SIST EN ISO 4064-5:2015
(Main)Water meters intended for the metering of cold potable water and hot water - Part 5: Installation requirements (ISO 4064-5:2014)
Water meters intended for the metering of cold potable water and hot water - Part 5: Installation requirements (ISO 4064-5:2014)
This part of ISO 4064 applies to water meters used to meter the volume of cold potable water and hot
water flowing through a fully charged, closed conduit. These water meters incorporate devices which
indicate the integrated volume.
This part of ISO 4064 specifies criteria for the selection of single, combination and concentric water
meters, associated fittings, installation, special requirements for meters, and the first operation of new
or repaired meters to ensure accurate constant measurement and reliable reading of the meter.
In addition to meters based on mechanical principles, this part of ISO 4064 also applies to water
meters based on electrical or electronic principles, and to water meters based on mechanical principles
incorporating electronic devices, used to measure the volume of cold potable water and hot water. It also
applies to electronic ancillary devices. Ancillary devices are optional. However, national or international
regulations may make some ancillary devices mandatory in relation to the utilization of the water meter.
The recommendations of this part of ISO 4064 apply to water meters, irrespective of technology, defined
as integrating measuring instruments continuously determining the volume of water flowing through
them.
NOTE Any national regulations apply in the country of use.
Wasserzähler zum Messen von kaltem Trinkwasser und heißem Wasser - Teil 5: Einbaubedingungen (ISO 4064-5:2014)
Der vorliegende Teil der ISO 4064 gilt für Wasserzähler zur Volumenmessung von kaltem Trinkwasser und
heißem Wasser, das durch eine vollständig gefüllte, geschlossene Leitung fließt. Diese Wasserzähler müssen
mit Einrichtungen versehen sein, die das summierte Volumen anzeigen.
Der vorliegende Teil der ISO 4064 legt Kriterien für die Auswahl von einzelnen Wasserzählern, Verbundzählern
und konzentrischen Wasserzählern, zugehörigen Armaturen, den Einbau, besondere Anforderungen
an Zähler und die Inbetriebnahme von neuen oder reparierten Zählern fest, um eine genaue konstante
Messung und zuverlässige Ablesung der Zähler zu gewährleisten.
Der vorliegende Teil der ISO 4064 gilt ebenfalls für Wasserzähler nach elektrischem oder elektronischem
Funktionsprinzip und für Wasserzähler nach mechanischem Funktionsprinzip mit elektronischen Einrichtungen,
die zur Messung des Durchflussvolumens von heißem Wasser und von kaltem Trinkwasser dienen.
Er gilt außerdem für elektronische Zusatzeinrichtungen. Zusatzeinrichtungen sind grundsätzlich optional.
ANMERKUNG In nationalen oder internationalen Vorschriften können jedoch einige Zusatzeinrichtungen hinsichtlich
der Verwendung von Wasserzählern verbindlich vorgeschrieben sein.
Die Empfehlungen dieses Teils der ISO 4064 gelten für Wasserzähler unabhängig von der Technologie, die
als eingebaute Messgeräte fortlaufend das Volumen des sie durchlaufenden Wassers bestimmen.
ANMERKUNG Es wird auf die Tatsache hingewiesen, dass im Anwendungsland nationale Gesetzgebung gelten kann,
die Vorrang vor den Vorschriften der vorliegenden Norm hat.
Compteurs d'eau destinés au mesurage de l'eau potable froide et chaude - Partie 5: Exigences d'installation (ISO 4064-5:2014)
L'ISO 4064-5:2013 s'applique aux compteurs d'eau utilisés pour mesurer le volume d'eau potable froide et d'eau chaude s'écoulant dans une conduite fermée et à pleine charge. Ces compteurs d'eau comportent des dispositifs indiquant le volume compté.
L'ISO 4064-5:2013 spécifie des critères pour le choix de compteurs d'eau individuels, combinés et concentriques, les accessoires associés, l'installation ainsi que des exigences spéciales pour la première mise en service de compteurs neufs ou réparés pour garantir un mesurage d'une exactitude constante et une lecture fiable du compteur.
En plus des compteurs dont le fonctionnement est basé sur des principes mécaniques, l'ISO 4064-5:2013 s'applique aussi aux compteurs d'eau dont le fonctionnement est basé sur un principe électrique ou électronique, ainsi qu'aux compteurs d'eau à fonctionnement mécanique incluant des dispositifs électroniques utilisés pour mesurer le volume débité d'eau chaude et d'eau potable froide. Elle s'applique également aux dispositifs électroniques auxiliaires. Les dispositifs auxiliaires sont facultatifs. Cependant, des réglementations nationales ou internationales peuvent rendre certains dispositifs auxiliaires obligatoires selon l'utilisation du compteur d'eau.
Les recommandations de l'ISO 4064-5:2013 s'appliquent aux compteurs d'eau, indépendamment de leur technologie, définis en tant qu'instruments de mesure totalisateurs de débit, déterminant de manière continue le volume de débit d'eau les traversant.
Vodomeri za merjenje hladne pitne vode in vroče vode - 5. del: Zahteve za vgradnjo (ISO 4064-5:2014)
Ta del standarda ISO 4064 se uporablja za vodomere za merjenje pretoka hladne pitne vode in vroče vode, ki teče skozi zaprto cev s polnim pretokom. Ti vodomeri imajo vgrajene naprave, ki prikazujejo vgrajen pretok.
Ta del standarda ISO 4064 določa merila za izbor enojnih, kombiniranih in koncentričnih vodomerov, povezane fitinge, namestitev, posebne zahteve za vodomere in prvo delovanje novih ali popravljenih vodomerov, da se zagotovi točne stalno merjenje in zanesljivo odčitavanje vodomera. Poleg mehansko delujočih vodomerov se ta del standarda ISO 4064 uporablja za električno ali elektronsko delujoče vodomere in vodomere, delujoče na podlagi mehanskih načel z vgrajenimi elektronskimi napravami, ki se uporabljajo za merjenje pretoka hladne pitne vode in vroče vode. Uporablja se tudi za elektronske pomožne naprave. Pomožne naprave so izbirne. Kljub temu lahko nacionalni ali mednarodni predpisi določajo obvezno uporabo nekaterih pomožnih naprav v povezavi z uporabo vodomerov. Priporočila iz tega dela standarda ISO 4064 veljajo za vodomere, ki so opredeljeni kot integrirani merilni instrumenti za konstantno določanje pretoka vode, ki teče skoznje, ne glede na tehnologijo.
OPOMBA Veljajo vsi nacionalni predpisi v državi uporabe
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN ISO 4064-5:2015
01-marec-2015
1DGRPHãþD
SIST EN 14154-1:2005+A1:2007
SIST EN 14154-1:2005+A2:2011
SIST EN 14154-2:2005+A1:2007
SIST EN 14154-2:2005+A2:2011
SIST EN 14154-3:2005+A1:2007
SIST EN 14154-3:2005+A2:2011
9RGRPHUL]DPHUMHQMHKODGQHSLWQHYRGHLQYURþHYRGHGHO=DKWHYH]D
YJUDGQMR,62
Water meters intended for the metering of cold potable water and hot water - Part 5:
Installation requirements (ISO 4064-5:2014)
Wasserzähler zum Messen von kaltem Trinkwasser und heißem Wasser - Teil 5:
Einbaubedingungen (ISO 4064-5:2014)
Compteurs d'eau destinés au mesurage de l'eau potable froide et chaude - Partie 5:
Exigences d'installation (ISO 4064-5:2014)
Ta slovenski standard je istoveten z: EN ISO 4064-5:2014
ICS:
17.120.10 Pretok v zaprtih vodih Flow in closed conduits
91.140.60 Sistemi za oskrbo z vodo Water supply systems
SIST EN ISO 4064-5:2015 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN ISO 4064-5:2015
---------------------- Page: 2 ----------------------
SIST EN ISO 4064-5:2015
EUROPEAN STANDARD
EN ISO 4064-5
NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2014
ICS 91.140.60 Supersedes EN 14154-2:2005+A2:2011
English Version
Water meters for cold potable water and hot water - Part 5:
Installation requirements (ISO 4064-5:2014)
Compteurs d'eau potable froide et d'eau chaude - Partie 5: Wasserzähler zum Messen von kaltem Trinkwasser und
Exigences d'installation (ISO 4064-5:2014) heißem Wasser - Teil 5: Einbaubedingungen (ISO 4064-
5:2014)
This European Standard was approved by CEN on 21 September 2013.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN ISO 4064-5:2014 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN ISO 4064-5:2015
EN ISO 4064-5:2014 (E)
Contents Page
Foreword .3
2
---------------------- Page: 4 ----------------------
SIST EN ISO 4064-5:2015
EN ISO 4064-5:2014 (E)
Foreword
This document (EN ISO 4064-5:2014) has been prepared by Technical Committee ISO/TC 30 “Measurement
of fluid flow in closed conduits” in collaboration with Technical Committee CEN/TC 92 “Water meters” the
secretariat of which is held by SNV.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by December 2014, and conflicting national standards shall be withdrawn
at the latest by June 2017.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 14154-2:2005+A2:2011.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
Endorsement notice
The text of ISO 4064-5:2014 has been approved by CEN as EN ISO 4064-5:2014 without any modification.
3
---------------------- Page: 5 ----------------------
SIST EN ISO 4064-5:2015
---------------------- Page: 6 ----------------------
SIST EN ISO 4064-5:2015
INTERNATIONAL ISO
STANDARD 4064-5
First edition
2014-06-01
Water meters for cold potable water
and hot water —
Part 5:
Installation requirements
Compteurs d’eau potable froide et d’eau chaude —
Partie 5: Exigences d’installation
Reference number
ISO 4064-5:2014(E)
©
ISO 2014
---------------------- Page: 7 ----------------------
SIST EN ISO 4064-5:2015
ISO 4064-5:2014(E)
COPYRIGHT PROTECTED DOCUMENT
© ISO 2014
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form
or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior
written permission. Permission can be requested from either ISO at the address below or ISO’s member body in the country of
the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2014 – All rights reserved
---------------------- Page: 8 ----------------------
SIST EN ISO 4064-5:2015
ISO 4064-5:2014(E)
Contents Page
Foreword .iv
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Criteria for the selection of water meters . 2
4.1 General considerations . 2
4.2 Information to be provided by the manufacturer . 2
4.3 Meters operating in parallel or in a group . 2
5 Associated fittings . 3
5.1 General . 3
5.2 Upstream of the meter . 3
5.3 Downstream of the meter . 3
6 Installation . 4
6.1 General requirements . 4
6.2 Installation requirements . 4
6.3 Water quality (suspended particles) . 5
6.4 Electromagnetic meters . 5
6.5 Meters operating in parallel or in a group . 5
6.6 Security of operation . 5
7 Hydraulic disturbances . 5
7.1 General considerations . 5
7.2 Methods to eliminate disturbances . 6
8 First operation of new or repaired water meters . 7
8.1 General considerations . 7
8.2 Meters operating in parallel or in a group . 7
8.3 Protection of the meter . 7
8.4 Safety of personnel and users . 9
8.5 Comfort of personnel — Access to the water meter and fittings .10
Bibliography .12
© ISO 2014 – All rights reserved iii
---------------------- Page: 9 ----------------------
SIST EN ISO 4064-5:2015
ISO 4064-5:2014(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2, www.iso.org/directives.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of any
patent rights identified during the development of the document will be in the Introduction and/or on
the ISO list of patent declarations received, www.iso.org/patents.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
The committee responsible for this document is ISO/TC 30, Measurement of fluid flow in closed conduits,
Subcommittee SC 7, Volume methods including water meters. It supersedes ISO 4064-2:2005, which has
been technically revised.
ISO 4064 consists of the following parts, under the general title Water meters for cold potable water and
hot water:
— Part 1: Metrological and technical requirements
— Part 2: Test methods
— Part 3: Test report format
— Part 4: Non-metrological requirements not covered in ISO 4064-1
— Part 5: Installation requirements
iv © ISO 2014 – All rights reserved
---------------------- Page: 10 ----------------------
SIST EN ISO 4064-5:2015
INTERNATIONAL STANDARD ISO 4064-5:2014(E)
Water meters for cold potable water and hot water —
Part 5:
Installation requirements
1 Scope
This part of ISO 4064 applies to water meters used to meter the volume of cold potable water and hot
water flowing through a fully charged, closed conduit. These water meters incorporate devices which
indicate the integrated volume.
This part of ISO 4064 specifies criteria for the selection of single, combination and concentric water
meters, associated fittings, installation, special requirements for meters, and the first operation of new
or repaired meters to ensure accurate constant measurement and reliable reading of the meter.
In addition to meters based on mechanical principles, this part of ISO 4064 also applies to water
meters based on electrical or electronic principles, and to water meters based on mechanical principles
incorporating electronic devices, used to measure the volume of cold potable water and hot water. It also
applies to electronic ancillary devices. Ancillary devices are optional. However, national or international
regulations may make some ancillary devices mandatory in relation to the utilization of the water meter.
The recommendations of this part of ISO 4064 apply to water meters, irrespective of technology, defined
as integrating measuring instruments continuously determining the volume of water flowing through
them.
NOTE Any national regulations apply in the country of use.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
ISO 4064-1:2014|OIML R 49-1:2013, Water meters for cold potable water and hot water — Part 1:
Metrological and technical requirements
ISO 6817, Measurement of conductive liquid flow in closed conduits — Method using electromagnetic
flowmeters
3 Terms and definitions
For the purposes of this part of ISO 4064, the definitions given in ISO 4064-1|OIML R 49-1 and the
following apply.
3.1
parallel operation
operation of two or more meters grouped together and connected to a common source
and a common delivery
3.2
multiple meter operation
operation of several meters grouped together where their inlets are connected to a common source, or
their outlets to a common delivery, but not both at the same time
© ISO 2014 – All rights reserved 1
---------------------- Page: 11 ----------------------
SIST EN ISO 4064-5:2015
ISO 4064-5:2014(E)
3.3
adaptor
additional mechanical device fitted into a connection interface on location in order
to combine an unmodified cartridge meter of one geometry with a connection interface of another
geometry
3.4
converter
connection interface consisting of several parts produced as a complete unit prior to
installation into the supply system
Note 1 to entry: No assembly work is to be done on location other than the installation of the complete interface.
Conversion is related to either change of flow pattern, change of flow direction or extension of seat depth.
4 Criteria for the selection of water meters
4.1 General considerations
The type, metrological characteristics, and sizes of water meters should be determined according to the
operating conditions of the installation and the environmental class(es) demanded, taking into account,
particularly, the following:
— the available supply pressure;
— the physical and chemical characteristics of the water, including water temperature and water
quality (suspended particles);
— the acceptable pressure loss across the meter;
— the expected flow rates: the flow rates Q and Q of the meter (as defined in ISO 4064-1:2014|OIML R 49-
1 3
1:2013, Clause 3) shall be compatible with the expected flow rate conditions of the installations,
including the water flow direction(s);
— the suitability of the meter type for the intended mechanical, climatic, electrical, and hydraulic
conditions, including ambient relative humidity, vibrations, electrostatic discharges, continuous
magnetic field, and electromagnetic disturbances;
— the available space and pipe work to install the meter and fittings;
— the possibility of deposition of substances from solution within the meter;
— the sustainability of the power supply of the water meter (where applicable).
When using combination meters, changeover flow rates shall be different from normal operating flow
rates.
4.2 Information to be provided by the manufacturer
Sufficient information shall be provided to enable customers to choose and install a meter that conforms
to particular metrological characteristics.
The influence factors that affect the indicating error of the individual design should be stated. For each
influence factor, the relevant rated operating conditions applicable to the meter should be stated.
4.3 Meters operating in parallel or in a group
4.3.1 For meters operating in parallel, means shall be provided so that the unserviceability of one or
more meters within a group shall not cause the remaining meters to operate at a flow rate in excess of the
limit of operation of each individual meter.
2 © ISO 2014 – All rights reserved
---------------------- Page: 12 ----------------------
SIST EN ISO 4064-5:2015
ISO 4064-5:2014(E)
4.3.2 To ensure that water meters of different types operate satisfactorily in parallel, the individual
characteristics of meters operating in parallel shall be compatible, e.g. by grouping them according to
pressure loss, flow rate range and maximum working pressure. However, the installation conditions for
each type shall be respected.
4.3.3 For meters operating in parallel and multiple meter operation, the possibilities of interaction
between one meter or meter type and another to the detriment of their life and accuracy, e.g. pressure
surges and vibration, should be considered.
NOTE Examples of the use of meters operating in parallel and multiple meter operation are:
— meters operating in parallel where the installation of one large meter to meet the maximum water demand
or to cover the required flow rate range is impractical;
— meters installed in parallel where ‘stand by’ meters are necessary to ensure continuity of delivery and flow
measurement in the case of filter blockage or water meter breakdown;
— meters grouped in multiple operation for ease of access, service and reading, where it is necessary to split a
water supply into a number of branches, as for instance in a block of flats, or where it is necessary to unite a
number of metered tributary flows into a common main, as in a water treatment plant.
5 Associated fittings
5.1 General
The water meter installation shall include the associated fittings listed in 5.2 and 5.3 as applicable.
5.2 Upstream of the meter
5.2.1 A stopcock or valve, optionally with the direction of the valve operation indicated.
5.2.2 A flow straightening device and/or a length of straight pipe fitted between the valve and the
meter.
5.2.3 A strainer fitted between the stop valve and the meter.
5.2.4 A means of sealing the connection of the water meter to the water supply line in order to detect
any unauthorized removal of the water meter.
5.3 Downstream of the meter
5.3
...