SIST EN 12817:2002
(Main)LPG equipment and accessories - Inspection and requalification of LPG tanks up to and including 13 m3 overground
LPG equipment and accessories - Inspection and requalification of LPG tanks up to and including 13 m3 overground
This European Standard specifies requirements for:
a) routine inspection, periodic inspection and requalification of fixed above ground LPG storage tanks of sizes from 150 l up to and including 13 m3, and associated fittings;
b) marking tanks and/or keeping records, as appropriate, as a result of routine inspection, periodic inspection and requalification.
This European Standard excludes refrigerated storage.
Flüssiggas-Geräte und Ausrüstungsteile - Instandhaltung und wiederkehrende Prüfung von Behältern für Flüssiggas (LPG) mit einem Fassungsraum bis einschließlich 13 m3 - Oberirdische Aufstellung
Diese Europäische Norm legt Anforderungen fest für:
a) die Instandhaltung, regelmäßige Prüfung und wiederkehrende Prüfung von ortsfesten oberirdischen Behältern für Flüssiggas (LPG) mit einem Fassungsraum von 150 l bis einschließlich 13 m3 sowie der zugehörigen Aus-rüs-tung;
b) die Kennzeichnung von Behältern und/oder Aufbewahrung der Beurkundungen der Resultate aus Instand-hal-tung, regelmäßiger Prüfung und wiederkehrender Prüfung.
Diese Norm gilt nicht für die Lagerung von tiefkalten Gasen.
Equipements pour GPL et leurs accessoires - Inspection et requalification de réservoirs GPL aériens de capacité inférieure ou égale a 13 m3
La présente Norme européenne spécifie les prescriptions concernant les points suivants :
a) l'inspection de routine, l'inspection périodique et la requalification de réservoirs fixes aériens de stockage de GPL, d'une capacité comprise entre 150 l et 13 m3 inclus, et les équipements associés;
b) le marquage des réservoirs et/ou les informations a conserver, en tant que de besoin au terme de l'inspection de routine, de l'inspection périodique et de la requalification.
La présente Norme européenne exclut les stockages réfrigérés.
Pregledi in periodični preskusi rezervoarjev za utekočinjeni naftni plin (UNP) nadzemne izvedbe z notranjo prostornino do vključno 13 m3
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Flüssiggas-Geräte und Ausrüstungsteile - Instandhaltung und wiederkehrende Prüfung von Behältern für Flüssiggas (LPG) mit einem Fassungsraum bis einschließlich 13 m3 - Oberirdische AufstellungEquipements pour GPL et leurs accessoires - Inspection et requalification de réservoirs GPL aériens de capacité inférieure ou égale a 13 m3LPG equipment and accessories - Inspection and requalification of LPG tanks up to and including 13 m3 overground23.020.30MHNOHQNHPressure vessels, gas cylindersICS:Ta slovenski standard je istoveten z:EN 12817:2002SIST EN 12817:2002en01-november-2002SIST EN 12817:2002SLOVENSKI
STANDARD
SIST EN 12817:2002
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 12817May 2002ICS 23.020.30English versionInspection and requalification of LPG tanks up to and including13 m³ overgroundInspection et requalification de réservoirs aériens decapacité inférieure ou égale à 13 m³ pour gaz de pétroleliquéfiés (GPL)Instandhaltung und wiederkehrende Prüfung von Behälternfür Flüssiggas (LPG) mit einem Fassungsraum biseinschließlich 13 m³ in oberirdischer AufstellungThis European Standard was approved by CEN on 25 October 2001.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2002 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 12817:2002 ESIST EN 12817:2002
EN 12817:2002 (E)2ContentspageForeword.4Introduction.51Scope.52Terms and definitions.53Safety.63.1Safety precautions.63.2Unsafe conditions.63.3Leaks.64Written scheme.65Tank inspection and requalification.75.1Routine inspection.75.2Periodic inspection.75.3Requalification.76Inspection of tank and tank fittings.86.1Tank.86.2Tank fittings and immediate pipework.86.3Valve cover.86.4Bonding.86.5Pressure relief valve.96.6Pressure gauge.96.7Contents gauges.96.8Shut-off valves.96.9Studs, bolts, nuts, and washers.97Site inspection.97.1Storage site.97.2Piers and foundations.107.3Warning notices.108Competence.108.1Routine inspection.108.2Periodic inspection.108.3Requalification.109Records.109.1Tank data.109.2Reports.10Annex A (informative)
Visual inspection.12A.1Internal and external visual inspections.12A.2Inspection techniques.12A.2.1External inspection.12A.2.2Internal inspection.12A.3Records.12A.4Additional inspection.12Annex B (informative)
Hydraulic pressure test.14Annex C (informative)
Acoustic emission testing.15C.1General.15C.2Safety precautions.15SIST EN 12817:2002
EN 12817:2002 (E)3C.3Acceptance criteria.15Annex D (informative)
Ultrasonic thickness test.17D.1General.17D.2Apparatus setting.17D.3Control measurement.17D.4Shell thickness measurements.17D.5End thickness.17D.6Interpretation.17D.7Rejection criteria.18Annex E (informative)
Assessment of tanks by sampling.19E.1General.19E.2Homogeneous batch.19E.3Selection of samples.19E.4Sample selection.20E.5Inspection period.20E.6Presentation of results and decisions.20E.7Pass criteria.20E.8Example calculation of a sample.20Annex F (informative)
Example of a report.22Annex ZA
(informative)
A–deviations.23SIST EN 12817:2002
EN 12817:2002 (E)4ForewordThis document EN 12817:2002 has been prepared by Technical Committee CEN/TC 286 "Liquefied petroleum gasequipment and accessories", the secretariat of which is held by NSAI.This European Standard shall be given the status of a national standard, either by publication of an identical text orby endorsement, at the latest by November 2002, and conflicting national standards shall be withdrawn at the latestby November 2002.In this standard annexes A, B, C, D, E, F and ZA are informative.Users of this standard, prepared in the field of application of Article 118A of the EC Treaty, should be aware thatstandards have no formal legal relationship with Directives that may have been made under Article 118A of theTreaty.
In addition, national legislation in the Member states may contain more stringent requirements than theminimum requirements of a Directive based on Article 118A.
Information on the relationship between the nationallegislation implementing Directives based on Article 118A and this EN may be given in a national foreword of thenational standard implementing this standard.According to the CEN/CENELEC Internal Regulations, the national standards organizations of the followingcountries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain,Sweden, Switzerland and the United Kingdom.SIST EN 12817:2002
EN 12817:2002 (E)5IntroductionPeriodic inspection and requalification regimes for overground LPG tanks up to and including 13 m3 havedeveloped in various countries in different ways, that range from defined to variable inspection periods withrequalification regimes achieved by various methods. This standard for periodic inspection and requalification isbased on European countries’ legislation and codes of practice and industry codes of practice. In addition, use ofLPG in different applications has encouraged the industry to approach the requirements for routine periodicinspection and requalification in different ways for each application.This European Standard calls for the use of substances and procedures that can be injurious to health if adequateprecautions are not taken. It refers to technical suitability and does not absolve the user from legal obligationsrelating to health and safety at any stage.It has been assumed in the drafting of this European Standard that execution of its provisions is entrusted toappropriately qualified and experienced people.1 ScopeThis European Standard specifies requirements for:a) routine inspection, periodic inspection and requalification of fixed above ground LPG storage tanks of sizesfrom 150 l up to and including 13 m3, and associated fittings;b) marking tanks and/or keeping records, as appropriate, as a result of routine inspection, periodic inspection andrequalification.This European Standard excludes refrigerated storage.2 Terms and definitionsFor the purposes of this European Standard, the following terms and definitions apply.2.1periodic inspectionexternal inspection of the visible parts of a tank and its fittings2.2routine inspectionexternal inspection of the visible parts of a tank and its fittings, carried out more frequently than periodic inspections2.3requalificationinspection/test carried out at intervals, typically at the time of a periodic inspection, in order to confirm that a tank isfit for a further period of service2.4competent bodyperson or corporate body, defined by a national competent authority, that, by appropriate qualification, training,experience, and resources, is able to make objective judgements related to inspection and testing of pressureequipment in LPG service2.5competent personperson who, by qualification, training, experience, and resources, is able to make objective judgements related toinspection and testing of pressure equipment in LPG serviceSIST EN 12817:2002
EN 12817:2002 (E)62.6national competent authorityorganization, recognized or appointed by a member state, that oversees safe operation of LPG pressure equipment2.7written schemedocument, prepared by a competent body, containing inspection information2.8commissioningpreparation for safe service2.9decommissioningremoving from service and safe preparation for inspection/test3 Safety3.1 Safety precautionsAppropriate safety precautions shall be taken during decommissioning, commissioning andinspection/requalification of a tank and its fittings.3.2 Unsafe conditionsAny unsafe condition observed by a competent person on the site of an LPG storage tank shall be reported to theperson responsible for safe operation of the tank/site, as appropriate, and action taken.3.3 LeaksAny leak discovered from the tank or its fittings shall be reported immediately to the person responsible for safeoperation of the tank.Action to make a tank or its fittings safe shall be taken by a competent person.NOTEMethods for detecting leaks include:— visual inspection;— smell;— listening;— use of gas detectors.4 Written scheme4.1Each tank and its fittings shall be included in a written scheme taking into account clauses 5 to 7.4.2If duties are shared between different parties, the written scheme shall clearly identify the respective areas ofresponsibility.4.3Intervals between inspections shall be determined by consideration of the following:¾ the design specification of the tank and its equipment;SIST EN 12817:2002
EN 12817:2002 (E)7¾ the corrosion protection system on the tank;¾ the system used to ensure that the LPG quality conforms to its specifications/standards, and that it does notcontain components damaging to the material of the tank or its fittings;¾ the level of control over the filling and maintenance of the tank.NOTEThe maximum period between requalifications should not normally be greater than 20 years, and if conditions arenot satisfactory the period should be reduced.4.4The written scheme shall contain the following information:¾ the maximum interval between inspections;¾ the parts to be inspected;¾ the nature of the inspection;¾ the critical parts t
...
Questions, Comments and Discussion