oSIST prEN IEC 62053-22:2026
(Main)Electricity metering equipment - Particular requirements - Part 22: Static meters for AC active energy (classes 0,1S, 0,2S and 0,5S)
- Status
- Not Published
- Public Enquiry End Date
- 30-Jul-2026
- Technical Committee
- MEE - Equipment for electrical energy measurement and load control
- Current Stage
- 4020 - Public enquire (PE) (Adopted Project)
- Start Date
- 11-Jun-2026
- Due Date
- 29-Oct-2026
- Completion Date
- 03-Aug-2026
oSIST prEN IEC 62053-22:2026 is the Slovene standard published by SIST that corresponds to prEN IEC 62053-22:2026 from IEC. It specifies particular requirements for transformer-operated or transducer-operated static meters for alternating current (AC) active energy in 50 Hz or 60 Hz networks, for accuracy classes 0,1S, 0,2S and 0,5S. It is written for type testing, so manufacturers, test laboratories and purchasers can use it to check meter performance and suitability.
What does oSIST prEN IEC 62053-22:2026 specify?
oSIST prEN IEC 62053-22:2026 sets the particular requirements for static watt-hour meters used to measure AC active energy, and it applies only to type tests. The document is organized into Clauses 1 to 10, followed by Annex A.
The standard covers meters intended for networks up to 1 000 V AC, with all functional elements enclosed in one meter case except the indicating display. It also allows integrated or detached displays, installation in a matching socket or rack, and optional extra functions.
It applies to meters designed for external transducers in two ways:
- as directly connected meters, when the meter and transducers are tested together
- as transducer-operated meters, when the meter is tested without the transducers
The scope excludes portable meters, rolling stock, vehicles, ships and airplanes, laboratory and meter test equipment, reference standard meters, remote multi-device systems, and meters above the stated voltage range. It also leaves out tampering detection and prevention requirements.
What are the key requirements of oSIST prEN IEC 62053-22:2026?
Meter ratings, currents and construction
oSIST prEN IEC 62053-22:2026 uses the electrical values from IEC 62052-11 for voltage and frequency, and it adds the current-related signals needed for this part. Clause 4 is important because it fixes the operating points that laboratories and product designers must use when checking meter behavior.
For currents, the document introduces the starting, minimum, transitional and maximum current signals for both transformer-operated and transducer-operated meters. In practice, this means a meter has to work not only at its normal current range but also at the low-current and high-current points used for registration and accuracy testing.
Clauses 5 and 6 defer construction requirements, marking and documentation to IEC 62052-11. That keeps the basic meter design, nameplate and user information aligned with the general metering standard, while this part focuses on the accuracy and influence tests.
Accuracy at reference conditions
Clause 7.9 sets the relative error limits at reference conditions for the three accuracy classes. The limits apply to single-phase meters and to poly-phase meters under balanced loads or single-phase loads, so test engineers must choose the loading arrangement carefully.
If a meter measures energy in both directions, the class limits apply in each direction. If a meter has multiple connection modes, the accuracy result is valid only for the connection modes actually tested, so a manufacturer cannot transfer one tested mode to an untested one.
Clause 7.5 to 7.8 cover initial start-up, no-load, starting current and repeatability tests. These checks matter because they show whether the meter starts, remains stable at low load, and repeats its result when the same test is run again.
Influence quantities and environmental stress
Clause 7.10 gives the limits for error shift caused by influence quantities. The tests cover electromagnetic and electrical disturbances, harmonic and waveform effects, voltage and frequency variation, auxiliary supply effects, self-heating, fast load changes, earth fault, and climatic exposure.
The document says the tests for influence quantities should be performed in one connection mode that exercises the meter’s full metrological capability. For a laboratory, that means choosing the most demanding practical wiring arrangement rather than testing every possible mode separately.
Clause 8 covers climatic requirements, and Clause 9 covers the effects of external influences. For tests with acceptance criterion A, Clause 9 points back to Table 6 in this document, so the special limits here govern the external-influence checks for this meter family.
Type testing and precedence over the base standard
Clause 10 applies the type-test requirements from IEC 62052-11. This confirms that oSIST prEN IEC 62053-22:2026 is a product standard for verification of meter types, not a field-installation or acceptance-inspection rule.
Where this document sets a requirement that overlaps with IEC 62052-11 or IEC 62052-31, the requirement in this part takes precedence. That matters in procurement and certification because the specific AC active-energy rules here override the more general meter rules where they differ.
What terms does oSIST prEN IEC 62053-22:2026 define?
oSIST prEN IEC 62053-22:2026 uses the terms and definitions from IEC 62052-11, so the wording is aligned with the general metering standard. The key terms in this part are the ones that control how the meter is rated and tested.
- Static meter - A meter with electronic measurement functions, used here for AC active energy.
- Transformer-operated meter - A meter intended to work with instrument transformers rather than direct connection.
- Transducer-operated meter - A meter intended to work with external transducers; this part allows it to be tested without the transducers.
- Starting current signal - The low current point used to check when the meter begins to register energy.
- Minimum current signal - The low current level used in the accuracy checks.
- Transitional current signal - The current level introduced in this edition that separates low-current behavior from higher-current behavior.
- Maximum current signal - The upper current level used to check metering performance at high load.
- Relative error - The difference between the meter result and the reference result, used throughout the accuracy tables.
Who uses oSIST prEN IEC 62053-22:2026?
This standard is used by meter manufacturers, design engineers, test laboratories, conformity assessment bodies and purchasers of electricity metering equipment. It is especially relevant to people who specify or verify static meters for billing and energy measurement in AC networks.
Utilities and system integrators can use it when selecting meters for installations that require defined accuracy classes and type-tested performance. Quality managers use it to plan product verification, document test evidence and check whether a meter type matches the intended connection mode and operating range.
What changed in oSIST prEN IEC 62053-22:2026 from the previous edition?
oSIST prEN IEC 62053-22:2026 is the third edition and replaces the second edition published in 2020. The document states these significant technical changes:
- normative references were updated
- transducer-operated meters were added to the scope, when tested without transducers
- the transitional current was introduced
- the starting, minimum and maximum current signals were expressed as fractions of the transitional current
- a ripple on DC supply voltage test was introduced
- the figures in Annex A were revised
Which standards are used with oSIST prEN IEC 62053-22:2026?
| Standard | What it contributes |
|---|---|
| IEC 62052-11 edition 2 CDV:2026 | General meter requirements, test conditions, terms and the main test framework used throughout this part |
| IEC 62052-31:2024 | Product safety requirements and tests for metering equipment |
| IEC 62052-41:2022 | Energy registration methods and requirements for multi-energy and multi-rate meters |
| IEC 62053-21 edition 3 CDV:2026 | Static meters for AC active energy of classes 0,5, 1 and 2 |
| IEC 62053-23 edition 3 CDV:2026 | Static meters for reactive energy of classes 2 and 3 |
| IEC 62053-24 edition 3 CDV:2026 | Static meters for fundamental component reactive energy |
| IEC 62053-41:2021 | Static meters for DC energy |
| IEC 62055-31:2022 | Static payment meters for active energy |
| IEC 62057-1:2023 | Stationary meter test units and test equipment |
| IEC 62057-3:2024 | Automatic meter testing systems |
| IEC 62058-11:2008 | General AC acceptance inspection methods |
| IEC 62058-31:2008 | Particular acceptance inspection requirements for static active-energy meters |
| IEC TR 62059-11:2002 | General dependability concepts |
| IEC TR 62059-21:2002 | Collection of meter dependability data from the field |
| IEC 62059-32-1:2011 | Stability testing of metrological characteristics by elevated temperature |
What does the oSIST prEN IEC 62053-22:2026 document contain?
The document contains the core test and requirement structure for type testing these meters: electrical values, construction requirements, marking and documentation, accuracy requirements, climatic requirements and external-influence tests. It also includes Tables 1 to 6, which set the current signal definitions and the error-limit framework used in testing.
Annex A provides a comparison of relative error limits at reference conditions for the three accuracy classes, with figures for different power factor and current conditions. In practice, this helps engineers and buyers compare how the classes behave across the range of intended test conditions without reading multiple separate standards.
Relations
- Effective Date
- 08-Apr-2025
- Effective Date
- 08-Apr-2025
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

Aboma Certification B.V.
Specialized in construction, metal, and transport sectors.
Sponsored listings
Frequently Asked Questions
oSIST prEN IEC 62053-22:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Electricity metering equipment - Particular requirements - Part 22: Static meters for AC active energy (classes 0,1S, 0,2S and 0,5S)". This standard covers: Electricity metering equipment - Particular requirements - Part 22: Static meters for AC active energy (classes 0,1S, 0,2S and 0,5S)
Electricity metering equipment - Particular requirements - Part 22: Static meters for AC active energy (classes 0,1S, 0,2S and 0,5S)
oSIST prEN IEC 62053-22:2026 is classified under the following ICS (International Classification for Standards) categories: 17.220.20 - Measurement of electrical and magnetic quantities; 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
oSIST prEN IEC 62053-22:2026 has the following relationships with other standards: It is inter standard links to SIST EN IEC 62053-22:2021, SIST EN IEC 62053-22:2021/A11:2021. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
oSIST prEN IEC 62053-22:2026 is associated with the following European legislation: EU Directives/Regulations: 2014/30/EU; Standardization Mandates: M/441, M/552. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
oSIST prEN IEC 62053-22:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 Standard electrical values
- 4.1 Voltages
- 4.2 Currents
- 4.3 Frequencies
- 4.4 Power consumption
- 5 Construction requirements
- 6 Meter marking and documentation
- 7 Accuracy requirements
- 7.1 General test conditions
- 7.2 Methods of accuracy verification
- 7.3 Measurement uncertainty
- 7.4 Meter constant
- 7.5 Initial start-up of the meter
- 7.6 Test of no-load condition
- 7.7 Starting current test
- 7.8 Repeatability test
- 7.9 Limits of error due to variation of the current signal
- 7.10 Limits of error shift due to influence quantities
- 2 I ≤ I ≤ I
- 7.11 Time-keeping accuracy
- 8 Climatic requirements
- 9 The effects of external influences
- 10 Type test
- Annex A
- Bibliography
INTRODUCTION This part of IEC 62053 is to be used with relevant parts of the IEC 62052, IEC 62058 and IEC 62059 series, Electricity metering equipment, with the IEC 62055 series, Electricity metering – Payment systems and with the IEC 62057 series, Electrical energy meters:
IEC 62052-11 edition 2 CDV:2026 , Electricity metering equipment – General requirements, tests and test conditions – Part 11: Metering equipment IEC 62052-31:2024, Electricity metering equipment – General requirements, tests and test conditions – Part 31: Product safety requirements and tests IEC 62052-41:2022, Electricity metering equipment – General requirements, tests and test conditions – Part 41: Energy registration methods and requirements for multi-energy and multirate meters IEC 62053-21 edition 3 CDV :2026, Electricity metering equipment – Particular requirements – Part 21: Static meters for AC active energy (classes 0,5, 1 and 2) IEC 62053-23 edition 3 CDV :2026, Electricity metering equipment – Particular requirements – Part 23: Static meters for reactive energy (classes 2 and 3) IEC 62053-24 edition 3 CDV :2026, Electricity metering equipment – Particular requirements – Part 24: Static meters for fundamental component reactive energy (classes 0,5 S, 1 S, 1, 2 and 3) IEC 62053-41:2021, Electricity metering equipment – Particular requirements – Part 41: Static meters for DC energy (classes 0,5 and 1) IEC 62055-31:2022, Electricity metering – Payment systems – Part 31: Particular requirements - Static payment meters for active energy (classes 1 and 2) IEC 62057-1:2023, Electrical energy meters – Test equipment, techniques and procedures – Part 1: Stationary meter test units (MTUs) IEC 62057-3:2024, Electrical energy meters – Test equipment, techniques and procedures – Part 3: Automatic meter testing system (AMTS) IEC 62058-11:2008, Electricity metering equipment (AC) – Acceptance inspection – Part 11:
General acceptance inspection methods IEC 62058-31:2008, Electricity metering equipment (AC) – Acceptance inspection – Part 31:
Particular requirements for static meters for active energy (classes 0,2 S, 0,5 S, 1 and 2) IEC TR 62059-11:2002, Electricity metering equipment – Dependability – Part 11: General concepts IEC TR 62059-21:2002, Electricity metering equipment – Dependability – Part 21: Collection of meter dependability data from the field IEC 62059-32-1:2011, Electricity metering equipment – Dependability – Part 32-1: Durability – Testing of the stability of metrological characteristics by applying elevated temperature This part is a standard for type testing electricity meters. It covers the particular requirements for meters, being used indoors and outdoors in large quantities worldwide. It does not deal with special implementations (such as metering-part and/or displays in separate housings).
oSIST prEN IEC 62053-22:2026
This document is intended to be used in conjunction with IEC 62052-11 edition 2 CDV:2026 and with IEC 62052-31:2024. When any requirement in this document concerns an item already covered in IEC 62052-11 edition 2 CDV:2026 or in IEC 62052-31:2024, the requirements of this document take precedence over the requirements of IEC 62052-11 edition 2 CDV:2026 or of IEC 62052-31:2024.
The specifications and test levels in this document are regarded as minimum values for the proper functioning of electricity measurement and load control equipment under normal working conditions. For special applications, additional or extended specificat ions or test levels might be necessary and are permitted but are neither identified nor prescribed in this document.
oSIST prEN IEC 62053-22:2026
1 Scope
This part of IEC 62053 applies only to transformer-operated or transducer-operated static watthour meters of accuracy classes 0,1 S, 0,2 S and 0,5 S for the measurement of alternating current electrical active energy in 50 Hz or 60 Hz networks and it applies to their type tests only.
NOTE 1 For other general requirements, such as safety, dependability, etc., see the relevant standards in the IEC 62052 or IEC 62059 series.
This document applies to electricity metering equipment designed to:
- measure and control electrical energy on electrical networks (mains) with voltage up to 1 000 V AC; NOTE 2 For AC electricity meters, the voltage mentioned above is the line-to-neutral voltage derived from nominal voltages. See IEC 62052-31:2024, Table 7.
- have all functional elements, including add-on modules, enclosed in, or forming a single meter case with exception of indicating displays;
- operate with integrated or detached indicating displays, or without an indicating display;
- be installed in a specified matching socket or rack;
- optionally, provide additional functions other than those for measurement of electrical energy.
Meters designed for operation with external transducers may be tested for compliance with this document:
- as directly connected meters, when such meters and their transducers are tested together; - as transducer-operated meters when such meters are tested without transducers. NOTE 3 When transducer-operated meters are tested without transducers, the reference measurements may be performed at the input terminals of the meter. This may require, for example, a traceable reference standard meter (standard, French: étalon) with inputs compatible with mV or mA level transducer output signals. Another practical way to test transducer-operated meters is to perform the reference measurement at the input terminals of calibrated reference transducers. This way, the reference standard meters, and test current sources may be the same as those used for testing of transformer-operated meters. The transformation ratio, metrological characteristics and uncertainty of the reference transducers are known and their influence can be removed by post -processing the test data. The determination of the appropriate test methodology is left to the expertise of the testing laboratory. NOTE 4 Modern electricity meters typically contain additional functions such as measurement of voltage magnitude, current magnitude, power, frequency, power factor, etc.; measurement of power quality parameters; load control functions; delivery, time, test, accounting, recording functions; data communication interfaces and associated data security functions. The relevant standards for these functions may apply in addition to the requirements of this document. However, the requirements for such functions are outside the scope of this document. NOTE 5 Product requirements for power metering and monitoring devices (PMDs) and measurement functions such as voltage magnitude, current magnitude, power, frequency, etc., are covered in IEC 61557-12. However, devices compliant with IEC 61557-12 are not intended to be used as billing meters unless they are also compliant with IEC 62052-11 edition 2 CDV:2026 and one or more relevant IEC 62053-xx accuracy class standards. NOTE 6 Product requirements for power quality instruments (PQIs) are covered in IEC 62586-1. Requirements for power quality measurement techniques (functions) are covered in IEC 61000-4-30. Requirements for testing of the power quality measurement functions are covered in IEC 62586-2. This document does not apply to:
- meters for which the voltage line-to-neutral derived from nominal voltages exceeds 1 000 V AC; - metering systems comprising multiple devices (except transducers) physically remote from one another; - portable meters; NOTE 7 Portable meters are meters that are not permanently connected. - meters used in rolling stock, vehicles, ships and airplanes;
oSIST prEN IEC 62053-22:2026
...