................. 16
10 Test procedure . 17
10.1 Pre-test adjustment . 17
10.1.1 Oxygen-measuring instrument . 17
10.1.2 Perforated plate . 17
10.2 Leakage measurement at ambient temperature. 17
10.3 Pre-fire test procedures . 18
10.4 Fire test. 18
10.5 Termination of test . 19
11 Performance criteria . 20
11.1 General requirements . 20
11.2 Criteria at ambient temperature . 20
11.2.1 Ambient leakage . 20
11.2.2 Maintenance of cross-section under ambient conditions outside the furnace . 20
11.3 Criteria under fire conditions . 20
11.3.1 General . 20
11.3.2 Integrity . 20
11.3.3 Smoke leakage . 21
12 Test report . 21
13 Direct field of application of test results . 21
13.1 General . 21
13.2 Duct sizes . 22
13.3 Suspension device . 22
13.4 Pressure difference . 22
13.5 Vertical
...