Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment

Corrigendum 1 - Compatibilité électromagnétique (CEM) - Partie 6-5: Normes génériques - Immunité pour les équipements utilisés dans les environnements de centrales électriques et de postes

General Information

Status
Published
Publication Date
06-Dec-2017
Drafting Committee
Current Stage
PPUB - Publication issued
Start Date
27-Dec-2017
Completion Date
07-Dec-2017
Ref Project

Relations

Buy Standard

Standard
IEC 61000-6-5:2015/COR1:2017 - Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment Released:12/7/2017
English and French language
1 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


 IEC 2017
INTERNATIONAL ELECTROTECHNICAL COMMISSION
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
IEC 61000-6-5 IEC 61000-6-5
Edition 1.0  2015-08 Édition 1.0  2015-08

Electromagnetic compatibility (EMC) – Compatibilité électromagnétique (CEM) –
Part 6-5: Generic standards Partie 6-5: Normes génériques
– Immunity for equipment used in – Immunité pour les équipements utilisés dans
power station les environnements
and substation environment de centrales électriques et de postes

CORRIGENDUM 1
Corrections to the French version appear after the English text.
Les corrections à la version française sont données après le texte anglais.

Table 5 – Immunity specifications – Power station – Low voltage a.c. input and output
power ports
Replace in test 3.5 for interface type 3:
“0,5 kV
(differential mode,
10 MHz)”
by:
“1 kV
(common mode,
10 MHz)”
Replace in test 3.5 for interface type 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
– 2 – IEC 61000-6-5:2015/COR1:2017
 IEC 2017
Table 6 – Immunity specifications – Power station – Low voltage d.c. input and output
power ports
Replace in test 4.5:
“Ripple on d.c.
power supply”
by:
“Ripple on d.c.
c

power supply
Replace in test 4.6 for interface type 3:
“0,5 kV
(differential mode,
10 MHz)”
by:
“1 kV
(common mode,
10 MHz)”
Replace in test 4.6 for interface type 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
Table 9 – Immunity specifications – Substation – Low voltage a.c. input and output
power ports
Replace in test 3.5 for interface types 2, 3 and 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
 IEC 2017
Table 10 – Immunity specifications – Substation – Low voltage d.c. input and output
power ports
Replace in test 4.5:
“Ripple on d.c.
power supply”
by:
“Ripple on d.c.
c

power supply
Replace in test 4.6 for int
...

Questions, Comments and Discussion