Energy performance of lamp controlgear - Part 1: Controlgear for fluorescent lamps - Method of measurement to determine the total input power of controlgear circuits and the efficiency of the controlgear (IEC 62442-1:2018)

This part of IEC 62442 defines a measurement and calculation method of the total input
power for controlgear-lamp circuits when operating with their associated fluorescent lamp(s).
The calculation method for the efficiency of the lamp controlgear is also defined. This
document applies to electrical controlgear-lamp circuits consisting only of the controlgear and
the lamp(s). It is intended for use on DC supplies up to 1 000 V and/or AC supplies up to
1 000 V at 50 Hz or 60 Hz.
NOTE Requirements for testing individual controlgear during production are not included.
This document specifies the measurement method for the total input power and the
calculation method of the controlgear efficiency for all controlgear used for domestic and
normal commercial purposes operating with the following fluorescent lamps:
– linear fluorescent lamps;
– single-ended (compact) fluorescent lamps;
– other general purpose fluorescent lamps.
This document does not apply to:
– controlgear which form an integral part of the lamp;
– controllable wire-wound magnetic controlgear;
– luminaires, which rely on additional optical performance aspects.

Energieeffizienz von Lampenbetriebsgeräten - Teil 1: Betriebsgeräte für Leuchtstofflampen - Messverfahren zur Bestimmung der Gesamteingangsleistung von Betriebsgeräteschaltungen und des Wirkungsgrades von Betriebsgeräten (IEC 62442-1:2018)

Performance énergétique des appareillages de lampes - Partie 1: Appareillages des lampes à fluorescence - Méthode de mesure pour la détermination de la puissance d'entrée totale des circuits d'appareillage et du rendement des appareillages (IEC 62442-1:2018)

NEW!IEC 62442-1:2018 est disponible sous forme de IEC 62442-1:2018 RLV qui contient la Norme internationale et sa version Redline, illustrant les modifications du contenu technique depuis l'édition précédente.

L’IEC 62442-1:2018 définit une méthode de mesure et de calcul de la puissance d'entrée totale pour les circuits d’appareillage-lampe fonctionnant avec la ou les lampes à fluorescence qui leur sont associées. La méthode de calcul du rendement des appareillages de lampe est également définie. Le présent document s'applique aux circuits électriques d’appareillage de lampe constitués exclusivement de l'appareillage et de(s) lampe(s). Il s'applique à des alimentations en courant continu jusqu’à 1 000 V et/ou à des alimentations en courant alternatif de 1 000 V au maximum, à 50 Hz ou 60 Hz. Cette deuxième édition annule et remplace la première édition parue en 2011. Cette édition constitue une révision technique et a été harmonisée avec l’IEC 62442-2 et l’IEC 62442-3.

Energijske lastnosti krmilne naprave sijalke - 1. del: Krmilna naprava za fluorescentne sijalke - Merilna metoda za ugotavljanje celotne vhodne moči krmilnih vezij in izkoristka krmilne naprave (IEC 62442-1:2018)

Ta del standarda IEC 62442 določa metodo za meritev in izračun celotne vhodne moči krmilnih vezij sijalk, kadar delujejo s fluorescenčnimi sijalkami.  Opredeljena je tudi računska metoda za izkoristek krmilne naprave. Ta dokument se uporablja za električna krmilna vezja sijalk, ki jih sestavljajo le krmilna naprava in sijalke. Namenjen je za uporabo z enosmerno napajalno napetostjo do vključno 1000 V in/ali izmenično napajalno napetostjo do vključno 1000 V pri frekvenci 50 Hz ali 60 Hz.
OPOMBA: Zahteve za preskušanje posameznih delov krmilne opreme med proizvodnjo niso vključene.
Ta dokument določa merilno metodo za skupno vhodno moč in metodo za izračun učinkovitosti krmilnih naprav za vse krmilne naprave, ki se uporabljajo za domačo uporabo in običajne komercialne namene ter delujejo z naslednjimi fluorescentnimi sijalkami:
– linearne fluorescentne sijalke;
– fluorescentne sijalke z enojno vijačnico (kompaktne);
– ostale fluorescentne sijalke za splošne namene.
Ta dokument se ne uporablja za:
– krmilno napravo, ki je sestavni del sijalke;
– krmiljeno magnetno krmilno napravo z žičnim navitjem;
– svetilke, ki so odvisne od dodatnih vidikov optične učinkovitosti.

General Information

Status
Published
Public Enquiry End Date
31-Aug-2017
Publication Date
07-Oct-2018
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
04-Oct-2018
Due Date
09-Dec-2018
Completion Date
08-Oct-2018

Relations

Buy Standard

Standard
EN IEC 62442-1:2019
English language
23 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Amendment
EN 62442-1:2012/oprA1:2017
English language
15 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN IEC 62442-1:2019
01-januar-2019
1DGRPHãþD
SIST EN 62442-1:2012
SIST EN 62442-1:2012/A11:2018
SIST EN 62442-1:2012/AC:2012
(QHUJLMVNHODVWQRVWLNUPLOQHQDSUDYHVLMDONHGHO.UPLOQDQDSUDYD]D
IOXRUHVFHQWQHVLMDONH0HULOQDPHWRGD]DXJRWDYOMDQMHFHORWQHYKRGQHPRþL
NUPLOQLKYH]LMLQL]NRULVWNDNUPLOQHQDSUDYH ,(&
Energy performance of lamp controlgear - Part 1: Controlgear for fluorescent lamps -
Method of measurement to determine the total input power of controlgear circuits and the
efficiency of the controlgear (IEC 62442-1:2018)
Energieeffizienz von Lampenbetriebsgeräten - Teil 1: Betriebsgeräte für
Leuchtstofflampen - Messverfahren zur Bestimmung der Gesamteingangsleistung von
Betriebsgeräteschaltungen und des Wirkungsgrades von Betriebsgeräten (IEC 62442-
1:2018)
Performance énergétique des appareillages de lampes - Partie 1: Appareillages des
lampes à fluorescence - Méthode de mesure pour la détermination de la puissance
d'entrée totale des circuits d'appareillage et du rendement des appareillages (IEC 62442-
1:2018)
Ta slovenski standard je istoveten z: EN IEC 62442-1:2018
ICS:
29.140.99 Drugi standardi v zvezi z Other standards related to
žarnicami lamps
SIST EN IEC 62442-1:2019 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN IEC 62442-1:2019

---------------------- Page: 2 ----------------------

SIST EN IEC 62442-1:2019


EUROPEAN STANDARD EN IEC 62442-1

NORME EUROPÉENNE

EUROPÄISCHE NORM
September 2018
ICS 29.140.99 Supersedes EN 62442-1:2011
English Version
Energy performance of lamp controlgear - Part 1: Controlgear for
fluorescent lamps - Method of measurement to determine the
total input power of controlgear circuits and the efficiency of the
controlgear
(IEC 62442-1:2018)
Performance énergétique des appareillages de lampes - Energieeffizienz von Lampenbetriebsgeräten - Teil 1:
Partie 1: Appareillages des lampes à fluorescence - Betriebsgeräte für Leuchtstofflampen - Messverfahren zur
Méthode de mesure pour la détermination de la puissance Bestimmung der Gesamteingangsleistung von
d'entrée totale des circuits d'appareillage et du rendement Betriebsgeräteschaltungen und des Wirkungsgrades von
des appareillages Betriebsgeräten
(IEC 62442-1:2018) (IEC 62442-1:2018)
This European Standard was approved by CENELEC on 2018-10-24. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.



European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2018 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN IEC 62442-1:2018 E

---------------------- Page: 3 ----------------------

SIST EN IEC 62442-1:2019
EN IEC 62442-1:2018 (E)
European foreword
The text of document 34C/1335A/CDV, future edition 2 of IEC 62442-1, prepared by SC 34C
"Auxiliaries for lamps" of IEC/TC 34 "Lamps and related equipment" was submitted to the IEC-
CENELEC parallel vote and approved by CENELEC as EN IEC 62442-1:2018.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2019-03-28
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2021-09-28
document have to be withdrawn
This document supersedes EN 62442-1:2011.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.

Endorsement notice
The text of the International Standard IEC 62442-1:2018 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 62442-1 NOTE Harmonized as EN 62442-1
IEC 62442-3 NOTE Harmonized as EN IEC 62442-3

2

---------------------- Page: 4 ----------------------

SIST EN IEC 62442-1:2019
EN IEC 62442-1:2018 (E)
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60081 1997 Double-capped fluorescent lamps - EN 60081 1998
Performance specifications
+ A4 2010  + A4 2010
- -  + A11 2018
IEC 60901 1996 Single-capped fluorescent lamps - EN 60901 1996
Performance specifications
+ A5 2011  + A5 2012
IEC 60921 2004 Ballasts for tubular fluorescent lamps - EN 60921 2004
Performance requirements
IEC 60929 2011 AC and/or DC-supplied electronic control EN 60929 2011
gear for tubular fluorescent lamps -
Performance requirements
- -  + AC 2011
IEC 61347-2-3 -  Lamp control gear - Part 2-3: Particular EN 61347-2-3 -
requirements for a.c. and/or d.c. supplied
electronic control gear for fluorescent
lamps
IEC 61347-2-8 -  Lamp controlgear - Part 2-8: Particular EN 61347-2-8 -
requirements for ballasts for fluorescent
lamps


3

---------------------- Page: 5 ----------------------

SIST EN IEC 62442-1:2019

---------------------- Page: 6 ----------------------

SIST EN IEC 62442-1:2019



IEC 62442-1

®


Edition 2.0 2018-05




INTERNATIONAL



STANDARD




NORME



INTERNATIONALE











Energy performance of lamp controlgear –

Part 1: Controlgear for fluorescent lamps – Method of measurement to determine

the total input power of controlgear circuits and the efficiency of controlgear




Performance énergétique des appareillages de lampes –

Partie 1: Appareillages des lampes à fluorescence – Méthode de mesure pour la


détermination de la puissance d'entrée totale des circuits d'appareillage et du

rendement des appareillages












INTERNATIONAL

ELECTROTECHNICAL

COMMISSION


COMMISSION

ELECTROTECHNIQUE


INTERNATIONALE




ICS 29.140.99 ISBN 978-2-8322-5641-1



Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------

SIST EN IEC 62442-1:2019
– 2 – IEC 62442-1:2018 © IEC 2018
CONTENTS
FOREWORD . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 General . 9
4.1 Applicability . 9
4.2 Ballast lumen factor . 9
4.3 Dimmable controlgear . 10
4.4 Multi-power and/or multi-number-lamp controlgear . 10
4.5 General notes on tests . 10
4.6 Sampling of controlgear for testing . 10
4.7 Size of the test sample. 10
4.8 Conditioning of lamps . 10
4.9 Test voltages and frequencies . 10
4.10 Sensor and network connections . 11
5 Method of measurement and calculation of total input power of controlgear-lamp
circuits and the efficiency of controlgear . 11
5.1 Correction for ballast lumen factor . 11
5.2 Method of measurement . 11
5.3 Measurement and calculation of the total input power of magnetic
controlgear-lamp circuits . 12
5.4 Calculation of the efficiency of electromagnetic controlgear . 12
5.5 Measurement and calculation of the total input power of electronic
controlgear-lamp circuits . 12
5.6 Calculation of the efficiency of electronic controlgear . 13
5.7 Measuring the standby power . 13
Annex A (normative) Energy performance measurement setup . 14
A.1 Measurement setup for electromagnetic controlgear . 14
A.2 Measurement setup for electronic controlgear . 14
A.2.1 Measurement of the total input power . 14
A.2.2 Measuring method of standby power . 15
A.2.3 Light output measurement . 15
A.2.4 Distance to lamp related to lamp length: explanations . 17
Annex B (informative) Application of the reference ballast when assessing lamps in
electronic operation . 19
B.1 Calculation of the reference ballast impedance . 19
B.2 Method of adjusting the lamp power . 19
Bibliography . 20

Figure A.1 – Measurement of electromagnetic controlgear-lamp circuits . 14
Figure A.2 – Measurement of AC supplied electronic controlgear-lamp circuits . 15
Figure A.3 – Test setup for measuring standby power . 15
Figure A.4 – Side view of light output measurement system . 16
Figure A.5 – Top view of light output measurement system . 16
Figure A.6 – Configuration of lamp and photocell sensor . 18

---------------------- Page: 8 ----------------------

SIST EN IEC 62442-1:2019
IEC 62442-1:2018 © IEC 2018 – 3 –
Table 1 – Typical nominal electricity supply details for some regions . 11

---------------------- Page: 9 ----------------------

SIST EN IEC 62442-1:2019
– 4 – IEC 62442-1:2018 © IEC 2018
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

ENERGY PERFORMANCE OF LAMP CONTROLGEAR –

Part 1: Controlgear for fluorescent lamps –
Method of measurement to determine the total input power
of controlgear circuits and the efficiency of controlgear

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62442-1 has been prepared by subcommittee 34C: Auxiliaries for
lamps, of IEC technical committee 34: Lamps and related equipment.
This second edition cancels and replaces the first edition published in 2011. This edition
constitutes a technical revision and has been harmonized with IEC 62442-2 and IEC 62442-3.
The text of this International Standard is based on the following documents:
CDV Report on voting
34C/1335A/CDV 34C/1376/RVC

Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.

---------------------- Page: 10 ----------------------

SIST EN IEC 62442-1:2019
IEC 62442-1:2018 © IEC 2018 – 5 –
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 62442 series, published under the general title Energy
performance of lamp controlgear, can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

---------------------- Page: 11 ----------------------

SIST EN IEC 62442-1:2019
– 6 – IEC 62442-1:2018 © IEC 2018
ENERGY PERFORMANCE OF LAMP CONTROLGEAR –

Part 1: Controlgear for fluorescent lamps –
Method of measurement to determine the total input power
of controlgear circuits and the efficiency of controlgear



1 Scope
This part of IEC 62442 defines a measurement and calculation method of the total input
power for controlgear-lamp circuits when operating with their associated fluorescent lamp(s).
The calculation method for the efficiency of the lamp controlgear is also defined. This
document applies to electrical controlgear-lamp circuits consisting only of the controlgear and
the lamp(s). It is intended for use on DC supplies up to 1 000 V and/or AC supplies up to
1 000 V at 50 Hz or 60 Hz.
NOTE Requirements for testing individual controlgear during production are not included.
This document specifies the measurement method for the total input power and the
calculation method of the controlgear efficiency for all controlgear used for domestic and
normal commercial purposes operating with the following fluorescent lamps:
– linear fluorescent lamps;
– single-ended (compact) fluorescent lamps;
– other general purpose fluorescent lamps.
This document does not apply to:
– controlgear which form an integral part of the lamp;
– controllable wire-wound magnetic controlgear;
– luminaires, which rely on additional optical performance aspects.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC 60081:1997, Double-capped fluorescent lamps – Performance specifications
IEC 60081:1997/AMD4:2010
IEC 60901:1996, Single-capped fluorescent lamps – Performance specifications
IEC 60901:1996/AMD5:2011
IEC 60921:2004, Ballasts for tubular fluorescent lamps – Performance requirements
IEC 60929:2011, AC and/or DC-supplied electronic control gear for tubular fluorescent lamps
– Performance requirements
IEC 61347-2-3, Lamp control gear – Part 2-3: Particular requirements for AC and/or DC
supplied electronic control gear for fluorescent lamps

---------------------- Page: 12 ----------------------

SIST EN IEC 62442-1:2019
IEC 62442-1:2018 © IEC 2018 – 7 –
IEC 61347-2-8, Lamp controlgear – Part 2-8: Particular requirements for ballasts for
fluorescent lamps
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
nominal value
suitable approximate quantity value used to designate or identify a component, device or
equipment
3.2
limiting value
greatest or smallest admissible value of one of the quantities
3.3
rated value
quantity value for specified operating conditions of a component, device or equipment
Note 1 to entry: The value and conditions are specified in the relevant standard or assigned by the manufacturer
or responsible vendor.
Note 2 to entry: For the different kinds of operation, rated electrical values are given on the lamp data sheets as:
− rated electrical values under “electrical characteristics”, if the lamp is defined for 50 Hz/60 Hz operation only,
− rated electrical values under “electrical characteristics”, if the lamp is defined for high frequency (≥ 20 kHz)
operation only,
− rated electrical values and typical electrical values, if the lamp is defined simultaneously for 50 Hz/60 Hz
operation and high frequency operation
• for 50 Hz/60 Hz operation: rated electrical values under “electrical characteristics”, and
• for high frequency operation: rated electrical values under “typical lamp characteristics”.
3.4
controlgear
one or more components between the supply and one or more lamps which may serve to
transform the supply voltage, limit the current of the lamp(s) to the required value, provide
starting voltage and preheating current, prevent cold starting, correct power factor or reduce
radio interference
3.5
electromagnetic controlgear
magnetic controlgear
controlgear which, by means of inductance, or a combination of inductance and capacitance,
serves mainly to limit the current of the lamp(s) to the required value and operates the lamp(s)
at the same frequency as the supply frequency
3.6
electronic controlgear
AC invertor supplied with alternating current and/or direct current and including stabilizing
elements for starting and operating one or more tubular fluorescent lamps, generally at high
frequency

---------------------- Page: 13 ----------------------

SIST EN IEC 62442-1:2019
– 8 – IEC 62442-1:2018 © IEC 2018
3.7
fluorescent lamp
discharge lamp of the low pressure mercury type, in which most of the light is emitted by one
or several layers of phosphors excited by the ultra-violet radiation from the discharge
3.8
controlgear-lamp circuit
electrical circuit, or part thereof, normally built in a luminaire, consisting of the controlgear
and lamp(s)
3.9
reference ballast
special ballast, either inductive for lamps for operation on AC mains frequencies, or resistive
for lamps for operation on high frequency
Note 1 to entry: It is designed for the purpose of providing comparison standards for use in testing ballasts, for
the selection of reference lamps and for testing regular production lamps under standardized conditions. It is
essentially characterized by the fact that, at its rated frequency, it has a stable voltage/current ratio which is
relatively uninfluenced by variations in current, temperature and magnetic surroundings, as outlined in IEC 60929
and IEC 60921.
Note 2 to entry: Annex B provides details for calculating the reference ballast characteristics and the method of
operation with the reference ballast.
3.10
reference lamp
lamp selected for testing controlgear which, when associated with a reference controlgear,
has electrical characteristics which are close to the rated values or typical lamp
characteristics as stated in the relevant lamp standard
Note 1 to entry: For details regarding the tolerances, see Clause B.2.
3.11
lamp rated power
P
Lrated
power of a given lamp type specified by the manufacturer or the supplier, the lamp being
operated under specified conditions
Note 1 to entry: The rated power of a lamp is expressed in W.
3.12
ballast lumen factor
BLF
ratio of the light output of the reference lamp when the ballast under test is operated at its
rated voltage, compared with the light output of the same lamp operated with the appropriate
reference ballast supplied at its rated voltage and frequency
Note 1 to entry: This note applies to the French language only.
3.13
total input power
total power consumed by the controlgear-lamp (light source) circuit measured at rated input
voltage
[SOURCE: IEC 62442-1:—, 3.13, modified — "supplied to" has been replaced with
"consumed by", "(light source)" has been added and the note has been deleted.]
3.14
controlgear efficiency
η
controlgear
ratio of the output power to the lamp(s) and the total input power of the controlgear

---------------------- Page: 14 ----------------------

SIST EN IEC 62442-1:2019
IEC 62442-1:2018 © IEC 2018 – 9 –
Note 1 to entry: Detailed measurement method and conditions are given in Clause 5.
Note 2 to entry: Loads from sensors, network connections and other auxiliary are disconnected or, if not possible,
otherwise eliminated from the result.
3.15
multi-power-lamp controlgear
controlgear designed to operate one or more lamp(s) with different rated powers
3.16
multi-number-lamp controlgear
controlgear designed to operate simultaneously more than one similar lamp
3.17
standby mode
mode of the controlgear, in which the light source is switched off by a control signal, while the
controlgear remains connected to the mains supply, failed lamp(s) not included
Note 1 to entry: The ignition phase of lamp(s) is excluded from the standby mode.
Note 2 to entry: Failed lamp(s) could lead to incorrect measurements.
3.18
standby power
average power consumption of a controlgear in the standby mode
Note 1 to entry: Power supplied by controlgear to sensors, network connections and other auxiliaries is not
included in the standby power.
Note 2 to entry: Standby power is expressed in W.
4 General
4.1 Applicability
The measurement and calculation methods in this document shall only be used for
controlgear which conforms to IEC 61347-2-3 or IEC 61347-2-8.
4.2 Ballast lumen factor
For every controlgear-lamp combination submitted for the test, the ballast lumen factor shall
be measured. The ballast lumen factor is defined in 3.12.
Light
test
BLF= (1)
Light
ref
where
Light is the light output of the reference lamp connected to the reference ballast
ref
measured by photocell meter reading;
Light is the light output of the reference lamp connected to the controlgear under test
test
measured by photocell meter reading.
The ballast lumen factor shall be in the range of 0,925 to 1,075. A controlgear with a lower
ballast lumen factor is not suitable for testing. The upper limit of 1,075 may be exceeded, if
the value for maximum lamp operation current and maximum current in any lead to cathodes
comply with the rated value in IEC 60081 and IEC 60901.

---------------------- Page: 15 ----------------------

SIST EN IEC 62442-1:2019
– 10 – IEC 62442-1:2018 © IEC 2018
4.3 Dimmable controlgear
A sufficient cathode temperature shall be produced by the heating circuit at any possible
dimming position within the available dimming range of the controlgear as specified in the
relevant datasheet in IEC 60081 and IEC 60901.
Dimmable controlgear shall be measured at 100 % and 25 % lumen output of the operated
lamp(s).
4.4 Multi-power and/or multi-number-lamp controlgear
Multi-power and multi-number-lamp controlgear shall be measured with all the possible lamp
power and number of lamp combinations. The manufacturer shall declare the relevant BLF for
each combination.
4.5 General notes on tests
The measurement conditions specified in IEC 60921:2004 or IEC 60929:2011, Annex A shall
be applied, unless otherwise specified in this document.
For measurement uncertainty and traceability see ISO/IEC Guide 98-3 and IEC Guide 115.
4.6 Sampling of controlgear for testing
The requirements and tolerances specified in this document are based on the testing of a type
test sample submitted by the manufacturer for that purpose. This sample should consist of
units having characteristics typical of the manufacturer’s production and be as close to the
production centre point values as possible.
4.7 Size of the test sample
Tests are carried out with one test specimen.
4.8 Conditioning of lamps
Lamps shall be handled and stabilized as described in IEC 60081:1997 and
IEC 60081:1997/AMD4:2010, B.1.1 and in IEC 60901:1996 and IEC 60901:1996/AMD5:2011,
B.1.1.
4.9 Test voltages and frequencies
W
...

SLOVENSKI STANDARD
SIST EN 62442-1:2012/oprA1:2017
01-september-2017
(QHUJLMVNHODVWQRVWLNUPLOQHQDSUDYHVLMDONHGHO.UPLOQDQDSUDYD]D
IOXRUHVFHQWQHVLMDONH0HULOQDPHWRGD]DXJRWDYOMDQMHFHORWQHYKRGQHPRþL
NUPLOQLKYH]LMLQL]NRULVWNDNUPLOQHQDSUDYH
Energy performance of lamp controlgear - Part 1: Controlgear for fluorescent lamps -
Method of measurement to determine the total input power of controlgear circuits and the
efficiency of the controlgear
Energieeffizienz von Lampenbetriebsgeräten - Teil 1: Betriebsgeräte für
Leuchtstofflampen - Messverfahren zur Bestimmung der Gesamteingangsleistung von
Betriebsgeräteschaltungen und des Wirkungsgrades von Betriebsgeräten
Performance énergétique des appareillages de lampes - Partie 1: Appareillages des
lampes à fluorescence - Méthode de mesure pour la détermination de la puissance
d'entrée totale des circuits d'appareillage et du rendement des appareillages
Ta slovenski standard je istoveten z: EN 62442-1:2011/prA1:2017
ICS:
29.140.99 Drugi standardi v zvezi z Other standards related to
žarnicami lamps
SIST EN 62442-1:2012/oprA1:2017 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 62442-1:2012/oprA1:2017

---------------------- Page: 2 ----------------------

SIST EN 62442-1:2012/oprA1:2017
34C/1335A/CDV

COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 62442-1/AMD1 ED1
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2017-06-09 (2017-06-02) 2017-08-25
SUPERSEDES DOCUMENTS:
34C/1278/CD,34C/1329/CC

IEC SC 34C : AUXILIARIES FOR LAMPS
SECRETARIAT: SECRETARY:
United Kingdom Mr Petar Luzajic
OF INTEREST TO THE FOLLOWING COMMITTEES: PROPOSED HORIZONTAL STANDARD:


Other TC/SCs are requested to indicate their interest, if
any, in this CDV to the secretary.
FUNCTIONS CONCERNED:
EMC ENVIRONMENT QUALITY ASSURANCE SAFETY

SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.

This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.

TITLE:
Amendment 1 - Energy performance of lamp controlgear - Part 1: Controlgear for fluorescent
lamps - Method of measurement to determine the total input power of controlgear circuits and
the efficiency of the controlgear

NOTE FROM TC/SC OFFICERS:
This ‘A’ version is circulated due to missing line numbering in the French version. The English version
remains unchanged.
The closing date remains unchanged.

Copyright © 2017 International Electrotechnical Commission, IEC. All rights reserved. It is permitted to
download this electronic file, to make a copy and to print out the content for the sole purpose of preparing National
Committee positions. You may not copy or "mirror" the file or printed version of the document, o r any part of it, for
any other purpose without permission in writing from IEC.

---------------------- Page: 3 ----------------------

SIST EN 62442-1:2012/oprA1:2017
62442-1/Ed1/A1/CDV © IEC (E) 2 34C/1335A/CDV

1 ENERGY PERFORMANCE OF LAMP CONTROLGEAR –
2
3 Part 1: Controlgear for fluorescent lamps –
4 Method of measurement to determine the total input power of controlgear
5 circuits and the efficiency of the controlgear
6
7 1 Scope
8 This part of IEC 62442 defines a measurement and calculation method of the total input power
9 for controlgear ‒ lamp circuits when operating with their associated fluorescent lamp(s). The
10 calculation method for the efficiency of the lamp controlgear is also defined. This document
11 applies to electrical controlgear lamp circuits consisting only of the controlgear and the lamp(s).
12 It is intended for use on DC supplies up to 1 000 V and/or AC supplies up to 1 000 V at 50 Hz
13 or 60 Hz.
14 NOTE Requirements for testing individual controlgear during production are not included.
15 It specifies the measurement method for the total input power and the calculation method of the
16 controlgear efficiency for all controlgear used for domestic and normal commercial purposes
17 operating with the following fluorescent lamps:
18 – linear fluorescent lamps;
19 – single-ended (compact) fluorescent lamps;
20 – other general purpose fluorescent lamps.
21 This International Standard does not apply to:
22 – controlgear which form an integral part of the lamp;
23 – controllable wire-wound magnetic controlgear;
24 – luminaires, which rely on additional optical performance aspects.
25 2 Normative references
26 The following documents are referred to in the text in such a way that some or all of their
27 content constitutes requirements of this document. For dated references, only the edition cited
28 applies. For undated references, the latest edition of the referenced document (including any
29 amendments) applies.
30 IEC 60081:1997, Double-capped fluorescent lamps – Performance specifications
31 IEC 60081/AMD1:2000
32 IEC 60081/AMD2:2003
33 IEC 60081/AMD3:2005
34 IEC 60081/AMD4:2010
35 IEC 60081/AMD5:2013
36 IEC 60901:1996, Single-capped fluorescent lamps – Performance requirements
37 IEC 60901/AMD1:1997
38 IEC 60901/AMD2:2000
39 IEC 60901/AMD3:2004
40 IEC 60901/AMD4:2007
41 IEC 60901/AMD5:2011
42 IEC 60901/AMD6:2014
43 IEC 60921:2004, Ballasts for tubular fluorescent lamps – Performance requirements
44 IEC 60921/AMD1:2006

---------------------- Page: 4 ----------------------

SIST EN 62442-1:2012/oprA1:2017
62442-1/Ed1/A1/CDV © IEC (E) 3 34C/1335A/CDV

45 IEC 60929:2011, AC and/or DC-supplied electronic control gear for tubular fluorescent lamps –
46 Performance requirements
47 IEC 60929/AMD1:2015
48 IEC 61347-2-3:2011, Lamp control gear – Part 2-3: Particular requirements for AC and/or DC
49 supplied electronic control gear for fluorescent lamps
50 IEC 61347-2-3/AMD1:2016
51 IEC 61347-2-8:2000, Lamp controlgear – Part 2-8: Particular requirements for ballasts for
52 fluorescent lamps
53 IEC 61347-2-8/AMD:2006
54 ISO/IEC GUIDE 98-3:2008, Uncertainty of measurement – Part 3: Guide to the expression of
55 uncertainty in measurement (GUM: 1995)
56 IEC Guide 115:2007, Application of uncertainty of measurement to conformity assessment
57 activities in the electrotechnical sector
58 3 Terms and definitions
59 For the purposes of this document, the following terms and definitions apply.
60 3.1
61 nominal value
62 suitable approximate quantity value used to designate or identify a component, device or
63 equipment
64 3.2
65 limiting value
66 the greatest or smallest admissible value of one of the quantities
67 3.3
68 rated value
69 quantity value for specified operating conditions of a component, device or equipment
70 Note 1 to entry: The value and conditions are specified in the relevant standard or assigned by the man ufacturer
71 or responsible vendor
72 Note 2 to entry: For the different kinds of operation, rated electrical values are given on the lamp data sheets as:
73 – rated electrical values under “electrical characteristics”, if the lam p is defined for 50 Hz / 60 Hz operation only,
74 – rated electrical values under “electrical characteristics”, if the lamp is defined for high frequency ( ≥ 20 kHz)
75 operation only,
76 – rated electrical values and typical electrical values, if the lamp is defined simultaneously for 50 Hz / 60 Hz
77 operation and high frequency operation
78 − for 50 Hz / 60 Hz operation: rated electrical values under “electrical characteristics”, and
79 − for high frequency operation: rated electrical values under “typical lamp characteristics” .
80 3.4
81 controlgear
82 one or more components between the supply and one or more lamps which may serve to
83 transform the supply voltage, limit the current of the lamp(s) to the required value, provide
84 starting voltage and preheating current, prevent cold starting, correct power factor or reduce
85 radio interference
86 3.5
87 electromagnetic or magnetic controlgear
88 controlgear which by means of inductance, or a combination of inductance and capacitance,
89 serves mainly to limit the current of the lamp(s) to the required value and operates the lamp(s)
90 at the same frequency as the supply frequency

---------------------- Page: 5 ----------------------

SIST EN 62442-1:2012/oprA1:2017
62442-1/Ed1/A1/CDV © IEC (E) 4 34C/1335A/CDV

91 3.6
92 electronic controlgear
93 AC and/or DC supplied to AC invertor including stabilizing elements for starting and operating
94 one or more tubular fluorescent lamps, generally at high frequency
95 3.7
96 fluorescent lamp
97 discharge lamp of the low pressure mercury type, in which most of the light is emitted by one or
98 several layers of phosphors excited by the ultra-violet radiation from the discharge
99 3.8
100 controlgear – lamp circuit
101 electrical circuit, or part thereof, normally built in a luminaire, consisting of the controlgear and
102 lamp(s)
103 3.9
104 reference ballast
105 special ballast, either inductive for lamps for operation on AC mains frequencies, or resistive
106 for lamps for operation on high frequency
107 It is designed for the purpose of providing comparison standards for use in testing ballasts, for
108 the selection of reference lamps and for testing regular production lam ps under standardized
109 conditions. It is essentially characterized by the fact that, at its rated frequency, it has a stable
110 voltage/current ratio which is relatively uninfluenced by variations in current, temperature and
111 magnetic surroundings, as outlined in IEC 60929 and IEC 60921.
112 Note to entry: Annex B provides details of calculating the reference ballast characteristics and the method of
113 operation with the reference ballast.
114 3.10
115 reference lamp
116 lamp selected for testing controlgear which, when associated with a reference controlgear, has
117 electrical characteristics which are close to the rated values or typical lamp characteristics as
118 stated in the relevant lamp standard
119 Note to entry: For details regarding the tolerances, see Clause B.2.
120 3.11
121 rated power of a lamp
122 P
Lrated
123 power, expressed in watts, of a given lamp type specified by the manufacturer or the supplier,
124 the lamp being operated under specified conditions
125 3.12
126 ballast lumen factor
127 BLF
128 ratio of the light output of the reference lamp when the ballast under test is operated at its rated
129 voltage, compared with the light output of the same lamp operated with the appropriate
130 reference ballast supplied at its rated voltage and frequency
131 3.13
132 total input power
133 total power supplied to the controlgear – lamp circuit measured at rated input voltage
134 Note to entry: The rated power specified is related to a specific ballast lumen factor (BLF).
135 3.14
136 efficiency of the controlgear
137 η
controlgear
138 ratio of the output power to the lamp(s) and the total input power of the controlgear
139 Note 1 to entry: Detailed measurement method and conditions are given in clause 5.

---------------------- Page: 6 ----------------------

SIST EN 62442-1:2012/oprA1:2017
62442-1/Ed1/A1/CDV © IEC (E) 5 34C/1335A/CDV

140 Note 2 to entry: Loads from sensors, network connections and other auxiliary are disconnected or if not possible
141 otherwise eliminated from the result.
142 3.15
143 multi-lamp-power controlgear
144 controlgear designed to operate one or more lamp(s) with different rated powers
145 3.16
146 multi-number-lamp controlgear
147 controlgear designed to operate simultaneous more than one similar lamp
148 3.17
149 standby mode
150 mode of the controlgear, in which the light source is switched off by a control signal, while the
151 controlgear remains connected to the mains supply, failed lamp(s) not included
152 Note 1 to entry: The ignition phase of lamp(s) is excluded from the standby mode.
153 Note 2 to entry: Failed lamp(s) could lead to falsify measurement results.
154 3.18
155 standby power
156 average power consumption of a controlgear in the standby mode
157 Note 1 to entry: Power supplied by controlgear to sensors, network connections and other auxiliaries is not
158 include in the standby power.
159 Note 2 to entry: Unit: W.
160 4 General
161 4.1 Applicability
162 The measurement and calculation methods of this standard shall only be used for controlgear
163 which conforms to IEC 61347-2-3 or IEC 61347-2-8.
164 4.2 Ballast lumen factor
165 For every controlgear – lamp combination submitted for the test. The ballast lumen factor shall
166 be measured. The ballast lumen factor is defined in 3.12.
Lighttest
167 BLF  (1)
Lightref
168 where
169 Light is the light output of reference lamp connected to reference ballast measured by
ref
170 photocell meter reading;
171 Light is the light output of the reference lamp connected to the controlgear under test
test
172 measured by photocell meter reading.
173 The ballast lumen factor shall be in the range of 0,925 to 1,075. A controlgear with lower ballast
174 lumen factor is not suitable for testing. The upper limit of 1,075 may be exceeded, if the value
175 for maximum lamp operation current and maximum current in any lead to cathodes comply with
176 the rated value in IEC 60081 and IEC 60901.
177 4.3 Dimmable controlgear
178 Sufficient cathode temperature shall be produced by the heating circuit at any possible
179 dimming position within the available dimming range of the controlgear as specified by the
180 relevant datasheet in IEC 60081 and IEC 60901.

---------------------- Page: 7 ----------------------

SIST EN 62442-1:2012/oprA1:2017
62442-1/Ed1/A1/CDV © IEC (E) 6 34C/1335A/CDV

181 Dimmable controlgear shall be measured at 100 % and 25 % lumen output of the operated
182 lamp(s).
183 4.4 Multi-power and/or multi-lamp controlgear
184 Multi-power-lamp and multi-number-lamp controlgear shall be measured with all the possible
185 lamp power and number of lamp combinations. The manufacturer shall declare relevant BLF for
186 each combination.
187 4.5 General notes on test
188 The measurement conditions are specified in IEC 60921:2004 or IEC 60929:2011, Annex A
189 shall be applied, unless otherwise specified in this standard.
190 For measurement uncertainty and traceability see ISO/IEC Guide 98-3 and IEC Guide 115.
191 4.6 Sampling of controlgear for testing
192 The requirements and tolerances specified in this standard are based on the testing of a type
193 test sample submitted by the manufacturer for that purpose. This sample should consist of
194 units having characteristics typical of the manufacturer’s production and be as close to the
195 production centre point values as possible.
196 4.7 Size of the test sample
197 Tests are carried out with one test specimen.
198 4.8 Conditioning of lamps
199 Lamps shall be handled and stabilized as described in IEC 60081:1997 and
200 IEC 60081:1997/AMD4:2010, B.1.1 and in IEC 60901:1996 and IEC 60901:1996/AMD5:2011,
201 B.1.1.
202 4.9 Test voltages and frequencies
203 Where the test voltage and frequency are not defined by national or regional requirements, the
204 test voltage and the test frequency shall be the nominal voltage and the nominal frequency of
205 the country or region for which the measurement is being determined (refer to Table 1).
206

---------------------- Page: 8 ----------------------

SIST EN 62442-1:2012/oprA1:2017
62442-1/Ed1/A1/CDV © IEC (E) 7 34C/1335A/CDV

207 Table 1 – Typical nominal electricity supply details for some regions
a, c
Country or region Rated voltage and frequency
Europe 230 V, 50 Hz
North America 120 V, 277 V, 60 Hz
b
Japan 100 V, 50/60 Hz
China 220 V, 50 Hz
Australia and New Zealand 230 V, 50 Hz
a
Values are for single phase only. Some single phase supply voltages can be double the nominal voltage
above (centre transformer tap). The voltage between two phases of a three-phase system is 1,73 times single
phase values (e.g. 400 V for Europe).
b
“50 Hz” is applicable for the Eastern part and “60 Hz” for the Western part, respectively.
c
“If the manufacturer advises that for a marked voltage range a discrete value shall be used for measuremen t,
this should be observed.
208
209 4.10 Sensor and network connections
210 For the measurement of all kinds of controlgear power (also standby) the power consumed by
211 all circuits (internal or external) which not involved in power conversion for the controlgear
212 operation (e.g. co
...

Questions, Comments and Discussion