Abstract

The requirements in this document govern the application of a set of explicit algebraic formulae for the calculation of specific characteristics of radiation heat flux from an open pool fire. This document is an implementation of the general requirements provided in ISO 16730‑1 for the case of fire dynamics calculations involving a set of explicit algebraic formulae. This document is arranged in the form of a template, where specific information relevant to the algebraic formulae is provided to satisfy the following types of general requirements: a) description of physical phenomena addressed by the calculation method; b) documentation of the calculation procedure and its scientific basis; c) limitations of the calculation method; d) input parameters for the calculation method; and e) domain of applicability of the calculation method. Examples of sets of algebraic formulae meeting the requirements of this document are provided in Annexes A and B. Annex A contains a set of algebraic formulae for radiation heat fluxes from a circular or near-circular open pool fire. Annex B contains formulae for configuration factors of a flame to a target.

Status
Not Published
Current Stage
6000 - International Standard under publication - 60 Publication
Start Date
12-Nov-2026
Due Date
01-Apr-2026
Completion Date
01-Apr-2026

Buy Documents

Draft

ISO/FDIS 24678-7 - Fire safety engineering — Requirements governing algebraic formulae — Part 7: Radiation heat flux received from an open pool fire

Release Date:02-Sep-2026
English language (39 pages)
sale 15% off
sale 15% off
Draft

REDLINE ISO/FDIS 24678-7 - Fire safety engineering — Requirements governing algebraic formulae — Part 7: Radiation heat flux received from an open pool fire

Release Date:02-Sep-2026
English language (39 pages)
sale 15% off
sale 15% off
Draft

ISO/FDIS 24678-7 - Ingénierie de la sécurité incendie — Exigences régissant les formules algébriques — Partie 7: Densité de flux énergétique rayonnée reçue d’un feu en nappe ouvert

Release Date:29-Sep-2026
French language (44 pages)
sale 15% off
sale 15% off

ISO 24678-7 is an ISO fire safety engineering standard that sets requirements for using explicit algebraic formulae to calculate radiation heat flux from an open pool fire. It is aimed at fire safety practitioners who need a documented calculation method for estimating thermal exposure to a target during fire safety design or assessment.

What does ISO 24678-7 specify?

ISO 24678-7 specifies how a set of explicit algebraic formulae shall be documented and used for radiation heat flux from an open pool fire. It implements the general requirements of ISO 16730-1 for fire dynamics calculations that rely on explicit algebraic formulae, and it is organized as a template so that the method, its basis, its limits, its inputs and its domain of applicability are stated in a consistent way.

The document is structured as follows:

AnnexWhat it covers
Annex AAlgebraic formulae for thermal radiation from a circular or near circular open pool fire
Annex BConfiguration factors of a cylindrical flame to a target

Clauses 1 to 3 cover scope, normative references, and terms and definitions. Clauses 4 to 8 set the requirements for describing the physical phenomena, the calculation process, limitations, input parameters, and the domain of applicability. Clause 9 gives an example of documentation.

What are the key requirements of ISO 24678-7?

ISO 24678-7 requires the calculation method to be described in a way that links the fire scenario, the target, and the selected formulae. In practice, that means a user should be able to see what fire geometry is being modeled, what target is being assessed, and why the chosen method is suitable.

  • Clause 4.2 states that open-pool-fire radiation is a thermo-physical and chemical process that may be transient or close to steady state. The practical point is that users need to think about fire behavior, fuel geometry, and the medium between the fire and the target before using any formula.
  • Clauses 4.3 to 4.5 require diagrams of the pool source, target positions, and any radiation screens, and they require the scenario elements and physical phenomena to be identified clearly. This matters because the calculation depends on geometry and on which fire scenario element is being assessed.
  • Clause 4.6 requires guidance when more than one method can calculate the same quantity. In practice, the document expects a reasoned choice of method rather than mixing formula sets without explanation.
  • Clause 4.7 says uncertainties in emissive power shall be handled properly, and it points to sensitivity analysis or conservative estimates. This matters when the result is used for safety decisions, because small input changes can have a large effect on predicted heat flux.
  • Clauses 5 to 8 apply the corresponding requirements of ISO 24678-1 to the calculation process, limitations, input parameters, and domain of applicability. This gives the method a common fire safety engineering structure and keeps the method tied to documented assumptions.
  • Clause 9 provides an example of documentation, and Annex A supplies a full worked example of a formula set meeting Clauses 4 to 8. This is useful when a team needs to write a calculation method in a report, model basis document, or design file.
  • Annex A shows a complete calculation chain: pool geometry, heat release rate, flame characteristics, configuration factor, atmospheric transmissivity, and final heat flux to the target. It also states that a single method should be used throughout the process, which is important because the parts are meant to work as one consistent model.
  • Annex B provides explicit configuration-factor formulae for upright and tilted cylindrical flames, including targets at different heights and orientations, plus a rectangular approximation. In practice, this is the view-factor step that links the flame model to the target location.

Annex A also gives practical method limits: it is intended for quasi-steady-state pool fire flames that are approximately circular or square in plan in an unobstructed environment, and it is presented for sooty hydrocarbon fires. Annex B states that its equations are also used by ISO 24678-9 for ejected flames.

What terms does ISO 24678-7 define?

ISO 24678-7 uses terms from ISO 13943 and defines the following key terms for this part.

  • Pool fire - burning of a horizontal, upward-facing fuel layer such as a liquid, liquefied gas, or horizontally placed melting plastic.
  • Open pool fire - a pool fire in open air or in a space large enough that surrounding enclosure effects on the flame are negligible.
  • Circular or near circular pool fire - a pool fire whose plan shape can be treated as circular.
  • Equivalent diameter - the diameter of a circular pool with the same plan area as a rectangular or irregular pool.
  • Absorption coefficient - the fraction of radiation intensity absorbed per unit length of travel through a medium.
  • Radiative fraction - the ratio of radiative heat release rate to total heat release rate.
  • Mean flame height - the time-averaged flame height, defined at the level where flame presence has a 50 % probability.
  • Atmospheric transmissivity - the ratio of transmitted radiation after a unit path through a participating medium to the radiation that would pass through clean air.

Who uses ISO 24678-7?

ISO 24678-7 is used by fire safety practitioners who work with calculation methods in fire safety engineering. The introduction says users are expected to be qualified and competent in the field and to understand the range in which a method can be applied.

It is relevant for engineers and assessors involved in the fire safety design of new or existing built environments, including buildings, ships, and vehicles. It is also used when comparing trial design options, checking whether performance criteria are met, and estimating consequences such as injury to people, equipment damage, ignition of materials, or deterioration of structural members.

What changed in ISO 24678-7 from the previous edition?

ISO 24678-7 is the second edition and it cancels and replaces ISO 24678-7:2019. The foreword states that the main body was revised to align with ISO 24678-1 on common requirements, and that some figures in Annex B were technically revised, including Figures B.3, B.14, and B.15.

Which standards are used with ISO 24678-7?

StandardContribution to ISO 24678-7
ISO 13943Provides fire safety vocabulary used for terms and definitions
ISO 16730-1Supplies the general requirements for verification and validation of calculation methods that ISO 24678-7 implements
ISO 16733-1Provides the framework for selecting design fire scenarios referenced in Clause 4
ISO 24678-1Provides the common requirements for algebraic formulae that Clauses 4 to 8 apply in this part
ISO 24678-2Provides the flame-height basis referenced in Annex A for the Heskestad method
ISO 24678-9Uses the same Annex B configuration-factor equations for ejected flames
ISO 24473Provides open calorimetry information cited in Annex A for obtaining heat release rate data

What does the ISO 24678-7 document contain?

ISO 24678-7 contains a clause structure for scope, references, definitions, and requirements, followed by two informative annexes with example formula sets. Annex A includes symbols, calculation steps, fuel-property tables, method selections such as Mudan-Croce, Shokri-Beyler, and the radiative fraction method, plus worked examples for radiation heat flux to a target.

Annex A also includes figures that show the radiation path, the calculation workflow, and radiative-fraction data for different fuels. Annex B contains symbols, geometry diagrams, explicit configuration-factor formulae for upright and tilted flames, and worked examples for vertical and horizontal targets.

Together, the document provides the algebraic structure, the assumptions, and the example calculations needed to document a pool-fire radiation model for design or assessment work.

Relations

Effective Date
12-Oct-2024

Buy Documents

Draft

ISO/FDIS 24678-7 - Fire safety engineering — Requirements governing algebraic formulae — Part 7: Radiation heat flux received from an open pool fire

Release Date:02-Sep-2026
English language (39 pages)
sale 15% off
sale 15% off
Draft

REDLINE ISO/FDIS 24678-7 - Fire safety engineering — Requirements governing algebraic formulae — Part 7: Radiation heat flux received from an open pool fire

Release Date:02-Sep-2026
English language (39 pages)
sale 15% off
sale 15% off
Draft

ISO/FDIS 24678-7 - Ingénierie de la sécurité incendie — Exigences régissant les formules algébriques — Partie 7: Densité de flux énergétique rayonnée reçue d’un feu en nappe ouvert

Release Date:29-Sep-2026
French language (44 pages)
sale 15% off
sale 15% off

Get Certified

Connect with accredited certification bodies for this standard

CIS Institut d.o.o.

Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

SA Slovenia Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Kmetijski inštitut Slovenije

Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

ISO 24678-7 is a draft published by the International Organization for Standardization (ISO). Its full title is "Fire safety engineering — Requirements governing algebraic formulae — Part 7: Radiation heat flux received from an open pool fire". This standard covers: The requirements in this document govern the application of a set of explicit algebraic formulae for the calculation of specific characteristics of radiation heat flux from an open pool fire. This document is an implementation of the general requirements provided in ISO 16730‑1 for the case of fire dynamics calculations involving a set of explicit algebraic formulae. This document is arranged in the form of a template, where specific information relevant to the algebraic formulae is provided to satisfy the following types of general requirements: a) description of physical phenomena addressed by the calculation method; b) documentation of the calculation procedure and its scientific basis; c) limitations of the calculation method; d) input parameters for the calculation method; and e) domain of applicability of the calculation method. Examples of sets of algebraic formulae meeting the requirements of this document are provided in Annexes A and B. Annex A contains a set of algebraic formulae for radiation heat fluxes from a circular or near-circular open pool fire. Annex B contains formulae for configuration factors of a flame to a target.

The requirements in this document govern the application of a set of explicit algebraic formulae for the calculation of specific characteristics of radiation heat flux from an open pool fire. This document is an implementation of the general requirements provided in ISO 16730‑1 for the case of fire dynamics calculations involving a set of explicit algebraic formulae. This document is arranged in the form of a template, where specific information relevant to the algebraic formulae is provided to satisfy the following types of general requirements: a) description of physical phenomena addressed by the calculation method; b) documentation of the calculation procedure and its scientific basis; c) limitations of the calculation method; d) input parameters for the calculation method; and e) domain of applicability of the calculation method. Examples of sets of algebraic formulae meeting the requirements of this document are provided in Annexes A and B. Annex A contains a set of algebraic formulae for radiation heat fluxes from a circular or near-circular open pool fire. Annex B contains formulae for configuration factors of a flame to a target.

ISO 24678-7 is classified under the following ICS (International Classification for Standards) categories: 13.220.01 - Protection against fire in general. The ICS classification helps identify the subject area and facilitates finding related standards.

ISO 24678-7 has the following relationships with other standards: It is inter standard links to ISO 24678-7:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

ISO 24678-7 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 pool fire
  • 3.2 open pool fire
  • 3.3 circular pool fire
  • 3.4 equivalent diameter
  • 3.5 absorption coefficient
  • 3.6 radiative fraction
  • 3.7 mean flame height
  • 3.8 atmospheric transmissivity
  • 4 Requirements governing the description of physical phenomena
  • 5 Requirements governing the calculation process
  • 6 Requirements governing limitations
  • 7 Requirements governing input parameters
  • 8 Requirements governing the domain of applicability
  • 9 Example of documentation
  • Annex A
  • Annex B
  • Bibliography

Introduction

The ISO 24678 series is intended to be used by fire safety practitioners involved with fire safety engineering calculation methods. It is expected that the users of this document are appropriately qualified and competent in the field of fire safety engineering. It is particularly important that the users understand the parameters within which particular methodologies may be used.

Algebraic formulae conforming to the requirements of this document are used with other engineering calculation methods during fire safety design. Such a design is preceded by the establishment of a context, including the fire safety goals and objectives to be met, as well as performance criteria when a trial fire safety design is subject to specified design fire scenarios. Engineering calculation methods are used to determine if these performance criteria are met by a particular design and if not, how the design needs to be modified.

The subjects of engineering calculations include the fire safety design of entirely new built environments, such as buildings, ships or vehicles as well as the assessment of the fire safety of existing built environments. The algebraic formulae discussed in this document can be useful for estimating the consequences of design fire scenarios. Such formulae are valuable for allowing the practitioner to quickly determine how a proposed fire safety design needs to be modified to meet performance criteria and to compare among multiple trial designs. Detailed numerical calculations can be carried out up until the final design documentation. Examples of areas where algebraic formulae have been applicable include determination of convective and radiative heat transfer from fire plumes, prediction of ceiling jet flow properties governing detector response times, calculation of smoke transport through vent openings, and analysis of compartment fire hazards such as smoke filling and flashover. However, the simple models often have stringent limitations and are less likely to include the effects of multiple phenomena occurring in the design fire scenarios. The general principles of fire safety engineering are described in ISO 23932-1, which provides a performancebased methodology for engineers to assess the level of fire safety for new or existing built environments. Fire safety is evaluated through an engineered approach based on the quantification of the behaviour of fire and based on knowledge of the consequences of such behaviour on life safety, property and the environment. ISO 23932-1 provides the process (i.e. necessary steps) and essential elements for conducting a robust performance-based fire safety design.

ISO 23932-1 is supported by a set of available fire safety engineering International Standards on the methods and data needed for all the steps in a fire safety engineering design as summarized in Figure 1 (taken from ISO 23932-1:2018, Clause 4). The set includes the ISO 16730 series, the ISO 16732 series, the ISO 16733 series, ISO/TR 16738, the ISO 24678 series, the ISO 24679 series, ISO 23932-1, ISO/TS 29761 and other supporting documents that provide examples of and guidance on the application of these standards. Each International Standard supporting the global fire safety engineering analysis and information system includes language in the introduction to tie the standard to the steps in the fire safety engineering design process outlined in ISO 23932-1. ISO 23932-1 requires that engineering methods be selected properly with acceptable accuracy to predict the fire consequences of specific scenarios and scenario elements (ISO 23932-1:2018, Clause 12). Pursuant to the requirements of ISO 23932-1, this document provides the requirements governing algebraic formulae for fire safety engineering. This step in the fire safety engineering process is shown as a highlighted box in Figure 1 and described in ISO 23932-1.

ISO/FDIS 24678-7:2026(en) Figure 1 — Flow chart illustrating the fire safety engineering (FSE) design process (from ISO 23932-1:2018)

FINAL DRAFT International Standard ISO/FDIS 24678-7:2026(en) Fire safety engineering — Requirements governing algebraic formulae — Part 7:

Radiation heat flux received from an open pool fire

1 Scope

The requirements in this document govern the application of a set of explicit algebraic formulae for the calculation of specific characteristics of radiation heat flux from an open pool fire. This document is an implementation of the general requirements provided in ISO 16730-1for the case of fire dynamics calculations involving a set of explicit algebraic formulae. This document is arranged in the form of a template, where specific information relevant to the algebraic formulae is provided to satisfy the following types of general requirements:

a) description of physical phenomena addressed by the calculation method; b) documentation of the calculation procedure and its scientific basis; c) limitations of the calculation method; d) input parameters for the calculation method; and e) domain of applicability of the calculation method.

Examples of sets of algebraic formulae meeting the requirements of this document are provided in Annex A and Annex B. Annex A contains a set of algebraic formulae for radiation heat fluxes from a circular or nearcircular open pool fire. Annex B contains formulae for configuration factors of a flame to a target.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 13943, Fire safety — Vocabulary ISO 16733-1, Fire safety engineering — Selection of design fire scenarios and design fires — Part 1: Selection of design fire scenarios ISO 24678-1, Fire safety engineering — Requirements governing algebraic formulae — Part 1: General requirements

3 Terms and definitions

For the purposes of this document, the terms and definitions given in ISO 13943 and the following apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https:// www .iso .org/ obp

ISO/FDIS 24678-7:2026(en) - IEC Electropedia: available at https:// www .electropedia .org/

3.1 pool fire

burning of a horizontal, upward-facing, combustible fuel of liquids, liquefied gases or horizontally placed melting plastic materials

3.2 open pool fire

pool fire (3.1) in open air or in a space that is very large relative to the size of the fire, where the confined effect of the built environment on the behaviour of its flame is negligible Note 1 to entry: The open pool fire characteristics are dependent on the outside conditions such as wind.

3.3 circular pool fire

near circular pool fire pool fire (3.1) whose geometry can be approximated by a circular shape Note 1 to entry: In case of an elongated pool, this approximation is valid if the ratio between the longest dimension and [6] the shortest dimension is not greater than 2 to 3 .

3.4 equivalent diameter

diameter of a circular pool of which the plan area is equivalent with rectangular or irregularly shaped pools

3.5 absorption coefficient

fraction of absorbed radiation intensity per unit length of radiation path

3.6 radiative fraction

ratio of the radiative heat release rate to the total heat release rate

3.7 mean flame height

time-averaged height of flames above the base of a fire, defined as the elevation where the probability of finding flames is 50 %

3.8 atmospheric transmissivity

ratio of the transmitted radiation intensity after passing through unit length of a participating medium (carbon dioxide, water vapour, dust and fog) to the radiation intensity that would have passed the same distance through clean air

4 Requirements governing the description of physical phenomena

4.1 The requirements specified in ISO 24678-1:2019, Clause 4, governing the description of physical phenomena, shall apply in addition to the requirements in the following subclauses. 4.2 Radiation heat flux from an open pool fire is a complex thermo-physical and chemical phenomenon that can be highly transient or nearly steady-state. Radiation heat flux depends on the properties and geometry of the combustible, and the environment between the radiation source and the "target" that receives the heat flux. The properties of the target need to be considered when further calculations of target behaviour are assessed, e.g. injuries to people, malfunction/damage of a piece of equipment, ignition of a combustible material, deteriorations of structural members. The physical phenomena described in this document are concerned with only the calculations of the radiation heat flux received by a target from an open pool fire.

ISO/FDIS 24678-7:2026(en) 4.3 General types of pool sources, pool geometry and relative positions of the considered targets (including the position of radiation screens placed between the pool and the targets) shall be described with the aid of diagrams.

4.4 Scenario elements, in accordance with ISO 16733-1, to which specific formulae apply shall be clearly identified. Radiation heat flux characteristics to be calculated and their useful ranges shall be clearly identified, including those characteristics inferred by association with calculated quantities, if applicable. 4.5 Physical phenomena (e.g. pool formation during a continuous release, interaction between fire and extinguishing materials) to which specific formulae apply shall be clearly identified. 4.6 Because different formulae describe different pool source radiative flame characteristics (see 4.3) or apply to different scenarios (see 4.4), it shall be shown that if there is more than one method to calculate a given quantity, guidance shall be given on the selection of appropriate methods. 4.7 The radiative emission from flame is affected by various factors. The uncertainties in emissive power shall be considered properly. Sensitivity analysis or conservative estimates is desirable. Sensitivity analysis is used to identify the input variables that cause the greatest variation in the output results. For example, a sensitivity analysis may be conducted on radiative fraction value to evaluate if a small variation may have a significant impact on the radiated heat flux. If so, radiative fraction should be used cautiously. The use of conservative assumptions may limit the impact of uncertainties on the final results. Safety factors and/or margins may be applied to input or output data. Appropriate safety factors and margins are usually derived [7] from references on model validation and verification .

5 Requirements governing the calculation process

The requirements specified in ISO 24678-1:2019, Clause 5, governing the calculation process, shall apply.

6 Requirements governing limitations

The requirements specified in ISO 24678-1:2019, Clause 6, governing limitations, shall apply.

7 Requirements governing input parameters

The requirements specified in ISO 24678-1:2019, Clause 7, governing input parameters, shall apply.

8 Requirements governing the domain of applicability

The requirements specified in ISO 24678-1:2019, Clause 8, governing the domain of applicability, shall apply.

9 Example of documentation

An example of sets of algebraic formulae meeting the requirements in Clause 4 to Clause 8 is provided in Annex A.

ISO/FDIS 24678-7:2026(en)

Annex A

(informative)

Algebraic formulae for thermal radiation from a circular or near circular open pool fire A.1 Symbols and abbreviated terms used in this annex

A plan area of a pool fire source (m ) s D equivalent diameter of a pool fire source (m)

E emissive power of a flame (kW/m ) f

E emissive power of the luminous region of a flame (kW/m ) max

E emissive power of smoke (kW/m ) s f configuration factor of side surface of an upright cylinder to a vertical target (−) cyl-v F configuration factor of a flame to a target (−)

F configuration factor of a flame to a vertical target (−) 12,v

g gravity acceleration (9,81 m/s ) H vertical distance from flame base to a target (m) −1 k radiation absorption coefficient of a flame from various fuels (m ) L mean flame height (m)

m" mass burning rate per unit area of a pool (kg/m ·s)

mass burning rate per unit area of a sufficiently large pool (kg/m ·s)

m

m non-dimensional burning rate (−)

q″ radiation heat flux to a target (kW/m )

heat release rate from a pool fire (kW) Q u wind velocity (m/s) w u* non-dimensional wind velocity X horizontal distance to a target from the centre of a flame (m) −1 β radiation absorption coefficient of a flame taking the diameter as the characteristic length (m ) χ radiative fraction (−) r Γ heat of combustion of fuel (J/kg) θ flame tilt angle (rad)

ISO/FDIS 24678-7:2026(en)

ρ density of normal ambient air (1,2 kg/m ) a τ atmospheric transmissivity (−) A.2 Description of the physical phenomena addressed by the algebraic formula set A.2.1 General The formulae described in this annex provide radiation heat fluxes from a pool fire to a target and can be applicable to various locations and orientations. The set of formulae is particularly convenient for horizontal and vertical target orientations. The formulae presented here have been validated on sooty liquid hydrocarbon fires.

A.2.2 General description of the calculation method Estimating the radiation heat flux received by a target from a pool fire involves the three following steps:

  • determination of the characteristics of the pool fire (burning surface, mass burning rate, duration of the fire, time to steady-state conditions, etc.);
  • determination of the thermal radiation characteristics of the pool fire (flame height, flame tilt, emissive power of the flames, etc.);
  • calculation of the radiation heat flux received by a target (configuration factor of a flame to a target, atmospheric transmissivity along radiation path).

It is very important that a single method be used for all the three steps of this process. The methods presented in this annex constitute whole methods and its parts cannot be changed. The validation of the whole model needs to be considered, not its components individually. A.2.3 Scenario elements to which the set of formulae is applicable The set of formulae is applicable to thermal radiation from quasi-steady-state pool fire flames that are approximately circular or square in plan area in an unobstructed environment, unless otherwise stated. A.2.4 Self-consistency of the set of formulae The set of formulae provided in this annex has been derived and reviewed to ensure that the calculation results from different formulae in the set are consistent (i.e. do not produce conflicts). A.2.5 Standards and other documents where the set of formulae is used None specified.

A.3 Documentation of the set of formulae A.3.1 General As shown in Figure A.1, radiation is emitted by a flame and received by a target. The heat flux received by a target from a pool fire can be calculated with Formula (A.1):

qE F (A.1) f12

ISO/FDIS 24678-7:2026(en) Key 1 flame (surface 1) 2 target (surface 2) 3 emissions (to all directions) 4 heat flux to a target Figure A.1 — Radiation from a flame to a target Figure A.2 depicts the successive steps necessary for estimating the radiation heat flux received by a target from a pool fire. From the specified burning object characteristics, the heat release rate and the diameter of the pool, when not given, are estimated. The emissive power from the flame surface is assumed to be a function of the diameter of the pool. The flame geometry is calculated by using the heat release rate and fire source diameter. Finally, the configuration factor of a flame to a target is calculated. The effect of blockage by a participation medium such as soot, water vapour and dipole gases is considered, where necessary, as atmospheric transmissivity.

The target is considered as an infinitesimally small plane element, which is assumed to be located at the minimum distance between the fire and the real target. Because configuration factors are also considered in the calculations of the physical phenomena, the point is associated with an element surface. In this annex, a solid cylindrical flame model is adopted. As presented in Figure A.2, the method is composed of different interdependent sub-models, mean flame height, emissive power and so on. Figure A.2 — Calculation process of radiation heat flux received by a target from a pool fire

ISO/FDIS 24678-7:2026(en) A.3.2 Geometry and heat release rate of pool fires A.3.2.1 Equivalent diameter of a pool fire source The equivalent diameter of a pool fire source, D, is given by Formula (A.2):

4A s D (A.2)

A.3.2.2 Heat release rate

The heat release rate from a pool fire, Q , is given by Formula (A.3):

Qm A (A.3) s Examples of mass burning rate and net heat of combustion are shown in Table A.1. Using these values, the [8] mass burning rate per unit area of a pool is estimated by Formula (A.4) :

mm{e1 xp()kD } (A.4)

NOTE Formula (A.4) is valid for pool fires with D > 0,2 m.

[9] Table A.1 — Net heat of combustion and mass burning rate of various fuels Net heat of Mass burning rate at Radiation absorption coef- Fuel combustion sufficiently large pool ficient

−1

Γ (MJ/kg) k (m )

m (kg/m ·s)

Liquid H 120 0,017 6,1

LNG 50,0 0,078 1,1 LP-gas 46,0 0,099 1,4 Methanol 20,0 0,017 — Ethanol 26,8 0,015 — Butane 42,7 0,078 2,7 Hexane 44,7 0,074 1,9 Heptane 44,6 0,101 1,1 benzene 40,1 0,085 2,7 Xylene 40,8 0,090 1,4 Acetone 25,8 0,041 1,9 Dioxane 26,2 0,018 5,4 Diethyl ether 34,2 0,085 0,7 Benzine 44,7 0,048 3,6 Gasoline 43,7 0,055 2,1 Kerosine 43,2 0,039 3,5 JP-4 43,5 0,051 3,6 JP-5 43,0 0,054 1,6 Transformer oil 46,4 0,039 0,7 Fuel oil, heavy 39,7 0,035 1,7 Crude oil 42,5 0,022 2,8

ISO/FDIS 24678-7:2026(en) A.3.3 Cylindrical solid flame model and surface emissive power A.3.3.1 Selection of methods Several models have been developed based on the solid flame concept. The most common one is the cylindrical solid flame model as shown in Figure A.1. This model has been chosen to represent the radiative emitter by the lateral envelope of the flame as well as the upper disk. There are various methods for estimating the surface emissive power. The surface emissive power is related [10] to the area of the cylindrical solid flame and the flame height. The Mudan-Croce’s method , Shokri-Beyler’s [11] method and the radiative fraction method are adopted in this annex. Each set of formulae corresponds to a specific fuel type and a range of fuel diameter. The Mudan-Croce method is accompanied with the Thomas’ [12],[13] formula for flame height and tilt . The Shokri-Beyler method is associated with the Heskestad’s [14] formula for flame height as described in ISO 24678-2. As the estimation formulae for the emissive power is related to the surface area of flame, mixing various methods shall be avoided. A.3.3.2 Mudan-Croce’s method A.3.3.2.1 General The Mudan-Croce’s method, for estimating the incident heat flux from a pool fire, suggests the following Formulae (A.5) to (A.9) for the effective emissive power of gasoline, kerosene, and JP-4 flames, but it is not recommended for LNG. The set of formulae uses correlations of flame height developed by Thomas from wood crib experiments. In case of windy conditions, the flame tilt angle is calculated by correlation developed by Thomas. This method is recommended in the range of diameter of approximately 1 m to 60 m. A.3.3.2.2 Flame height by Thomas’ formula [15] In case of quiescent atmosphere, the flame height is calculated by Formula (A.5) :

...

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 4 Requirements governing the description of physical phenomena
  • 5 Requirements governing the calculation process
  • 6 Requirements governing limitations
  • 7 Requirements governing input parameters
  • 8 Requirements governing the domain of applicability
  • 9 Example of documentation
  • Annex A
  • Annex B
  • Bibliography

Introduction

This documentThe ISO 24678 series is intended to be used by fire safety practitioners involved with fire safety engineering calculation methods. It is expected that the users of this document are appropriately qualified and competent in the field of fire safety engineering. It is particularly important that the users understand the parameters within which particular methodologies canmay be used. Algebraic formulae conforming to the requirements of this document are used with other engineering calculation methods during fire safety design. Such a design is preceded by the establishment of a context, including the fire safety goals and objectives to be met, as well as performance criteria when a trial fire safety design is subject to specified design fire scenarios. Engineering calculation methods are used to determine if these performance criteria are met by a particular design and if not, how the design needs to be modified. The subjects of engineering calculations include the fire safety design of entirely new built environments, such as buildings, ships or vehicles as well as the assessment of the fire safety of existing built environments. The algebraic formulae discussed in this document can be useful for estimating the consequences of design fire scenarios. Such formulae are valuable for allowing the practitioner to quickly determine how a proposed fire safety design needs to be modified to meet performance criteria and to compare among multiple trial designs. Detailed numerical calculations can be carried out up until the final design documentation. Examples of areas where algebraic formulae have been applicable include determination of convective and radiative heat transfer from fire plumes, prediction of ceiling jet flow properties governing detector response times, calculation of smoke transport through vent openings, and analysis of compartment fire hazards such as smoke filling and flashover. However, the simple models often have stringent limitations and are less likely to include the effects of multiple phenomena occurring in the design fire scenarios. The general principles of fire safety engineering are described in ISO 23932-1, which provides a performancebased methodology for engineers to assess the level of fire safety for new or existing built environments. Fire safety is evaluated through an engineered approach based on the quantification of the behaviour of fire and based on knowledge of the consequences of such behaviour on life safety, property and the environment. ISO 23932-1 provides the process (i.e. necessary steps) and essential elements to conductfor conducting a robust performance-based fire safety design.

ISO 23932-1 is supported by a set of available fire safety engineering International Standards on the methods and data needed for all the steps in a fire safety engineering design as summarized in Figure 1 Figure 1 (taken from ISO 23932-1:2018, Clause 4). The set includes the ISO 16730 series, the ISO 16732 series, the ISO 16733 series, ISO/TR 16738, the ISO 24678 series, the ISO 24679 series, ISO 23932-1, ISO/TS 29761 and other supporting documents that provide examples of and guidance on the application of these standards. Each International Standard supporting the global fire safety engineering analysis and information system includes language in the introduction to tie the standard to the steps in the fire safety engineering design process outlined in ISO 23932-1. ISO 23932-1 requires that engineering methods be selected properly with acceptable accuracy to predict the fire consequences of specific scenarios and scenario elements (ISO 23932- 1:2018, Clause 12). Pursuant to the requirements of ISO 23932-1, this document provides the requirements governing algebraic formulae for fire safety engineering. This step in the fire safety engineering process is shown as a highlighted box in Figure 1 Figure 1 and described in ISO 23932-1.

ISO #####-#:####(X/FDIS 24678-7:2026(en)

Figure 1 — Flow chart illustrating the fire safety engineering (FSE) design process (from ISO 23932- 1:2018)

DRAFT International Standard ISO/FDIS 24678-7:2026(en)

Fire safety engineering — Requirements governing algebraic formulae — — Part 7:

Radiation Heat Flux Receivedheat flux received from an Open Pool Fireopen pool fire

1 Scope

The requirements in this document govern the application of a set of explicit algebraic formulae for the calculation of specific characteristics of radiation heat flux from an open pool fire. This document is an implementation of the general requirements provided in ISO 16730-1 for1for the case of fire dynamics calculations involving a set of explicit algebraic formulae. This document is arranged in the form of a template, where specific information relevant to the algebraic formulae is provided to satisfy the following types of general requirements:

a) a) description of physical phenomena addressed by the calculation method; b) b) documentation of the calculation procedure and its scientific basis; c) c) limitations of the calculation method; d) d) input parameters for the calculation method; and e) e) domain of applicability of the calculation method.

Examples of sets of algebraic formulae meeting the requirements of this document are provided in Annex AAnnex A and Annex BAnnex B. Annex A. Annex A contains a set of algebraic formulae for radiation heat fluxes from a circular or near-circular open pool fire. Annex BAnnex B contains formulae for configuration factors of a flame to a target.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 13943, Fire safety — Vocabulary ISO 16730-1, Fire safety engineering — Procedures and requirements for verification and validation of calculation methods — Part 1: General ISO 16733--1, Fire safety engineering — Selection of design fire scenarios and design fires — Part 1: Selection of design fire scenarios

ISO #####-#:####(X/FDIS 24678-7:2026(en) ISO 24678--1, Fire safety engineering — Requirements governing algebraic formulae — Part 1: General requirements

3 Terms and definitions

For the purposes of this document, the terms and definitions given in ISO 13943 and the following apply. ISO and IEC maintain terminologyterminological databases for use in standardization at the following addresses:

  • — ISO Online browsing platform: available at https://www.iso.org/obp
  • — IEC Electropedia: available at https://www.electropedia.org/ 3.1 3.1 pool fire burning of a horizontal, upward-facing, combustible fuel of liquids, liquefied gases or horizontally placed melting plastic materials 3.2 3.2 open pool fire pool fire (3.1(3.1)) in open air or in a space that is very large relative to the size of the fire, where the confined effect of the built environment on the behaviour of its flame is negligible Note 1 to entry: The open pool fire characteristics are dependent on the outside conditions such as wind. 3.3 3.3 circular or pool fire near circular pool fire pool fire (3.1(3.1)) whose geometry can be approximated by a circular shape Note 1 to entry: In case of an elongated pool, this approximation is valid if the ratio between the longest dimension and [5] the shortest dimension is not greater than 2 to 3[6] ..

3.4 3.4 equivalent diameter diameter of a circular pool of which the plan area is equivalent with rectangular or irregularly shaped pools 3.5 3.5 absorption coefficient fraction of absorbed radiation intensity per unit length of radiation path. 3.6 3.6 radiative fraction ratio of the radiative heat release rate to the total heat release rate 3.7 3.7 mean flame height time-averaged height of flames above the base of a fire, defined as the elevation where the probability of finding flames is 50 % 3.8 3.8 atmospheric transmissivity ratio of the transmitted radiation intensity after passing through unit length of a participating medium (carbon dioxide, water vapour, dust and fog) to the radiation intensity that would have passed the same distance through clean air

ISO/FDIS 24678-7:2026(en)

4 Requirements governing the description of physical phenomena

4.1 4.1 The requirements specified in Clause 4 of ISO 24678-1:2019, Clause 4, governing the description of physical phenomena, shall apply in addition to the requirements in the following subclauses. 4.2 4.2 Radiation heat flux from an open pool fire is a complex thermo-physical and chemical phenomenon that can be highly transient or nearly steady-state. Radiation heat flux depends on the properties and geometry of the combustible, and the environment between the radiation source and the "target" that receives the heat flux. The properties of the target need to be considered when further calculations of target behaviour are assessed, e.g. injuries to people, malfunction/damage of a piece of equipment, ignition of a combustible material, deteriorations of structural members. The physical phenomena described in this document are concerned with only the calculations of the radiation heat flux received by a target from an open pool fire.

4.3 4.3 General types of pool sources, pool geometry and relative positions of the considered targets (including the position of radiation screens placed between the pool and the targets) shall be described with the aid of diagrams.

4.4 4.4 Scenario elements, in accordance with ISO 16733-1, to which specific formulae apply shall be clearly identified. Radiation heat flux characteristics to be calculated and their useful ranges shall be clearly identified, including those characteristics inferred by association with calculated quantities, if applicable. 4.5 4.5 Physical phenomena (e.g. pool formation during a continuous release, interaction between fire and extinguishing materials) to which specific formulae apply shall be clearly identified. 4.6 4.6 Because different formulae describe different pool source radiative flame characteristics (see 4.34.3)) or apply to different scenarios (see 4.44.4),), it shall be shown that if there is more than one method to calculate a given quantity, guidance shall be given on the selection of appropriate methods. 4.7 4.7 The radiative emission from flame is affected by various factors. The uncertainties in emissive power shall be considered properly. Sensitivity analysis or conservative estimates is desirable. Sensitivity analysis is used to identify the input variables that cause the greatest variation in the output results. For example, a sensitivity analysis may be conducted on radiative fraction value to evaluate if a small variation may have a significant impact on the radiated heat flux. If so, radiative fraction should be used cautiously. The use of conservative assumptions may limit the impact of uncertainties on the final results. Safety factors and/or margins may be applied to input or output data. Appropriate safety factors and margins are usually [6] derived from references on model validation and verification[7]. .

5 Requirements governing the calculation process

The requirements specified in Clause 5 of ISO 24678-1:2019, Clause 5, governing the calculation process, shall apply.

6 Requirements governing limitations

The requirements specified in Clause 6 of ISO 24678-1:2019, Clause 6, governing limitations, shall apply.

7 Requirements governing input parameters

The requirements specified in Clause 7 of ISO 24678-1:2019, Clause 7, governing input parameters, shall apply.

ISO #####-#:####(X/FDIS 24678-7:2026(en)

8 Requirements governing the domain of applicability

The requirements specified in Clause 8 of ISO 24678-1:2019, Clause 8, governing the domain of applicability, shall apply.

9 Example of documentation

An example of sets of algebraic formulae meeting the requirements in 4Clause 4 to 8Clause 8 is provided in Annex AAnnex A..

ISO/FDIS 24678-7:2026(en)

Annex A

(informative)

Algebraic formulae for thermal radiation from a circular or near circular open pool fire A.1 Symbols and abbreviated terms used in this Annexannex

A plan area of a pool fire source (m ) s D equivalent diameter of a pool fire source (m)

E emissive power of a flame (kW/m ) f

E emissive power of the luminous region of a flame (kW/m ) max

Es emissive power of smoke (kW/m ) f configuration factor of side surface of an upright cylinder to a vertical target (−) cyl-v F configuration factor of a flame to a target (−)

F configuration factor of a flame to a vertical target (−) 12,v

g gravity acceleration (9,81 m/s ) H vertical distance from flame base to a target (m) −1 k radiation absorption coefficient of a flame from various fuels (m ) L mean flame height (m)

𝑚˙ " mass burning rate per unit area of a pool (kg/m ·s)

mass burning rate per unit area of a sufficiently large pool (kg/m ·s) 𝑚˙

m non-dimensional burning rate (−)

𝑞˙ ″ radiation heat flux to a target (kW/m )

heat release rate from a pool fire (kW) 𝑄 u wind velocity (m/s) w u* non-dimensional wind velocity X horizontal distance to a target from the centre of a flame (m) −1 β radiation absorption coefficient of a flame taking the diameter as the characteristic length (m ) χ radiative fraction (−) r heat of combustion of fuel (J/kg) Γ θ flame tilt angle (rad)

ρ density of normal ambient air (1,2 kg/m ) a τ atmospheric transmissivity (−)

ISO #####-#:####(X/FDIS 24678-7:2026(en) A.2 Description of the physical phenomena addressed by the algebraic formula set A.2.1 General The formulae described in this annex provide radiation heat fluxes from a pool fire to a target and can be applicable to various locations and orientations. The set of formulae is particularly convenient for horizontal and vertical target orientations. The formulae presented here have been validated on sooty liquid hydrocarbon fires.

A.2.2 General description of the calculation method Estimating the radiation heat flux received by a target from a pool fire involves the three following steps:

  • — determination of the characteristics of the pool fire (burning surface, mass burning rate, duration of the fire, time to steady-state conditions, etc.);
  • — determination of the thermal radiation characteristics of the pool fire (flame height, flame tilt, emissive power of the flames, etc.);
  • — calculation of the radiation heat flux received by a target (configuration factor of a flame to a target, atmospheric transmissivity along radiation path).

It is very important that a single method be used for all the three steps of this process. The methods presented in this annex constitute whole methods and its parts cannot be changed. The validation of the whole model needs to be considered, not its components individually.

A.2.3 Scenario elements to which the set of formulae is applicable The set of formulae is applicable to thermal radiation from quasi-steady-state pool fire flames that are approximately circular or square in plan area in an unobstructed environment, unless otherwise stated. A.2.4 Self-consistency of the set of formulae The set of formulae provided in this annex has been derived and reviewed to ensure that the calculation results from different formulae in the set are consistent (i.e. do not produce conflicts). A.2.5 Standards and other documents where the set of formulae is used None specified.

A.3 Documentation of the set of formulae A.3.1 General As shown in Error! Reference source not found.Figure A.1,, radiation is emitted by a flame and received by a target. The heat flux received by a target from a pool fire can be calculated with Error! Reference source not found.the following algebraic formula::

𝑞˙ = 𝜏𝐸 𝐹 f 12 (A.1)

ISO/FDIS 24678-7:2026(en)

Key 1 flame (surface 1) 2 target (surface 2) 3 emissions (to all directions) 4 heat flux to a target Figure A.1 — Radiation from a flame to a target Figure A.2 Figure A.2 depicts the successive steps necessary for estimating the radiation heat flux received by a target from a pool fire. From the specified burning object characteristics, the heat release rate and the diameter of the pool, when not given, are estimated. The emissive power from the flame surface is assumed to be a function of the diameter of the pool. The flame geometry is calculated by using the heat release rate and fire source diameter. Finally, the configuration factor of a flame to a target is calculated. The effect of blockage by a participation medium such as soot, water vapour and dipole gases is considered, where necessary, as atmospheric transmissivity.

ISO #####-#:####(X/FDIS 24678-7:2026(en) The target is considered as an infinitesimally small plane element, which is assumed to be located at the minimum distance between the fire and the real target. Because configuration factors are also considered in the calculations of the physical phenomena, the point is associated with an element surface. In this annex, a solid cylindrical flame model is adopted. As presented in Figure A.2 Figure A.2,, the method is composed of different interdependent sub-models, mean flame height, emissive power and so on.

Figure A.2 — Calculation process of radiation heat flux received by a target from a pool fire A.3.2 Geometry and heat release rate of pool fires A.3.2.1 Equivalent diameter of a pool fire source The equivalent diameter of a pool fire source, D, is given by Error! Reference source not found.Formula (A.2)::

4𝐴 s

𝐷 = 𝜋 (A.2) A.3.2.2 Heat release rate

The heat release rate from a pool fire,,, 𝑄, is given by Error! Reference source not found.Formula (A.3)::

ISO/FDIS 24678-7:2026(en)

𝑄 = 𝛤𝑚˙ ″𝐴 (A.3) s Examples of mass burning rate and net heat of combustion are shown in Error! Reference source not found.Table A.1.. Using these values, the mass burning rate per unit area of a pool is estimated by Error! [7] Reference source not found.Error! Reference source not found.Formula (A.4) ::

𝑚˙ ″ = 𝑚˙ {1 − exp(−𝑘𝐷)}

(A.4) NOTE Formula (A.4) (A.4) is valid for pool fires with D > 0,2 m. [ [8]] Table A.1 — Net heat of combustion and mass burning rate of various fuels [9] Net heat of Mass burning rate at Radiation absorption Fuel combustion sufficiently large pool coefficient

2 −1 k (m ) Γ (MJ/kg) 𝑚˙ (kg/m ·s)

Liquid H2 120 0,017 6,1 LNG 50,0 0,078 1,1 LP-gas 46,0 0,099 1,4 Methanol 20,0 0,017 — Ethanol 26,8 0,015 — Butane 42,7 0,078 2,7 Hexane 44,7 0,074 1,9 Heptane 44,6 0,101 1,1 benzene 40,1 0,085 2,7 Xylene 40,8 0,090 1,4 Acetone 25,8 0,041 1,9 Dioxane 26,2 0,018 5,4 Diethyl ether 34,2 0,085 0,7 Benzine 44,7 0,048 3,6 Gasoline 43,7 0,055 2,1 Kerosine 43,2 0,039 3,5 JP-4 43,5 0,051 3,6 JP-5 43,0 0,054 1,6 Transformer oil 46,4 0,039 0,7 Fuel oil, heavy 39,7 0,035 1,7 Crude oil 42,5 0,022 2,8 A.3.3 Cylindrical solid flame model and surface emissive power A.3.3.1 Selection of methods Several models have been developed based on the solid flame concept. The most common one is the cylindrical solid flame model as shown in Figure A.1 Figure A.1.. This model has been chosen to represent the radiative emitter by the lateral envelope of the flame as well as the upper disk.

...

Contents

  • Introduction
  • 1 Domaine d’application
  • 2 Références normatives
  • 3 Termes et définitions
  • 3.1 feu en nappe
  • 3.2 feu en nappe ouvert
  • 3.3 feu en nappe circulaire
  • 3.4 diamètre équivalent
  • 3.5 coefficient d’absorption
  • 3.6 fraction radiative
  • 3.7 hauteur moyenne de la flamme
  • 3.8 transmissivité atmosphérique
  • 4 Exigences régissant la description des phénomènes physiques
  • 5 Exigences régissant le processus de calcul
  • 6 Exigences régissant les limites
  • 7 Exigences régissant les paramètres d’entrée
  • 8 Exigences régissant le domaine d’application
  • 9 Exemple de documentation
  • Annexe A
  • Annexe B
  • Bibliographie

Introduction

La série ISO 24678 est destinée à être utilisée par les praticiens de la sécurité incendie impliqués dans les méthodes de calcul utilisées dans l’ingénierie de la sécurité incendie. Il est attendu que les utilisateurs du présent document possèdent une qualification et une compétence appropriées dans le domaine de l’ingénierie de la sécurité incendie. Il est particulièrement important que les utilisateurs comprennent les paramètres avec lesquels les méthodologies spécifiques peuvent être utilisées. Les formules algébriques conformes aux exigences du présent document sont utilisées conjointement avec d’autres méthodes de calcul d’ingénierie lors du dimensionnement de la sécurité incendie. Ces calculs sont précédés par l’établissement d’un contexte, y compris les buts et objectifs de sécurité contre l’incendie à atteindre, ainsi que par des critères de performance lorsqu’un dimensionnement de sécurité incendie d’essai est soumis à des scénarios d’incendie de dimensionnement. Les méthodes de calcul d’ingénierie sont utilisées pour déterminer si ces critères de performance sont satisfaits par un dimensionnement particulier et si ce n’est pas le cas, comment il est nécessaire de modifier le dimensionnement. Les aspects couverts par les calculs d’ingénierie incluent le dimensionnement de la sécurité incendie des environnements bâtis entièrement neufs, par exemple les bâtiments, les navires ou les véhicules, ainsi que l’évaluation de la sécurité contre l’incendie des environnements bâtis existants. Les formules algébriques mentionnées dans le présent document peuvent être utiles pour estimer les conséquences des scénarios d’incendie de dimensionnement. Ces formules sont utiles dans la mesure où elles permettent au praticien de déterminer rapidement la manière dont il est nécessaire de modifier un dimensionnement de sécurité incendie suggéré pour répondre aux critères de performance, et de le comparer avec de multiples dimensionnements d’essai. Les calculs numériques détaillés peuvent être effectués jusqu’à la documentation de dimensionnement finale. Les domaines dans lesquels des formules algébriques se sont avérées applicables comprennent, par exemple, la détermination du transfert de chaleur par convection et par rayonnement, des panaches de feu, la prédiction des propriétés des écoulements en jet sous plafond régissant les temps de réponse des détecteurs, le calcul du transport de la fumée dans les ouvertures de ventilation et l’analyse des dangers d’un feu en compartiment tels que le remplissage par la fumée et l’embrasement généralisé. Cependant, les modèles simples ont parfois des limites contraignantes et sont moins susceptibles d’inclure les effets de phénomènes multiples qui se produisent dans le scénario d’incendie de dimensionnement.

Les principes généraux de l’ingénierie de la sécurité incendie sont décrits dans l’ISO 23932-1, qui fournit une méthodologie axée sur la performance utile aux ingénieurs pour l’évaluation du niveau de sécurité incendie des environnements bâtis neufs ou existants. La sécurité incendie est évaluée par une méthode d’ingénierie basée sur la quantification du comportement du feu, prenant en compte la connaissance des conséquences d’un tel comportement sur la protection des vies humaines, des biens et de l’environnement. L’ISO 23932-1 décrit le processus (c’est-à-dire les étapes nécessaires) et les éléments essentiels afin de réaliser un dimensionnement performantiel et robuste de la sécurité incendie. L’ISO 23932-1 s’appuie sur un ensemble de normes ISO d’ingénierie de la sécurité incendie disponibles et portant sur les méthodes et les données requises pour toutes les étapes de conception d’un processus d’ingénierie de sécurité incendie, résumées à la Figure 1 (extraite de l’Article 4 de l’ISO 23932-1:2018). L’ensemble comprend la série ISO 16730, la série ISO 16732, la série ISO 16733, l’ISO/TR 16738, la série ISO 24678, la série ISO 24679, l’ISO 23932-1, l’ISO/TS 29761 et d’autres documents de référence qui fournissent des exemples et des recommandations relatives à l’application de ces normes. Chaque Norme internationale se rapportant au système global d’information et d’analyse de l’ingénierie de la sécurité incendie comprend, dans son introduction, des informations permettant de relier la norme aux étapes correspondantes du processus de dimensionnement par l’ingénierie de la sécurité incendie présenté dans l’ISO 23932-1. L’ISO 23932-1 exige que les méthodes d’ingénierie soient choisies correctement pour prédire les conséquences du feu de scénarios et éléments de scénario spécifiques (ISO 23932-1:2018, Article 12). Conformément aux exigences de l’ISO 23932-1, le présent document fournit les exigences qui régissent les formules algébriques du dimensionnement de la sécurité incendie. L’étape correspondante dans le processus de dimensionnement de la sécurité incendie est indiquée par la case grise à la Figure 1 cidessous et décrite dans l’ISO 23932-1.

ISO/FDIS 24678-7:2026(fr) Figure 1 — Organigramme représentant le processus de conception par ingénierie de la sécurité incendie (ISI) (extrait de l’ISO 23932-1:2018)

PROJET FINAL Norme internationale ISO/FDIS 24678-7:2026(fr) Ingénierie de la sécurité incendie — Exigences régissant les formules algébriques — Partie 7:

Densité de flux énergétique rayonnée reçue d’un feu en nappe ouvert

1 Domaine d’application

Les exigences du présent document régissent l’application d’un ensemble de formules algébriques explicites pour le calcul de caractéristiques spécifiques de la densité de flux énergétique rayonnée provenant d’un feu en nappe.

Le présent document est une mise en application des exigences générales spécifiées dans l’ISO 16730-1 pour les calculs relatifs à la dynamique du feu impliquant un ensemble de formules algébriques explicites. Le présent document est organisé sous la forme d’un modèle dans lequel les informations spécifiques relatives aux formules algébriques sont fournies pour satisfaire aux types suivants d’exigences générales:

a) description des phénomènes physiques abordés par la méthode de calcul; b) documentation du mode opératoire de calcul et de sa base scientifique; c) limites de la méthode de calcul; d) paramètres d’entrée de la méthode de calcul; et e) domaine d’application de la méthode de calcul.

Des exemples d’ensembles de formules algébriques satisfaisant aux exigences du présent document sont fournis dans l’Annexe A et l’Annexe B. L’Annexe A contient un ensemble de formules algébriques portant sur les densités de flux énergétiques rayonnées provenant d’un feu en nappe ouvert circulaire ou quasi circulaire. L’Annexe B contient des formules pour les facteurs de configuration d’une flamme par rapport à une cible.

2 Références normatives

Les documents suivants sont cités dans le texte de sorte qu’ils constituent, pour tout ou partie de leur contenu, des exigences du présent document. Pour les références datées, seule l’édition citée s’applique. Pour les références non datées, la dernière édition du document de référence s’applique (y compris les éventuels amendements).

ISO 13943, Sécurité au feu — Vocabulaire ISO 16733-1, Ingénierie de la sécurité incendie — Sélection de scénarios d'incendie et de feux de dimensionnement - Partie 1: Sélection de scénarios d'incendie de dimensionnement ISO 24678-1, Ingénierie de la sécurité incendie — Exigences régissant les formules algébriques — Partie 1:

Exigences générales

ISO/FDIS 24678-7:2026(fr)

3 Termes et définitions

Pour les besoins du présent document, les termes et les définitions de l’ISO 13943 ainsi que les suivants s’appliquent.

L’ISO et l’IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation, consultables aux adresses suivantes:

  • ISO Online browsing platform: disponible à l’adresse https:// www .iso .org/ obp
  • IEC Electropedia: disponible à l’adresse https:// www .electropedia .org/

3.1 feu en nappe

combustion d’un carburant combustible horizontal et orienté vers le haut composé de liquides, de gaz liquéfiés ou de matières plastiques en fusion placées horizontalement

3.2 feu en nappe ouvert

feu en nappe (3.1) en plein air ou dans un espace très grand par rapport à la taille du feu, où l’effet confiné de l’environnement bâti sur le comportement de sa flamme est négligeable Note 1 à l'article: Les caractéristiques du feu en nappe ouvert dépendent des conditions extérieures comme le vent.

3.3 feu en nappe circulaire

feu en nappe quasi circulaire feu en nappe (3.1) dont la géométrie peut être assimilée à une forme circulaire Note 1 à l'article: Dans le cas d’une nappe allongée, cette assimilation est valide si le rapport entre la dimension la plus [6] longue et la dimension la plus courte ne dépasse pas 2 à 3 .

3.4 diamètre équivalent

diamètre d’une nappe circulaire dont la surface plane est équivalente aux nappes de forme rectangulaire ou irrégulière

3.5 coefficient d’absorption

fraction d’intensité du rayonnement absorbé par unité de longueur de la trajectoire de rayonnement

3.6 fraction radiative

rapport entre le taux de dégagement thermique radiatif et le débit calorifique total

3.7 hauteur moyenne de la flamme

moyenne temporelle de la hauteur des flammes au-dessus de la base d’un feu, définie comme l’élévation où la probabilité de trouver des flammes est de 50 %

3.8 transmissivité atmosphérique

rapport entre l’intensité du rayonnement transmise après avoir traversé une longueur unitaire d’un fluide présent (dioxyde de carbone, vapeur d’eau, poussière et brouillard) et l’intensité du rayonnement qui aurait parcouru la même distance dans de l’air propre

4 Exigences régissant la description des phénomènes physiques

4.1 Les exigences régissant la description des phénomènes physiques spécifiées dans l’Article 4 de l’ISO 24678-1 s’appliquent, en complément des exigences spécifiées dans les paragraphes suivants.

ISO/FDIS 24678-7:2026(fr) 4.2 La densité de flux énergétique rayonnée provenant d’un feu en nappe ouvert est un phénomène thermophysique et chimique complexe qui peut être très transitoire ou de régime permanent. La densité de flux énergétique rayonnée dépend des propriétés et de la géométrie du combustible et de l’environnement entre la source de rayonnement et la “cible” qui reçoit la densité de flux énergétique. Les propriétés de la cible doivent être prises en considération lorsque des calculs supplémentaires du comportement de la cible sont évalués, par exemple les blessures subies par les personnes, le dysfonctionnement/les dommages sur une partie de l’équipement, l’allumage d’un matériau combustible, les détériorations d’éléments structurels. Les phénomènes physiques décrits dans le présent document concernent uniquement les calculs de la densité de flux énergétique rayonnée provenant d’un feu en nappe ouvert et reçue par une cible. 4.3 Différents types de sources de feux en nappe, la géométrie de la nappe et les positions relatives des cibles examinées (y compris la position des écrans antirayonnements placés entre la nappe et les cibles) doivent être décrits à l’aide de diagrammes.

4.4 Les éléments de scénario, conformément à l’ISO 16733-1, auxquels s’appliquent les formules spécifiques, doivent être clairement identifiés. Les caractéristiques de la densité de flux énergétique rayonnée à calculer ainsi que leurs plages utiles doivent être clairement identifiées, y compris les caractéristiques présumées par association avec des grandeurs calculées, si applicable.

4.5 Les phénomènes physiques (par exemple la formation d’une nappe pendant un dégagement continu, l’interaction entre le feu et les matériaux extincteurs) auxquels des formules spécifiques s’appliquent doivent être clairement identifiés.

4.6 Étant donné que différentes formules décrivent différentes caractéristiques des flammes radiatives de la source de la nappe (voir 4.3) ou s’appliquent à différents scénarios (voir 4.4), il doit être démontré que si plusieurs méthodes permettent de calculer une grandeur donnée, des recommandations doivent être données pour choisir les méthodes appropriées.

4.7 L’émission radiative de la flamme est affectée par divers facteurs. Les incertitudes sur le pouvoir émissif doivent être prises en compte de manière appropriée. Une analyse de sensibilité ou des estimations prudentes sont souhaitables. L’analyse de sensibilité est utilisée pour identifier les variables d’entrée qui entraînent la plus grande variation des résultats de sortie. Par exemple, une analyse de sensibilité peut être réalisée sur la valeur de la fraction radiative pour évaluer si une petite variation peut avoir un impact significatif sur la densité de flux énergétique rayonnée. Si tel est le cas, il convient d’utiliser la fraction radiative avec précaution. L’utilisation d’hypothèses prudentes peut limiter l’impact des incertitudes sur les résultats finaux. Des facteurs et/ou des marges de sécurité peuvent être appliqués aux données d’entrée ou de sortie. Les facteurs et marges de sécurité appropriés sont généralement dérivés des références sur la [4,7] validation et la vérification du modèle .

5 Exigences régissant le processus de calcul

Les exigences spécifiées dans l’Article 5 de l’ISO 246781:2019 régissant le processus de calcul s’appliquent.

6 Exigences régissant les limites

Les exigences spécifiées dans l’Article 6 de l’ISO 24678-1:2019 régissant les limites s’appliquent.

7 Exigences régissant les paramètres d’entrée

Les exigences spécifiées dans l’Article 7 de l’ISO 24678-1:2019 régissant les paramètres d’entrée s’appliquent.

8 Exigences régissant le domaine d’application

Les exigences spécifiées dans l’Article 8 de l’ISO 24678-1:2019 régissant le domaine d’application s’appliquent.

ISO/FDIS 24678-7:2026(fr)

9 Exemple de documentation

Un exemple d’ensembles de formules algébriques satisfaisant aux exigences des Articles 4 à 8 est fourni dans l’Annexe A.

ISO/FDIS 24678-7:2026(fr)

Annexe A

(informative)

Formules algébriques pour le rayonnement thermique d’un feu en nappe ouvert circulaire ou quasi circulaire A.1 Symboles et abréviations utilisés dans la présente annexe

A surface plane d’une source de feu en nappe (m ) s D diamètre équivalent d’une source de feu en nappe (m)

E pouvoir émissif d’une flamme (kW/m ) f

E pouvoir émissif de la région lumineuse d’une flamme (kW/m ) max

E pouvoir émissif de la fumée (kW/m ) s f facteur de configuration d’une surface latérale d’un cylindre vertical par rapport à une cible vercyl-v ticale (−) F facteur de configuration d’une flamme par rapport à une cible (−)

F facteur de configuration d’une flamme par rapport à une cible verticale (−) 12,v

g accélération de la gravité (9,81 m/s ) H distance verticale entre la base de la flamme et une cible (m) −1 k coefficient d’absorption de rayonnement d’une flamme pour différents combustibles (m ) L hauteur moyenne de la flamme (m)

m" vitesse massique de brûlage par unité de surface d’une nappe (kg/m ·s)

vitesse massique de brûlage par unité de surface d’une nappe suffisamment grande (kg/m ·s)

m

m* vitesse de brûlage non dimensionnelle (−)

q″ densité de flux énergétique rayonnée vers une cible (kW/m )

débit calorifique d’un feu en nappe (kW) Q u vitesse du vent (m/s) w u* vitesse du vent non dimensionnelle X distance horizontale par rapport à une cible à partir du centre d’une flamme (m) β coefficient d’absorption de rayonnement d’une flamme en prenant le diamètre comme longueur −1 caractéristique (m ) χ fraction radiative (−) r Γ chaleur de la combustion du combustible (J/kg)

ISO/FDIS 24678-7:2026(fr) θ angle d’inclinaison de la flamme (rad)

ρ densité de l’air ambiant normal (1,2 kg/m ) a τ transmissivité atmosphérique (−) A.2 Description des phénomènes physiques abordés par l’ensemble de formules algébriques A.2.1 Généralités Les formules décrites dans la présente annexe fournissent des densités de flux énergétique rayonnées depuis un feu en nappe vers une cible et peuvent être applicables à différents emplacements et orientations. L’ensemble de formules est particulièrement pratique pour les cibles orientées à la verticale et à l’horizontale. Les formules présentées ici ont été validées avec des feux d’hydrocarbures liquides produisant beaucoup de suie.

A.2.2 Description générale de la méthode de calcul L’estimation de la densité de flux énergétique rayonnée reçue par une cible et provenant d’un feu en nappe implique les trois étapes suivantes:

  • détermination des caractéristiques du feu en nappe (surface en combustion, vitesse massique de brûlage, durée du feu, durée jusqu’aux conditions de régime permanent, etc.);
  • détermination des caractéristiques de rayonnement thermique du feu en nappe (hauteur de la flamme, inclinaison de la flamme, pouvoir émissif de la flamme, etc.);
  • calcul de la densité de flux énergétique rayonnée reçue par une cible (facteur de configuration d’une flamme par rapport à une cible, transmissivité atmosphérique le long de la trajectoire du rayonnement). Il est très important d’utiliser une seule méthode pour les trois étapes de ce processus. Les méthodes présentées dans la présente annexe forment des méthodes complètes et ses parties ne peuvent pas être modifiées. La validation du modèle complet doit être considérée, et non pas chaque composant individuellement.

A.2.3 Éléments de scénario auxquels l’ensemble de formules est applicable L’ensemble de formules est applicable au rayonnement thermique qui émane de flammes de feux en nappe de régime permanent et qui sont quasi circulaires ou rectangulaires dans une surface vue en plan dans un environnement non obstrué, sauf si indication contraire.

A.2.4 Cohérence intrinsèque de l’ensemble de formules L’ensemble de formules fourni dans la présente annexe a été dérivé et révisé afin de garantir que les résultats des calculs de différentes formules de l’ensemble sont cohérents (c’est-à-dire qu’ils ne forment pas de conflits).

A.2.5 Normes et autres documents dans lesquels l’ensemble de formules est utilisé Aucun spécifié.

ISO/FDIS 24678-7:2026(fr) A.3 Documentation de l’ensemble de formules A.3.1 Généralités Comme représenté à la Figure A.1, le rayonnement est émis par une flamme et reçu par une cible. La densité de flux énergétique provenant d’un feu en nappe et reçue par une cible peut être calculée à l’aide de la Formule (A.1):

qE  F (A.1) f12 Légende 1 flamme (surface 1) 2 cible (surface 2) 3 émissions (dans toutes les directions) 4 densité de flux énergétique rayonnée vers une cible Figure A.1 — Rayonnement d’une flamme vers une cible La Figure A.2 décrit les étapes successives nécessaires pour estimer la densité de flux énergétique rayonnée provenant d’un feu en nappe et reçue par une cible. Le débit calorifique et le diamètre de la nappe, s’il n’est pas indiqué, sont estimés à partir des caractéristiques spécifiques de l’objet qui brûle. Le pouvoir émissif émanant de la surface de la flamme est présumé être une fonction du diamètre de la nappe. La géométrie de la flamme est calculée en utilisant le débit calorifique et le diamètre de la source du feu. Enfin, le facteur de configuration d’une flamme par rapport à une cible est calculé. L’effet de blocage par une substance présente, par exemple de la suie, de la vapeur d’eau et des gaz dipolaires, est considéré comme transmissivité atmosphérique quand cela est nécessaire.

...