oSIST prEN 15269-20:2007
Extended application of test results for smoke control for doorsets and shutter assemblies - Part 20: Timber and steel hinged and pivoted doorsets
Extended application of test results for smoke control for doorsets and shutter assemblies - Part 20: Timber and steel hinged and pivoted doorsets
To draft an extended application of test results for fire resistance for doorsets and shutter assemblies - For smoke control doors in particular.
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und Rauchdichte von Türen, Toren und Verblendverschlüssen - Teil 20: Rauchdichte von Drehtüren aus Holz und Stahl sowie Verblendverschlüssen
Diese Europäische Norm behandelt einflügelige und zweiflügelige Drehflügeltüren aus Holz und Stahl sowie Verblendverschlüsse. Es wird die Methologie zur Erweiterung der Anwendung von Prüferergebnissen aus Prüfungen nach EN 1634-3 beschrieben.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung oder Prüfungen, kann der erweiterte Anwendungsbereich die Klassifizierungen der Rauchdichtheit bei Umgebungstemperatur (Sa) und die Rauchdichtheit bei erhöhter Temperatur (Sm) sowie einige oder alle der folgenden Bereiche abdecken:
a) verglaste Bauteile, Lüftungsgitter und/oder Ventilationsöffnungen;
b) Seitenteile, Oberteile oder obere Türblenden;
c) Türbeschläge;
d) dekorative Beschichtungen;
e) dämmschichtbildende Dichtungen, sowie Dichtungen zur Behinderung von Rauchdurchtritt (Rauchschutzdichtungen), Durchzug oder der Schallübertragung (Schallschutzdichtungen);
f) alternative Tragkonstruktionen.
ANMERKUNG Sofern eine Änderung in einem Parameter eines Türbeschlags vorgesehen ist, muss der Einfluss auf die Dauerfunktionstüchtigkeit/selbstschließende Eigenschaft nach EN 14600 mit berücksichtigt werden.
Application élargie des résultats d'essai en matiere d'étanchéité a la fumée des blocs-portes et des blocs-fermetures - Partie 20: Blocs-portes pivotants ou battants en bois et en acier
Razširjena uporaba rezultatov preskusov nadzora dima za vrata in zaporne elemente - 20. del: Lesena in jeklena vrata s tečaji
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
01-marec-2007
5D]ãLUMHQDXSRUDEDUH]XOWDWRYSUHVNXVRYQDG]RUDGLPD]DYUDWDLQ]DSRUQH
HOHPHQWHGHO/HVHQDLQMHNOHQDYUDWDVWHþDML
Extended application of test results for smoke control for doorsets and shutter
assemblies - Part 20: Timber and steel hinged and pivoted doorsets
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und
Rauchdichte von Türen, Toren und Verblendverschlüssen - Teil 20: Rauchdichte von
Drehtüren aus Holz und Stahl sowie Verblendverschlüssen
Application élargie des résultats d'essai en matiere d'étanchéité a la fumée des blocs-
portes et des blocs-fermetures - Partie 20: Blocs-portes pivotants ou battants en bois et
en acier
Ta slovenski standard je istoveten z: prEN 15269-20
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
DRAFT
NORME EUROPÉENNE
EUROPÄISCHE NORM
December 2006
ICS
English Version
Extended application of test results for smoke control for
doorsets and shutter assemblies - Part 20: Timber and steel
hinged and pivoted doorsets
Application élargie des résultats d'essai en matière
d'étanchéité à la fumée des blocs-portes et des blocs-
fermetures - Partie 20: Blocs-portes pivotants ou battants
en bois et en acier
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,
Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2006 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15269-20:2006: E
worldwide for CEN national Members.
Contents Page
Foreword.3
1 Scope.3
2 Normative references.4
3 Definitions.4
4 Determination of the field of extended application.4
4.1 General.4
4.2 Procedure for evaluation .5
4.3 Procedure for maximum field of extended application .5
4.4 Interpretation of Test Results.6
5 Extended application report .6
6 Classification report.6
Annex A (normative) Construction Parameter Variations .7
A.1 General.7
Figures referred to in Annex A.26
Annex B Arrangements for Doorsets incorporating Side and/pr Overpanels.32
Foreword
This document (prEN 15269-20:2006) has been prepared by Technical Committee CEN/TC 127 “Fire safety in
buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document is one of a series of Standards intended to be used by experts or competent bodies for the
purpose of producing an extended application report (EXAP). It is not intended to be used for the
interpretation of test results by non-fire experts.
NOTE Clarification is needed to establish if such experts are Bodies Notified for either testing and/or Certification
Part 1: General requirements for fire resistance;
Part 2: Fire resistance of steel hinged and pivoted doorsets;
Part 3: Fire resistance of timber hinged and pivoted doorsets;
Part 4: Fire resistance of glass hinged and pivoted doorsets;
Part 5: Fire resistance of metal framed glazed hinged and pivoted doorsets and openable windows;
Part 6: Fire resistance of timber sliding doorsets;
Part 7: Fire resistance of steel sliding doorsets;
Part 8: Fire resistance of timber horizontally folding;
Part 9: Fire resistance of steel horizontally folding doorsets;
Part 10: Fire resistance of Steel rolling shutter assemblies;
Part 20: Smoke control for all types of doorsets and shutter assemblies
1 Scope
assemblies. It prescribes the methodology for extending the application of test results obtained from test(s)
conducted in accordance with EN 1634-3.
Subject to the completion of the appropriate test or tests, the extended application may cover Ambient
Temperature Smoke Control (S ) and Medium Temperature Smoke Control (S ) classifications and all or some
a m
of the following :
a) glazed elements, louvres and/or vents;
b) side, transom or overpanels;
c) items of building hardware;
d) decorative finishes;
e) intumescent, smoke, draught or acoustic seals;
f) alternative supporting construction(s).
NOTE When considering a change in a parameter of building hardware, the effect on the durability of self-closing
shall be considered in accordance with EN 14600.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and
elements of building hardware’ Part 3: Smoke control test for door and shutter assemblies
EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification using
data from fire resistance tests excluding ventilation services
prEN 15269-1, Extended application of test results for fire resisting and smoke control doorsets and shutter
assemblies — Part 1, General requirements for fire resistance
prEN 14351-3, Windows and pedestrian doorsets – Product Standard – Part 3: Products with resistance to fire
and external fire characteristics
EN ISO 13943, Fire safety — Vocabulary
EN 14600, Doorsets and openable windows with fire resisting and/or smoke control characteristics -
Requirements and classification
3 Definitions
For the purposes of this part, the definitions given in EN1363-1, EN ISO 13943, EN 1634-1, EN 1634-3 and
prEN 15269-1 together with the following apply :
3.1
core
material fitted centrally within the thickness of a door leaf. It may consist of a single sheet of material or a
combination either of sheets of the same material or layers of different materials
4 Determination of the field of extended application
4.1 General
4.1.1 Before there can be any consideration for extended application the doorset shall have been tested
and classified in accordance with EN 1634-3 and EN 13501-2 respectively in order to establish a classification
for the doorset.
4.1.2 Evaluation to a higher classification is not possible.
4.1.3 All evaluations shall be made on the basis of retaining the classification obtained from testing to
EN1634-3.
4.1.4 If, by following the ensuing procedure, any part of the classification cannot be achieved by extended
application theory, that element of classification shall be omitted from the subsequent extended application
report and classification report.
4.2 Procedure for evaluation
4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an
extended application report.
4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of
Table A.1.
4.2.3 Review the type of classification to be retained from column (3) of Table A.1 and establish from the
contents of column (4) of Table A.1 whether any extended application is available without the need for further
testing.
4.2.4 Where this is possible this can be recorded in the extended application report together with any
appropriate restrictions and the stated rules from column (4) in Table A.1.
4.2.5 Where the variations required can only be achieved from additional testing, the additional test can be
made on another door from the same product family including the required variation against which the
extended application is sought. Alternatively, column (5) in Table A.1 identifies an option for alternative testing
and relevant test parameters.
4.2.6 It is a requirement of this document that all items of building hardware are in accordance with the
relevant product standard and that the door assembly onto which the building hardware will be fitted is
appropriate to that class of use.
4.3 Procedure for maximum field of extended application
4.3.1 It is possible to provide an extended field of application from a single test. However, where a
manufacturer envisages to manufacture a range of doors incorporating single doors and also double doors
with or without side, transom or over panels, with or without glazing, louvres or ventilation grilles, with
alternative element of building hardware, etc., it is recommended that careful consideration is given to the
complete range of doorset designs and options in order to minimise the testing required before testing
commences.
4.3.2 Establish all the parameter variations which are required to be part of the product ‘family’, and in
particular for single leaf hinged or pivoted timber based doorsets into rebated frames.
4.3.3 Determine which are the most important specification requirements and incorporate as many as
possible into the specimen(s) for the first tests in the series.
4.3.4 Complete the first test or a series of tests and prepare a field of direct application and a classification
report from the results of the test(s).
4.3.5 Establish which of the original desired parameter variations have not been covered by the direct
application classification report.
4.3.6 Identify these parameter variations using Table A.1 and establish where an extended application is
possible with the available test evidence.
4.3.7 Record this for the extended application report together with any restrictions and rules given in
column (5) in Table A.1.
4.3.8 Evaluate which, if any, of the desired parameter variations have not been covered by the field of
direct application or the initial field of extended application derived from 4.3.6.
4.3.9 Select the required outstanding parameter variations from column (1) and column (2) of Table A.1
and observe from column (5) in Table A.1 which are the most appropriate weakest specimen options for
further testing.
4.3.10 If the complete selection of required parameter variations have not been covered by the tests
completed in accordance with 4.3.8 and 4.3.9, then an appropriate test or tests may be carried out with the
additional product variations incorporated.
4.4 Interpretation of Test Results
4.4.1 In order to maximise the field of extended application, it is important that the test reports shall record
details of any failure throughout the duration of the test.
4.4.2 Where a series of tests have been conducted, the field of extended application shall be based on the
lowest performance achieved from the complete series of tests unless excessive leakage has been attributed
to one or more specific construction parameter variation.
4.4.3 Where it has been possible, to identify leakage due to a specific parameter, the extended application
for all other construction parameter variations can be based on the performance achieved after isolating the
parameter with excessive leakage.
5 Extended application report
Prepare an extended application report in accordance with the requirements of Clause 5 of EXAP prEN
15269-1, based on the results of evaluations in accordance with the above.
6 Classification report
The classification report shall be determined from the results of the extended application report and
...