Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows

This document covers hinged or pivoted, doorsets with timber based leaves. It prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 5 the extended application may cover all or some of the following:
- uninsulated (E), radiation (EW) or insulated (EI1 or EI2) classifications;
- glazed elements, louvres and/or vents;
- side, transom or overpanels;
- items of building building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s);

Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren, Abschlüssen und Fenstern einschließlich ihrer Baubeschläge - Teil 3: Feuerwiderstandsfähigkeit von Drehflügeltüren und Fenstern aus Holz

Dieses Dokument behandelt Drehflügeltüreinheiten mit einem Flügel aus Holz bzw. Holzwerkstoff. Es beschreibt die Methodologie zur Erweiterung der Anwendung von Prüfergebnissen auf der Basis von Prüfungen nach EN 1634-1.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung oder Prüfungen, die in Abschnitt 5 aufgeführt sind, kann der erweiterte Anwendungsbereich einige oder alle der folgenden Bereiche abdecken:
-   Klassifizierungen von nichtwärmegedämmten Türeinheiten (E), sowie solchen mit Anforderungen an die Strahlung (EW) oder wärmegedämmten Türeinheiten (EI1 oder EI2);
-   verglaste Teilbereiche, Lüftungsgitter und/oder Ventilationsöffnungen;
-   Seitenteile, Oberteile oder obere Türblenden;
-   Türbeschläge;
-   dekorative Beschichtungen;
-   dämmschichtbildende Dichtungen, sowie Dichtungen zur Behinderung von Rauchdurchtritt, Durchzug oder der Schallübertragung;
alternative Tragkonstruktionen

Application élargie des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, fermetures et fenêtre, y compris leurs éléments de quincaillerie - Partie 3: Résistance au feu des blocs-portes battants et pivotants et des fenêtres à ossature bois

Le présent document couvre les blocs-portes pivotants ou battants avec vantaux à base de bois, les portes  menuisées/vitrées à ossature à dormant en bois et les ouvrants de fenêtres à dormant enossature bois. Il prescrit une méthode permettant d'étendre l'application des résultats du/des essai(s) effectué(s) conformément à l'EN 1634-1.
En fonction de l'exécution du/des essai(s) approprié(s), l'application élargie peut couvrir la totalité, ou certains, des exemples suivant :
-   classements non isolé (E), rayonnement (EW) ou isolé (EI1 ou EI2) ;
-   éléments vitrés/menuisés, jalousies et/ou évents ;
-   panneaux latéraux, panneaux d'imposte ou panneaux supérieursd'imposte affleurants ;
-   éléments de quincaillerie  de porte;
-   finitions décoratives ;
-   calfeutrements joints intumescents, d'étanchéitéétanches à la fumée, à l'air, ou acoustiques ;
-   autre(s) construction(s) support.

Razširjena uporaba rezultatov preskusov požarne odpornosti in/ali dimotesnosti za vrata, zapore in okna, ki se odpirajo, vključno z njihovim okovjem - 3. del: Požarna odpornost lesenih vrat in oken s tečaji

General Information

Status
Not Published
Public Enquiry End Date
19-Mar-2009
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
22-Dec-2011
Due Date
27-Dec-2011
Completion Date
22-Dec-2011

Buy Standard

Draft
prEN 15269-3:2009
English language
66 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-marec-2009
5D]ãLUMHQDXSRUDEDUH]XOWDWRYSUHVNXVRYSRåDUQHRGSRUQRVWLLQDOLGLPRWHVQRVWL
]DYUDWD]DSRUHLQRNQDNLVHRGSLUDMRYNOMXþQR]QMLKRYLPRNRYMHPGHO
3RåDUQDRGSRUQRVWOHVHQLKYUDWLQRNHQVWHþDML
Extended application of test results for fire resistance and/or smoke control for door,
shutter and openable window assemblies, including their elements of building hardware -
Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber
framed windows
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit
und/oder Rauchdichtigkeit von Türen, Toren, Abschlüssen und Fenstern einschließlich
ihrer Baubeschläge - Teil 3: Feuerwiderstandsfähigkeit von Drehflügeltüren und Fenstern
aus Holz
Application élargie des résultats d'essais en matière de résistance au feu et/ou
d'étanchéité à la fumée des blocs-portes, fermetures et fenêtre, y compris leurs éléments
de quincaillerie - Partie 3: Résistance au feu des blocs-portes battants et pivotants et des
fenêtres à ossature bois
Ta slovenski standard je istoveten z: prEN 15269-3
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
DRAFT
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2008
ICS 13.220.50; 91.060.50
English Version
Extended application of test results for fire resistance and/or
smoke control for door, shutter and openable window
assemblies, including their elements of building hardware - Part
3: Fire resistance of hinged and pivoted timber doorsets and
openable timber framed windows
Application élargie des résultats d'essais en matière de
résistance au feu et/ou d'étanchéité à la fumée des blocs-
portes, fermetures et fenêtre, y compris leurs éléments de
quincaillerie - Partie 3: Résistance au feu des blocs-portes
battants et pivotants et des fenêtres à ossature bois
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15269-3:2008: E
worldwide for CEN national Members.

Contents Page
Foreword. 3
1 Scope. 4
2 Normative references . 4
3 Definitions. 5
4 Determination of the field of extended application . 5
4.1 General. 5
4.2 How to use the extended application rules in Annex A. 6
4.3 Procedure for maximum field of extended application. 6
4.4 Analysis of test results. 7
5 Extended application report . 7
6 Classification report . 7
Annex A (normative) Construction parameter variations . 8
Annex B (normative) Arrangements for doorsets incorporating side and/or overpanels. 62

Foreword
This document (prEN 15269-3:2008) has been prepared by Technical Committee CEN/TC 127 “Fire
safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission and
the European Free Trade Association, and supports essential requirements of EC Directive(s).
This document is one of a series entitled “prEN 15269 Extended application of test results for fire
resistance and/or smoke control for door, shutter and openable window assemblies, including their
elements of building hardware” which consists of the following:
Part 1: General requirements
Part 2: Fire resistance of hinged and pivoted steel doorsets
Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows
Part 4: Fire resistance of hinged and pivoted glass doorsets
Part 5: Fire resistance of hinged and pivoted, metal framed, glazed doorsets and openable windows
Part 6: Fire resistance of sliding timber doorsets
Part 7: Fire resistance of sliding steel doorsets
Part 8: Fire resistance of horizontally folding timber doorsets
Part 9: Fire resistance of horizontally folding steel doorsets
Part 10: Fire resistance of steel rolling shutters
Part 11: Fire resistance of fabric curtains
Part 20: Smoke control for hinged and pivoted timber and steel doorsets

1 Scope
This document covers hinged or pivoted doorsets with timber based leaves, timber framed glazed
doors and openable timber framed windows. It prescribes the methodology for extending the
application of test results obtained from test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests the extended application may cover all or
some of the following examples:
 uninsulated (E), radiation (EW) or insulated (EI or EI ) classifications;
1 2
 glazed elements, louvres and/or vents;
 side, transom or overpanels;
 items of building hardware;
 decorative finishes;
 intumescent, smoke, draught or acoustic seals;
 alternative supporting construction(s).
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies.
EN 844, Round and sawn timber — Terminology
EN 179, Building hardware — Emergency exit devices operated by a lever handle or push pad —
Requirements and test methods
EN 1125, Building hardware — Panic exit devices operated by a horizontal bar — Requirements and
test methods
EN 1363-1, Fire resistance tests — Part 1: General requirements
EN 1634-1, Fire resistance and smoke control tests for door, shutter and openable window
assemblies and elements of building hardware — Part 1: Fire resistance test for door, shutter and
openable window assemblies
prEN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window
assemblies and elements of building hardware - Part 2: Fire resistance characterisation test for
elements of building hardware
EN 12519, Windows and pedestrian doors — Terminology
EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification
using test data from fire resistance tests excluding ventilation services
EN ISO 13943, Fire safety — Vocabulary
EN 15254-4 Extended application of results from fire resistance tests — Non-loadbearing walls
— Part 5: Glazed constructions
prEN 15269-1, Extended application of test results for fire resistance and/or smoke control for door,
shutter and openable window assemblies, including their elements of building hardware —
Part 1: General Requirements
3 Definitions
For the purposes of this part, the definitions given in EN 1363-1, EN 12519, ISO 13943, EN 1634-1,
prEN 1634-2 and prEN 15269-1 together with the following apply:
3.1
core
material fitted centrally within the thickness of a door leaf. It may consist of a single sheet of material
or a combination either of sheets of the same material or layers of different materials
3.2
effective rebate depth
dimension of the door leaf thickness of overlapping adjacent edges of door leaf relative to the door
frame, transom or side panel or flush overpanel. At the meeting edges and for rebated leaves the
dimension shall be the depth of the largest rebate or the rebate where the intumescent seal is fitted
3.3
leaf symmetry
construction of a door leaf, without consideration of any leaf edge rebates, viewed either side of an
imaginary plane drawn centrally in the thickness of the leaf. A symmetrical door leaf will be identical
either side of this imaginary plane, whilst an asymmetrical door leaf will differ
4 Determination of the field of extended application
4.1 General
4.1.1 Before there can be any consideration for extended application, the doorset shall have been
tested in accordance with EN 1634-1 to achieve a test result which could generate a classification in
accordance with EN 13501-2 at least equal to the classification subsequently required from extended
application considerations.
4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics
may be improved by a particular parameter variation. All evaluations shall be made on the basis of
retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test
duration. However, this shall never lead to an increased classification for any specific parameter
beyond that achieved during any one test unless specifically identified in the relevant Construction
Parameter Variation tables.
4.1.3 If, when following the extended application procedure, any part of the classified product
cannot be covered by the extended application rules then that part shall be omitted from the
subsequent extended application report and classification report.
4.1.4 The effect on the durability of self closing of the doorsets following an extended application
process is not addressed in this series of documents.
4.2 How to use the extended application rules in Annex A
4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by
an extended application report.
4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and
(2) of Annex A.
4.2.3 Review the type of classification to be retained from column (3) of Annex A and establish from
the contents of column (4) of Annex A whether any extended application is available beyond the direct
application rules in EN 1634-1 without the need for further testing.
4.2.4 Where this is deemed to be possible it can be recorded in the extended application report
together with any appropriate restrictions and the stated rules from column (4) of Annex A.
4.2.5 Where the variations required can only be achieved from additional testing, the additional test
can be made on a similar specimen type (e.g. single-leaf doorset) to the original test against which the
extended application is sought. Alternatively, column (5) of Annex A identifies an option for alternative
testing and relevant test parameters.
4.3 Procedure for maximum field of extended application
4.3.1 It is possible to provide an extended field of application from a single test. However, where a
manufacturer envisages to manufacture a range of doors incorporating single doors and also double
doors with or without side, transom or over panels, with or without glazing, louvres or ventilation
grilles, with alternative element of building hardware, etc., it is recommended that careful
consideration is given to the complete range of doorset designs and options in order to minimise the
testing required before testing commences.
4.3.2 Establish all the parameter variations which are required to be part of the product range.
4.3.3 Determine which are the most important specification requirements and incorporate as many
as possible into the specimen(s) for the first tests in the series.
4.3.4 Conduct the first test or a series of tests and then establish which of the original desired
parameter
...

Questions, Comments and Discussion