IEC 60309-1:1999/AMD1:2005/COR1:2014
(Amendment)Corrigendum 1 - Amendment 1 - Plugs, socket-outlets and couplers for industrial purposes - Part 1: General requirements
Corrigendum 1 - Amendment 1 - Plugs, socket-outlets and couplers for industrial purposes - Part 1: General requirements
Corrigendum 1 - Amendement 1 - Prises de courant pour usages industriels - Partie 1: Règles générales
General Information
Relations
Standards Content (Sample)
IEC 60309-1:1999/AMD1:2005
(Amendment 1 to the fourth edition)
Plugs, socket-outlets and couplers for
industrial purposes –
Part 1: General requirements
CO RRI G E NDUM 1
Table 3 – Size for connectable conductors
In the "Current A" column, "Series I", move value "125" to the line above, as follows:
1) 5)
Rating of Internal connection External earthing
the accessory connection if any
Flexible cables for plugs Solid or stranded cables
2) 6)
Voltage Current and connectors for socket-outlets
V A Solid or stranded cables
2)
for appliance inlets
Series Series Other Series I Series II Series I Series II Series I Series II
I II ratings
2 3) 2 3) 2 3)
mm AWG/MCM mm AWG/MCM mm AWG/MCM
Not 16 20 4 to 10 12 to 8 4 to 10 12 to 8
exceed-
32 30 4 to 10 12 to 8 4 to 10 12 to 8
ing 50
6 0,75 to 1 18 to - 0,75 to 1,5 18 to 16 2,5 14
10 1 to 1,5 - to 16 1 to 1,5 - to 16 2,5 14
16 20 1 to 2,5 16 to 12 1,5 to 4 16 to 12 6 10
25 1,5 to 4 16 to 12 2,5 to 6 14 to 10 6 10
32 30 2,5 to 6 14 to 10 2,5 to 10 14 to 8 10 8
40 4 to 10 12 to 8 4 to 16 12 to 6 10 8
50 4 to 10 12 to 8 4 to 16 12 to 6 16 6
Exceeding
63 60 6 to 16 10 to 6 6 to 25 10 to 4 25 4
80 10 to 25 8 to 4 16 to 35 6 to 2 25 4
90 10 to 25 8 to 4 16 to 35 6 to 2 25 4
125 100 16 to 50 6 to 0 25 to 70 4 to 00 25 4
...