Fixed firefighting systems - Components for sprinkler and water spray systems - Part 12: Pumps

This part of the EN 12259 series specifies requirements for single stage and multi-stage centrifugal pumps with mechanical seal or soft packing for use in automatic sprinkler systems and is for use with EN 12845 and EN 17451.
This document is only applicable for the following pumps, independent of installed orientation (vertical, horizontal or sloped):
- end suction pumps (close coupled or long coupled) of the back pull-out type pump;
- axial horizontal split case pumps;
- ring section pumps;
- inline pumps (vertical line shaft pump with inlet and outlet in line);
- vertical turbine pumps;
- multistage inline pumps;
- multi stage-multi outlet pumps;
- submersible motor borehole pumps.

Ortsfeste Brandbekämpfungsanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 12: Sprinklerpumpen

Dieser Teil der Normenreihe EN 12259 legt Anforderungen an einstufige und mehrstufige Kreiselpumpen mit mechanischer Dichtung oder Weichstoffdichtung für den Einsatz in automatischen Sprinkleranlagen fest und ist für die Verwendung mit EN 12845 und EN 17451 bestimmt.
Dieses Dokument ist ausschließlich für die folgenden Pumpen anwendbar, unabhängig von der Einbau-ausrichtung (vertikal, horizontal oder geneigt):
- Pumpen mit axialem Eintritt (Blockausführung oder Grundplattenausführung) der Pumpe in Prozess-bauweise;
- längs geteilte Axial Gehäusepumpen;-
- Gliederpumpen;
- Reihenpumpen (Vertikalwellenpumpe mit Einlass und Auslass in Reihe);
- vertikale Turbinenpumpen;
- mehrstufige Reihenpumpen;
- mehrstufige Pumpen mit mehreren Ausgängen;
- Motortauchpumpen.

Installations fixes de lutte contre l'incendie - Composants des systèmes d'extinction du type sprinkleur et à pulvérisation d'eau - Partie 12 : Pompes

La présente partie de la série EN 12259 spécifie les exigences relatives aux pompes monocellulaires et multicellulaires à garnitures mécaniques d’étanchéité ou à tresses, destinées à être utilisées dans les systèmes d’extinction automatique du type sprinkleur et avec l’EN 12845 et l’EN 17451.
Le présent document ne s’applique qu’aux pompes suivantes, indépendamment de leur orientation d’installation (verticale, horizontale ou inclinée) :
- les pompes à aspiration axiale (à accouplement rigide ou à accouplement long) de type à démontage arrière « back pull-out » ;
- les pompes axiales à plan de joint horizontal ;
- les pompes à corps segmenté ;
- les pompes en ligne (pompe à axe vertical avec orifices d’aspiration et de refoulement en ligne) ;
- les pompes à turbine verticale ;
- les pompes multicellulaires en ligne ;
- les pompes multicellulaires à plusieurs orifices de refoulement ;
- les pompes de forage à moteur immergé.

Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s pršečo vodo – 12. del: Črpalke

General Information

Status
Not Published
Public Enquiry End Date
30-Jul-2022
Technical Committee
Current Stage
4020 - Public enquire (PE) (Adopted Project)
Start Date
15-Jun-2022
Due Date
02-Nov-2022

Buy Standard

Draft
oSIST prEN 12259-12:2022
English language
14 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
oSIST prEN 12259-12:2022
01-julij-2022
Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s
pršečo vodo – 12. del: Črpalke

Fixed firefighting systems - Components for sprinkler and water spray systems - Part 12:

Pumps

Ortsfeste Brandbekämpfungsanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen -

Teil 12: Sprinklerpumpen

Installations fixes de lutte contre l'incendie - Composants des systèmes d'extinction du

type sprinkleur et à pulvérisation d'eau - Partie 12 : Pompes
Ta slovenski standard je istoveten z: prEN 12259-12
ICS:
13.220.10 Gašenje požara Fire-fighting
oSIST prEN 12259-12:2022 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 12259-12:2022
---------------------- Page: 2 ----------------------
oSIST prEN 12259-12:2022
DRAFT
EUROPEAN STANDARD
prEN 12259-12
NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2022
ICS 13.220.20
English Version
Fixed firefighting systems - Components for sprinkler and
water spray systems - Part 12: Pumps
Ortsfeste Brandbekämpfungsanlagen - Bauteile für
Sprinkler- und Sprühwasseranlagen - Teil 12:
Sprinklerpumpen

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee

CEN/TC 191.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,

Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 12259-12:2022 E

worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 12259-12:2022
prEN 12259-12:2022 (E)
Contents Page

European foreword ............................................................................................................................................. 3

1 Scope .......................................................................................................................................................... 4

2 Normative references .......................................................................................................................... 4

3 Terms, definitions, symbols and abbreviated terms ................................................................ 4

3.1 Terms and definitions ......................................................................................................................... 4

3.2 Symbols and abbreviated terms ...................................................................................................... 5

4 Assessment methods and criteria ................................................................................................... 5

4.1 Characteristic curves, minimum flow and rotational speed tests ....................................... 5

4.1.1 Assessment method .............................................................................................................................. 5

4.1.2 Criteria for rotational speed ............................................................................................................. 6

4.1.3 Criteria for characteristic curves .................................................................................................... 6

4.2 Minimum flow ........................................................................................................................................ 7

4.2.1 Assessment method .............................................................................................................................. 7

4.2.2 Criteria ...................................................................................................................................................... 7

4.3 Pump materials ...................................................................................................................................... 7

4.3.1 Assessment method .............................................................................................................................. 7

4.3.2 Criteria ...................................................................................................................................................... 7

4.4 Pump casing strength .......................................................................................................................... 7

4.4.1 Assessment method .............................................................................................................................. 7

4.4.2 Criteria ...................................................................................................................................................... 7

4.5 Pump leakage test ................................................................................................................................. 8

4.5.1 Assessment method .............................................................................................................................. 8

4.5.2 Criteria ...................................................................................................................................................... 8

4.6 Stress calculations ................................................................................................................................ 8

4.6.1 Assessment method .............................................................................................................................. 8

4.6.2 Criteria ...................................................................................................................................................... 8

5 Marking and documentation ............................................................................................................. 8

5.1 General ...................................................................................................................................................... 8

5.2 Marking ..................................................................................................................................................... 9

5.3 Documentation ....................................................................................................................................... 9

Annex A (informative) Example pump characteristic curve sheets ..............................................11

Figure A.1 — Typical curves for constantly rising power consumption pumps (2 of 2) .........12

Figure A.2 — Typical curves for non-overloading power pumps ....................................................13

Annex B (informative) Specimen of manufacturer’s name plate ....................................................14

Figure B.1 — Example of a name plate ......................................................................................................14

---------------------- Page: 4 ----------------------
oSIST prEN 12259-12:2022
prEN 12259-12:2022 (E)
European foreword

This document (prEN 12259-12:2022) has been prepared by Technical Committee CEN/TC 191 “Fixed

fire fighting systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
---------------------- Page: 5 ----------------------
oSIST prEN 12259-12:2022
prEN 12259-12:2022 (E)
1 Scope

This part of the EN 12259 series specifies requirements for single stage and multi-stage centrifugal

pumps with mechanical seal or soft packing for use in automatic sprinkler systems and is for use with

EN 12845 and EN 17451.

This document is only applicable for the following pumps, independent of installed orientation (vertical,

horizontal or sloped):

— end suction pumps (close coupled or long coupled) of the back pull-out type pump;

— axial horizontal split case pumps;
— ring section pumps;
— inline pumps (vertical line shaft pump with inlet and outlet in line);
— vertical turbine pumps;
— multistage inline pumps;
— multi stage-multi outlet pumps;
— submersible motor borehole pumps.
2 Normative references

The following documents are referred to in the text in such a way that some or all of their content

constitutes requirements of this document. For dated references, only the edition cited applies. For

undated references, the latest edition of the referenced document (including any amendments) applies.

EN ISO 9906:2012, Rotodynamic pumps - Hydraulic performance acceptance tests - Grades 1, 2 and 3 (ISO

9906:2012)

EN 12162:2001+A1:2009, Liquid pumps - Safety requirements - Procedure for hydrostatic testing

EN 12845, Fixed firefighting systems - Automatic sprinkler systems - Design, installation and maintenance

EN ISO 17769-1, Liquid pumps and installation - General terms, definitions, quantities, letter symbols and

units - Part 1: Liquid pumps (ISO 17769-1)

ISO 3069:2000, End-suction centrifugal pumps — Dimensions of cavities for mechanical seals and for soft

packing
3 Terms, definitions, symbols and abbreviated terms
3.1 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 12845, EN ISO 17769-1 and the

following apply.

ISO and IEC maintain terminological databases for use in standardization at the following addresses:

— IEC Electropedia: available at https://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
---------------------- Page: 6 ----------------------
oSIST prEN 12259-12:2022
prEN 12259-12:2022 (E)
3.1.1
back pull-out type pump

centrifugal pump design type which allows the rotating assembly to be pulled out of the pump casing

without having to remove the pump casing from the piping
3.2 Symbols and abbreviated terms
NPSH net positive suction head
NPSHr net positive suction head required
Q rated flow of the pump when tested in accordance 4.1.1

NOTE It is determined from the flow of the pump to generate an NPSHr of 8,5 m for vertical line

shaft and submersible pumps or 5 m for all other pumps.
zero flow condition (closed valve)
maximum allowable casing working pressure
allw
4 Assessment methods and criteria
4.1 Characteristic curves, minimum flow and rotational speed tests
4.1.1 Assessment method

Pump characteristic curves shall be drawn for the rated speed condition. The highest flow to be shown in

the curves shall be sufficient to demonstrate a non-overloading power characteristic or a flow

corresponding to at least NPSHr of 16 m.

In case of non-overloading power characteristic, all curves shall be shown including values which are

minimum 15 % higher than the flow at the maximum power demand.

The flow, power consumption, NPSHr and the corresponding delivery head shall be determined in

accordance with EN ISO 9906:2012, Grade 2. The measurement uncertainty as specified in

EN ISO 9906:2012, Grade 2 shall be applied.
NOTE For examples, see Annex A.

Type tests and conversion of test data shall be undertaken using methods defined in EN ISO 9906:2012,

Grade 2 and the tolerances given there.
Where there are a range of impeller diameters, tests shall include the maxi
...

Questions, Comments and Discussion