Live working - Voltage detectors - Part 1: Capacitive type to be used for voltages exceeding 1 kV a.c.

Arbeiten unter Spannung - Spannungsprüfer - Teil 1: Kapazitive Ausführung für Wechselspannungen über 1 kV

Travaux sous tension - Détecteurs de tension - Partie 1: Type capacitif pour usage sur des tensions alternatives de plus de 1 kV

Delo pod napetostjo - Napetostni detektorji - 1. del: Kapacitivni tip za uporabo pri izmeničnih napetostih nad 1 kV (IEC 61243-1:2003/A1:2009)

Amandma A1:2010 je dodatek k standardu SIST EN 61243-1:2007
Ta del IEC 61243 velja za prenosne napetostne detektorje z vgrajenim napajanjem ali brez, ki se uporabljajo v električnih sistemih pri napetostih med 1 kV in 765 kV izmeničnega toka in frekvenci 50 Hz in/ali 60 Hz. Ta del velja le za napetostne detektorje, ki se uporabljajo v stiku s preskušanim delom, kot popolna naprava z vključenimi izolacijskimi elementi ali kot ločena naprava, ki se prilega izolacijski palici, ki je kot ločeno orodje ta standard ne zajema (glej 4.4.1 za splošno zasnovo). Ta del standarda ne zajema drugih vrst napetostnih detektorjev. Za njihovo uporabo v primeru tovarniško sestavljenih stikalnih naprav in nadzemnih sistemov elektrificiranih železniških prog velja nekaj omejitev (glej Dodatek B, navodila za uporabo). OPOMBA: Vse napetosti, opredeljene v tem standardu, se nanašajo na vrednosti medfaznih napetosti trifaznih sistemov, razen kadar je določeno drugače. V drugih sistemih se morajo za določanje delovne napetosti uporabljati medfazne ali ozemljitvene napetosti.

General Information

Status
Withdrawn
Publication Date
25-Feb-2010
Withdrawal Date
30-Nov-2012
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
26-May-2024
Completion Date
26-May-2024

Relations

Buy Standard

Amendment
EN 61243-1:2007/A1:2010
English language
20 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-junij-2010
'HORSRGQDSHWRVWMR1DSHWRVWQLGHWHNWRUMLGHO.DSDFLWLYQLWLS]DXSRUDERSUL
L]PHQLþQLKQDSHWRVWLKQDGN9 ,(&$
Live working - Voltage detectors - Part 1: Capacitive type to be used for voltages
exceeding 1 kV a.c. (IEC 61243-1:2003/A1:2009)
Arbeiten unter Spannung - Spannungsprüfer - Teil 1: Kapazitive Ausführung für
Wechselspannungen über 1 kV (IEC 61243-1:2003/A1:2009)
Travaux sous tension - Détecteurs de tension - Partie 1: Type capacitif pour usage sur
des tensions alternatives de plus de 1 kV (CEI 61243-1:2003/A1:2009)
Ta slovenski standard je istoveten z: EN 61243-1:2005/A1:2010
ICS:
13.260 9DUVWYRSUHGHOHNWULþQLP Protection against electric
XGDURP'HORSRGQDSHWRVWMR shock. Live working
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 61243-1/A1
NORME EUROPÉENNE
February 2010
EUROPÄISCHE NORM
ICS 29.240.99
English version
Live working -
Voltage detectors -
Part 1: Capacitive type to be used for voltages exceeding 1 kV a.c.
(IEC 61243-1:2003/A1:2009)
Travaux sous tension -  Arbeiten unter Spannung -
Détecteurs de tension - Spannungsprüfer -
Partie 1: Type capacitif pour usage Teil 1: Kapazitive Ausführung
sur des tensions alternatives für Wechselspannungen über 1 kV
de plus de 1 kV (IEC 61243-1:2003/A1:2009)
(CEI 61243-1:2003/A1:2009)
This amendment A1 modifies the European Standard EN 61243-1:2005; it was approved by CENELEC on
2009-11-17. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: Avenue Marnix 17, B - 1000 Brussels

© 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61243-1:2005/A1:2010 E

Foreword
The text of document 78/751/CDV, future amendment 1 to IEC 61243-1:2003, prepared by IEC TC 78,
Live working, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as
amendment A1 to EN 61243-1:2005 on 2009-11-17.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.
The following dates were fixed:
– latest date by which the amendment has to be
implemented at national level by publication of
an identical national standard or by endorsement (dop) 2010-09-01
– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2012-12-01
As a consequence of endorsing amendment 1:2009 to IEC 61243-1:2003, the common modifications in
EN 61243-1:2005 are now covered by the IEC text.
__________
Endorsement notice
The text of amendment 1:2009 to the International Standard IEC 61243-1:2003 was approved by
CENELEC as an amendment to the European Standard without any modification.
__________
- 3 - EN 61243-1:2005/A1:2010
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
NOTE Where an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year
Replace the existing reference to IEC 60071-1:1993 by the following:
IEC 60071-1 2006 Insulation co-ordination EN 60071-1 2006
Part 1: Definitions, principles and rules
Add:
IEC 61318 2007 Live working - Conformity assessment EN 61318 2008
applicable to tools, devices and
equipment
IEC 61243-1 ®
Edition 2.0 2009-04
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 1
AMENDEMENT 1
Live working – Voltage detectors –
Part 1: Capacitive type to be used for voltages exceeding 1 kV a.c.

Travaux sous tension – Détecteurs de tension –
Partie 1: Type capacitif pour usage sur des tensions alternatives de plus de 1 kV

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
Q
CODE PRIX
ICS 29.240.99 ISBN 2-8318-1040-4
– 2 – 61243-1 Amend.1 © IEC:2009
FOREWORD
This amendment has been prepared by IEC technical committee 78: Live working.
The text of this amendment is based on the following documents:
CDV Report on voting
78/751/CDV 78/794/RVC
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the maintenance result date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
_____________
2 Normative references
Replace the existing reference to IEC 60071-1:1993 by the following:
IEC 60071-1:2006, Insulation co-ordination – Part 1: Definitions, principles and rules
Replace the existing reference to IEC 61318:2003 by the following:
IEC 61318:2007, Live working – Conformity assessment applicable to tools, devices and
equipment
3 Terms and definitions
Replace the first sentence by the following:
For the purposes of this document, the terms and definitions given in IEC 61318:2007 and the
following apply.
3.1
voltage detector
Replace the existing definition and note by the following:
device used to provide clear evidence of the presence or the absence of the operating voltage
NOTE For example, voltage detectors can be described as capacitive type or resistive type.
[Definition 11.2.5 of IEC 60743, modified, and IEV 651-10-04, modified]

61243-1 Amend.1 © IEC:2009 – 3 –
3.4
family of voltage detectors
Replace the existing definition by the following:
for testing purposes, a group of voltage detectors, delimited by a minimum and a maximum
rated voltage, that are identical in design (including dimensions) and only differ by their
nominal voltages or nominal voltage ranges
3.10
insulating stick
Replace the existing definition by the following:
insulating tool essentially made of an insulating tube and/or rod with end fittings
[Definition 2.5.1 of IEC 60743 and IEV 651-02-01]
NOTE For voltage detection, an insulating stick is intended to be attached to a voltage detector as a separate
device in order to provide the length to reach the installation to be tested and adequate safety distance and
insulation to the user.
3.29
type test
Delete the definition.
3.30
routine test
Delete the definition.
3.31
sampling test
Delete the definition.
3.32
acceptance test
Delete the definition.
4.2 Functional requirements
4.2.1 Clear indication
Replace the existing text by the following:
The voltage detector shall give an unambiguous indication of the presence and/or the
absence of the system operating voltage as a function of the nominal voltage or nominal
voltage range of the voltage detector, and its nominal frequency or nominal frequencies.
Indication may not be reliable in the vicinity of large conductive parts that create equipotential
zones.
When the voltage detector is used in accordance with instructions for use, the presence of an
adjacent live or earthed part shall not affect its indication.
When used in accordance with instructions for use, the voltage detector shall not indicate
"voltage present" for usual values of interference voltages.

– 4 – 61243-1 Amend.1 © IEC:2009
4.2.1.1 Continuous indication
The voltage detector shall give continuous indication when in direct contact with a live part.
4.2.1.2 Threshold voltage
4.2.1.2.1 General
The user shall not have access to the threshold voltage setting.
The indication “voltage present” shall appear if the voltage to earth on the part to be tested is
greater than 45 % of the nominal voltage.
NOTE 1 45 % of the nominal voltage corresponds to 0,78U 3 .
n
The indication "voltage present" shall not appear if the voltage to earth on the part to be
tested is equal to or less than 10 % of the nominal voltage.
NOTE 2 10 % of the nominal voltage corresponds to 0,17U 3 and is the maximum phase to earth induced
n
voltage normally encountered in the field.
To fulfil the above requirements, the threshold voltage U shall satisfy the following
t
relationship:
0,10 U max< U ≤ 0,45 U min
n t n
For voltage detectors with only one nominal voltage, U max. equals U min.

n n
NOTE 3 There is a theoretical limit of 4,5 to the ratio between U max. and U min. to achieve clear indication of

n n
the voltage detector. This value corresponds to the division of 0,45 by 0,1.
NOTE 4 It may happen that the induced voltage level on a specific network is higher than 10 % of the nominal
voltage or of the maximum nominal voltage of the range.
It may also happen that the variations of the nominal voltage network are such that the 0,45 U or 0,45 U max. is
n n
not the lowest possible value.
Moreover, when is it expected that the voltage detector will be used in the vicinity of large conductive parts that
create equipotential zones (see 4.2.1), the customer may specify a low value of the threshold voltage.
In all these cases, manufacturer and customer should reach an agreement to set the appropriate value for the
threshold voltage, while keeping it within the range specified above. The setting of the threshold voltage is further
limited by the requirements for clear indication which shorten the range of possible values, and the relevant tests
(clear indication) have to be passed.
4.2.1.2.2 Particular case of voltage detectors to be used on networks with low values
of interference voltage
In some cases, the customer may wish to take advantage of a network with low values of
interference voltage by reducing the lower limit of the threshold voltage below 0,10 U max.
n
NOTE 1 This particular case could help to deal with the use of the voltage detector in the vicinity of large
conductive parts. In spite of this change of the threshold voltage for a lower value, the theoretical limit of 4,5 for
the ratio between U max. and U min. still remains valid, and the relevant tests (clear indication) have to be

n n
passed.
In such case, the voltage detector shall have a special marking and a warning shall be
included in the instructions for use to inform the users of the modification brought to the
threshold voltage.
NOTE 2 The special marking should be the result of an agreement between the manufacturer and the client.

61243-1 Amend.1 © IEC:2009 – 5 –
4.2.3 Temperature and humidity dependence of the indication
Replace the existing fourth paragraph by the following:
In these cases, the threshold voltage shall satisfy 4.2.1.2.

4.4.2 Dimensions, construction
Replace the existing Table 2 and the notes by the following:
Table 2 – Minimum length of the insulating element (L )
i
of a voltage detector as a complete device
U L
r i
kV
mm
1 < U ≤ 7,2 320
r
7,2 < U ≤ 12 360
r
12 < U ≤ 17,5
r
17,5 < U ≤ 24
r
24 < U ≤ 36 520
r
36 < U ≤ 72,5 830
r
72,5 < U ≤ 123 1 300
r
1 700
123 < U ≤ 170
r
2 300
170 < U ≤ 245
r
3 600
245 < U ≤ 420
r
420 < U ≤ 525 4 300
r
525 < U ≤ 765 6 600
r
NOTE 1 The nominal voltage U is used when the parameters to be specified are related to the installation
n
dimensioning or to the functional performance of the voltage detector, while the rated voltage U is used when
r
insulation performance of the voltage detector is concerned.
NOTE 2 The L values of Table 2 correspond to the minimum distance in air (obtained from Tables 1 and 2 of
i
IEC 61936-1) plus an additional safety distance.
NOTE 3 The L values of Table 2 can be used as a guidance to determine the length of the insulating stick used
i
with a voltage detector as a separate device. However, the length of the insulating stick for live working can be
shortened for voltage detectors as a separate device taking into account the minimum approach distances or in
accordance with national or regional regulations.
Replace the second paragraph by the following:
For L equal to or greater than 520 mm, conductive parts not exceeding 200 mm (in total),
i
measured from the limit mark towards the handle, are allowed within the minimum length of
the insulating element if they are completely externally insulated.
4.5 M
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.